will run the higher of heat pump efficiency airflow and electric
heater airflow. The factory selection is largest heater range
approved. (See Fig. 16.)
B.
AC/HP Size
The factory setting for air conditioner or heat pump size is largest
unit meant for application with model of fan coil purchased. The
installer needs to select air conditioner or heat pump size to ensure
that airflow delivered falls within proper range for size of unit
installed in all operational modes. (See Fig. 16.)
C.
System Type
The type of system must be selected.
1. AC—air conditioner
2. HP-COMFORT—provides same airflow as air conditioner
selection (approximately 375 CFM/ton)
3. HP-EFF—provides most efficient airflow for heating and
cooling modes (approximately 410 CFM/ton heating and
375 CFM/ton cooling)
The factory setting is AC. (See Fig. 16.)
D.
AC/HP CFM Adjust
Select low, medium, or high airflow. To provide any of these
airflows, AC/HP ADJUST select must be moved to MED position.
The factory selection is LO. The adjust selections HI/LO will
regulate airflow supplied for all operational modes, except non-
heat pump heating modes, +10 percent and -10 percent respec-
tively. The adjust selection options are provided to adjust airflow
supplied to meet individual installation needs for such things as
noise, comfort, and humidity removal. (See Fig. 16.)
E.
AC/HP Time Delay
Select desired time delay profile. Four motor operation delay
profiles are provided to customize and enhance system operation.
(See Fig. 16.) The selection options are:
1. The standard 90 sec off delay (factory setting).
2. No delay option used for servicing unit or when a thermo-
stat is utilized to perform delay functions.
Fig. 17—Easy Select Board Circuitry
A94077
ST1
E
8
ST1
W2
9
ST1
W3
10
ST1
C
3
ST1
R
2
ST1
G
7
ST1
Y/Y2
5
ST1
Y1
4
ST1
L
1
ST1
O
3
JW2
JW1
JW3
JW4
D1
D2
D2
R3
1K 2W
SEC1
SEC2
PS1
R2
1K 2W
R1
1K 2W
P1
1
2
3
4
5
6
7
8
9
10
11
12
HIGH VOLTAGE
M1
T1
T2
M2
T3
AUX1
HUM1
AUX2
HUM2
D7
D8
D9
D4
D5
D6
P2
W/W1
G
C1
C2
R
Y/Y2
Y1
D11
D10
5 – 30
1200
5 – 20
1000
5 – 10
800
0 – 5
600
RED
QC19
QC4
QC8
QC3
QC7
QC2
QC6
QC1
QC5
024
030
036
042
QC9
AC
QC12
QC15
ON
OFF
LOW
0
90
QC13
MED
QC10
HP–COM.
QC11
HP–EFF.
QC14
HI
QC16
30
90
QC17
30
30
QC18
0
0
AUX. HEAT
RANGE
AC/HP
SIZE
AC/HP
TYPE
AC/HP
CFM TRIM
AC/HP
DELAY
—23—