UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Improper wiring or installation may damage Thermidistat

Control. Check to make sure wiring is correct before

proceeding with installation or turning on power.

CAUTION

!

On power up, all display segments will light for 5 sec. For the

next 5 sec a 2--digit code appears on large display which

identifies Thermidistat Control configuration:

1. AC—for 1--stage air conditioner
2. HP—for 1--stage heat pump
3. A2—for 2--stage air conditioner
4. H2—for 2--stage heat pump
5. dF—for 1--stage Hybrid Heat
6. d2—for 2--stage Hybrid Heat
7. HS—for 1--stage heat pump with Intelligent Heat Staging

(3--stage auxiliary heat with 40FK, FK4C, or FV4A Series
fan coils.)

When this identifier disappears, normal operation begins. The
MODE control should be set to OFF and FAN control to AUTO,

so equipment does not start until further configuration and

checkout is completed.

STEP 4

Set Thermidistat Control Configuration

Configuration options, like DIP switch settings, are intended to
be selected at installation and normally are not modified by the

homeowner. These options are not discussed in the homeowner’s
manual and therefore must be made as part of the installation. A

special procedure allows entry into the configuration mode.

While in configuration mode, up to 17 selections can be made. A
description of each selection and how to use the configuration

mode follows.
CONFIGURATION OPTIONS — SUMMARY:
Option 1—Anticipator adjustment
Option 2—Clean filter timer adjustment

Option 3—English/Metric selection

Option 4—Fan (G) ON with W selection
Option 5—Variable--stage blower present selection

Option 6—Cooling lockout below 55

_

selection

Option 7—Variable--stage super dehumidification selection (only

available when variable--stage blower is used)

Option 8—Auxiliary heat lockout temperature setting (only

available when heat pump is used)

Option 9—Intelligent Heat Staging selection (only available

when single--stage heat pump is used)

Option 10—Hybrid Heat selection (only available when heat

pump is used)

Option 11—Balance point setting (only available when

Hybrid Heat is selected)

Option 12—Defrost heat selection (only available when

heat pump is used)

Option 13—Room temperature offset adjustment

Option 14—Heat/cool dead band adjustment

Option 15—Enable Auto mode
Option 16—Enables Super Comfort Heat Mode

Option 17—Non--Programmable selection
TO ENTER CONFIGURATION MODE:
Press and hold FAN button for approximately 10 sec until COOL

set point display indicates a flashing 1. The Thermidistat Control
is now in configuration mode. It will automatically exit this mode

if no button is pressed for 3 minutes. Pressing END button will
exit configuration mode immediately.

WHILE IN CONFIGURATION MODE:
The upper small (COOL set point) display indicates selected

option number and large display indicates selection made within
that option. One of these will be flashing. The up and down

buttons are used both to move between available options and to

make selection for each option. When option number (small
display) is flashing, up and down buttons adjust it, moving

between available option numbers. After desired option number
has been selected, press SET TIME/TEMP button once. The

large display will now flash, indicating that up and down buttons

now control available choices within that option. Each press of
TIME/TEMP button switches between available option (small

display) and available selections within each option (large
display).
CONFIGURATION OPTIONS —SELECTION:

Option 1—Anticipator Adjustment

This adjustment controls sensitivity and cycle rate of Thermidistat

Control. Higher numbers decrease sensitivity and slow cycle rate.
Lower numbers increase sensitivity and cycle rate. However, a

limiting feature will not allow more than 4 cycles per hr,
regardless of setting. Anticipator values can range from 1 to 9.

Factory default is 3. This default selection provides optimum

performance in nearly all installations. Try it first. Do not change
setting unless there is evidence of need to do so. Unlike

conventional anticipators, this setting is not determined by current
draw. There is no need to measure, know, or compensate for

current draw. There is also no droop with this Thermidistat

Control. Regardless of setting and number of stages, both heating
and cooling will control to their respective set points.
TO ADJUST:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” The upper small (COOL
set point) display will be flashing 1. If not, use up and

down buttons to move it to 1.

2. Press SET TIME/TEMP button once to flash current

selection of 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display.

Factory default is 3.

3. Use up and down buttons to move between available

choices.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to

exit configuration mode.

Option 2—Clean Filter Timer

Select hours of blower operation (heating, cooling, or fan) before
CLEAN FILTER icon is displayed. With OFF selected, icon will

never come on, disabling this feature. Time selection can range

from 400 to 3600 hr by selecting numbers 1 through 9. (Time is
400 X number selected.) Factory default is 2 (800 hr).

Recommended selections are: disposable filter—400 to 800 hr,
media filter—1200 to 1600 hr, or electronic air cleaner—1600 to

2400 hr of blower operation.
TO SELECT OR ADJUST:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down
buttons to make small (now flashing) display indicate 2.

2. Press SET TIME/TEMP button once to flash current

selection of OF, 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display.
Factory default is 2.

3. Use up and down buttons to move between available

choices.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to
exit configuration mode.

Option 3—English/Metric

Select between Fahrenheit and Celsius operation. Factory default

is Fahrenheit.

TST

AT

Содержание THERMIDISTAT CONTROL TSTAT

Страница 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Страница 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Страница 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Страница 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Страница 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Страница 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Страница 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Страница 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Страница 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Страница 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Страница 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Страница 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Страница 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Страница 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Отзывы: