Thermidistat Control Troubleshooting

SYMPTOM

WHAT TO CHECK

No Display

Open Thermidistat Control. Check for 24vac between R and C at screw terminals on mount-

ing base. Reassemble, making sure pins on board engage sockets in mounting base. If

display does not appear, replace Thermidistat Control.

“--- ---” in place of room temperature

Thermidistat Control cannot properly read room temperature. Replace Thermidistat Control.

“E3” or “--- ---” in place of outdoor

temperature

Thermidistat Control cannot properly read outdoor temperature. Check outdoor sensor and

its wiring.

“E4” or “E5”

Internal failure. Replace Thermidistat Control.

“E6”

System is stuck in defrost. Check wiring and heat pump defrost control board.

“Clean Filter” icon displayed

Filter timer has expired. Clean or replace filter and then press VACATION and HOLD/END

buttons together to reset.

Cooling or heating will not come on

See Installer Setup to force heating or cooling. Check for 24vac at equipment terminals. If

not present, check wiring.

Humidify or dehumidify will not come on

See Installer Setup to force HUM or DEHUM. Check for 24vac at equipment terminals. If not

present, check wiring.

TST

AT

Содержание THERMIDISTAT CONTROL TSTAT

Страница 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Страница 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Страница 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Страница 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Страница 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Страница 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Страница 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Страница 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Страница 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Страница 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Страница 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Страница 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Страница 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Страница 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Отзывы: