Bryant THERMIDISTAT CONTROL TSTAT Скачать руководство пользователя страница 5

5

requires prior selection of heat pump (DIP switch 1 ON), and
must be selected in Hybrid Heat installations. It prevents

simultaneous operation of both furnace and heat pump, and
prevents direct transition from heat pump to furnace operation.

When system is Hybrid Heat (heat pump and furnace), set to ON.

When system contains fan coil, set to OF. Factory default is OF
(off).

TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down

buttons to make small (now flashing) display indicate 10.

2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to alternate between OF and ON

on large display. Factory default is OF.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to
exit configuration mode.

Option 11—Balance Point Setting

This option is for Hybrid Heat installations only. It requires prior

selection of heat pump (DIP switch 1 ON) and Hybrid Heat
equipment (Option 10 ON). It allows selection of an outdoor

temperature of 5

_

F through 55

_

F (or equivalent values in C), or

OF (off). Heat pump is prevented from operating for outdoor

temperatures below selected temperature. If OF (off) is selected,

heat pump operation is allowed at all outdoor temperatures.
Factory default is OF (off). This setting can only be equal to or

below the setting choice made for Option 8. Moving the setting
higher may push Option 8 setting upward. If the outdoor

temperature is above the “balance point setting”, the heat pump

will energize first to try to satisfy the indoor temperature demand.
If the heat pump does not make a sufficient improvement within a

reasonable time period (i.e. 15 minutes), then the gas furnace will
come on to satisfy the indoor temperature demand. If the outdoor

temperature is below the “balance point setting” the heat pump
will not be allowed to operate (i.e. locked out), and the gas

furnace will be used to satisfy the indoor temperature.
There are three separate concepts which are related to selecting
the final “balance point setting”. Read each of the following

carefully to determine the best “balance point setting” in a Hybrid
Heat installation:
CAPACITY BALANCE TEMPERATURE:

This is the point where the heat pump cannot provide sufficient
capacity to keep up with the indoor temperature demand because

of declining outdoor temperature. At or below this point, the
furnace is needed to maintain proper indoor temperature.
ECONOMIC BALANCE TEMPERATURE:

Above this point, the heat pump is the most cost efficient to
operate, and below this point, the furnace is the most cost efficient

to operate. This can be somewhat complicated to determine and it
involves knowing the cost of gas and electricity, as well as the

efficiency of the furnace and heat pump. For the most economical
operation, the heat pump should operate above this temperature

(assuming it has sufficient capacity), and the furnace should

operate below this temperature.
COMFORT BALANCE TEMPERATURE:

When the heat pump is operating below this point, the indoor
supply air feels uncomfortable (i.e. too cool). This is purely

subjective and will depend on the homeowner’s idea of comfort.

Below this temperature, the gas furnace should operate in order to
satisfy the desire of indoor comfort.
TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down
buttons to make small (now flashing) display indicate 11.

2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to move between OF, 5, 10, 15,

20, 25, 30, 35, 40, 45, 50, or 55 on large display. Factory
default is OF.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to
exit configuration mode.

Option 12—Defrost Heat Select

This option allows installer to select the amount of heat provided

by Thermidistat Control during a heat pump defrost cycle. This
can be very helpful in maintaining a comfortable leaving air

temperature during defrost. The Thermidistat Control senses

when defrost is in progress by monitoring voltage placed on the
O line by the heat pump while defrosting. It responds by turning

on selected combination of W1 and W2 during defrost. Note that
this is very different from the operation of an ordinary thermostat,

which cannot sense defrost in progress and only turns on its W
outputs in response to a temperature demand. Combinations of

W1 and W2 are selected via the following:

Table 1—W1/W2 Outputs

Selection

Definition

0

W1 nor W2 is turned on. This is factory default.

1

Only W1 is turned on.

2

Both W1 and W2 turned on.

3

Only W2 turned on (available only if 3---stage

heat is selected.

The selection procedure is given below. If 0 is selected, operation

is like that of an ordinary thermostat, and a wire is required
between W2 of outdoor unit and a selected W on indoor unit.

When selection 1, 2, or 3 is made, no wire should be connected
from outdoor W2 because this connection may override selection

made. Obviously the heater must be in 2 sections, and fan coil
jumper must be removed between W1 and W2 for there to be a

difference between selections 1, 2, and 3. For most heaters, W1 is

lower wattage heater, and W2 is higher, although some have
equal elements for W1 and W2. Consult fan coil/heater

combination for the actual wattage connected to each of W1 and
W2.
In Hybrid Heat applications, above selection choices apply and

can be used to select low or high heat if furnace is 2 stage. W1
will produce low heat. W1 and W2 together produce high heat.

This option provides no value with single--stage furnaces because
only 1 value of heat is available.
The selection choices guarantee selected outputs will be on

during defrost. If room temperature demand requires additional
heat, it will be supplied, resulting in additional outputs being

turned on. If room overheats, specified outputs will not turn off,
guaranteeing a sufficiently warm leaving air temperature during

defrost. Temperature overshoot during defrost can occur, but is
almost never noticeable because of the short duration of the

defrost cycle (4 minutes typical, 10 minutes maximum).
An additional feature of Thermidistat Control defrost is that it
always allows defrost cycle to run to completion. The

Thermidistat Control leaves the Y output on as long as outdoor
unit holds voltage on the O line, even if it is satisfied. This

prevents premature termination of defrost cycles, which occur

with normal thermostats.
TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down

buttons to make small (now flashing) display indicate 12.

2. Press SET TIME/TEMP button once to flash large display.

TST

AT

Содержание THERMIDISTAT CONTROL TSTAT

Страница 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Страница 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Страница 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Страница 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Страница 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Страница 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Страница 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Страница 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Страница 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Страница 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Страница 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Страница 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Страница 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Страница 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Отзывы: