11

5.4  

Heating element

Each actuator includes a heating resistor.
As soon as the actuator is installed in the field, it is recommended
to power the resistor to prevent condensation.

Immediately put  the cover back  in place after start-up while

ensuring its seal is clean. Never leave actuator electrical

components without their protection cover.

In case of water intrusion:

Dry electrical components before putting back the cover.

Check electrical insulation.

6 TRAVEL LIMIT SETTINGS

The actuator is factory-set for a 90°travel.
It features 2 devices to limit the travel:

Cams trigger switches to switch off power at an end position or

to signal a position

Mechanical stops mechanically block rotation to protect the valve

in case of over-travel. 

They must not be used as travel limits.

Single cam setting

The cam rotates with  the 

output shaft and 

triggers a switch by 

pushing on its lever. 

Cams orientation are factory

 

pre-set, yet you can still

re-adjust them 

during  the

 commissioning

if

 necessary.

Rep.

Function

Status before installation

1

Clockwise travel limit

Pre-wired, cam pre-set

2

Counter-clockwise travel limit

Pre-wired, cam pre-set

3

Clockwise signaling

To wire, to set

4

Counter-clockwise signaling

To wire, to set

  

12

Содержание 215.3842.6.11 171.8093.1L.13

Страница 1: ...1 AQ SWITCH RANGE Start Up Guide Instructions de mise en service SUG_17003 Ind A Art 5100466...

Страница 2: ...on 4 EMERGENCY HANDWHEEL OPERATION 6 5 ELECTRICAL COMMISSIONNING 6 5 1 Connection and preliminary tests 5 2 Position feedback potentiometer OPTION 5 3 TAM position transmitter OPTION 5 4 Heating resis...

Страница 3: ...Avoid placing the actuator directly on the floor Check that plugs on cable entries are correctly tightened Check that cover screws are correctly tightened to ensure weatherproof sealing of the cover...

Страница 4: ...not in service increases the risk of malfunction This is not advisable If a long term storage is absolutely necessary we strongly recommend a revision of the electronic boards in our factory before a...

Страница 5: ...be oriented upwards loss of water tightness Changing closing direction indication As a standard AQ actuator is configured to close clockwise If the actuator must close counter clockwise you can change...

Страница 6: ...nd preliminary tests 8 Capacitor 7 Switches board 6 Torque limiter 5 Motor 4 Heating resistance 3 Cams 2 Terminal block 1 Position indicator Actuator and its components are wired to internal terminal...

Страница 7: ...nd check that the motor rotates in the right direction 5 Manually press on the counter clockwise travel limit switch then the motor should stop 6 Repeat steps 4 and 5 for clockwise direction If any fa...

Страница 8: ...eases then turn backwards to reach the closest value to 0 Ohm Tighten back the positioner pinion blocking screw 4 Drive the actuator to the OPEN position and write down the resistance value correspond...

Страница 9: ...Maximum admissible resistance values are given in the following table DC supply volts Max admissible resistance ohms 12 150 24 750 32 1050 Signal direction inversion The TAM transmitter when supplied...

Страница 10: ...stop as soon as the minimum value determined here above is reached and tighten back the potentiometer pinion blocking screw The potentiometer is then positioned at the very beginning of its track 6 Th...

Страница 11: ...for a 90 travel It features 2 devices to limit the travel Cams trigger switches to switch off power at an end position or to signal a position Mechanical stops mechanically block rotation to protect t...

Страница 12: ...osition when the travel limit switch is tripped Travel limit settings The mechanical stops 1 counter clockwise 2 clockwise avoid over travel in case of handwheel operation They can be set on the actua...

Страница 13: ...the cam corresponding to clockwise travel limit switch Clockwise signaling switch cam setting if wired 6 Drive slightly the output in the counter clockwise direction using manual override 7 Set the ca...

Страница 14: ...ue limiter operation Please check below torque limiter setting components 5 Clockwise direction cam 4 Clockwise direction switch 3 Counter clockwise direction cam 2 Counter clockwise direction switch...

Страница 15: ...BERNARD CONTROLS BENELUX NIVELLES BRUSSELS inquiry belgium bernardcontrols com inquiry holland bernardcontrols com Tel 32 0 2 343 41 22 FRANCE BERNARD CONTROLS FRANCE BERNARD CONTROLS NUCLEAR FRANCE G...

Отзывы: