background image

6. W2 is used to turn on the first stage of electric heat which

is interlocked with the fan through the normally closed fan
relay. Unless the tabs are broken off, all stages of electric
heat will turn on when W2 receives a signal from the
thermostat.

7. W3 is used to turn on the second stage of electric heat. Note

the W2 and W3 tab must be broken off for individual
staging to take place. Energizing W3 will always turn on the
first stage through the diodes even if the tabs are broken off.

8. E is used to turn on the third stage of electric heat. Note that

the W3 and E tab must be broken for this individual staging.
Energizing E will always turn on the first stage through the
diodes even if the tab is broken off.

9. L is used as a junction to wire a diagnostic light (LED) on

selected thermostats.

B.

Transformer

The proper wiring of the transformer on the HK61GA001 board is
illustrated in Fig. 8. Note that T1, T2, and T3 are wired to the
primary or high side of the transformer. The blue wire is connected
to T3 for 208-v applications. The red wire is connected to T3 for
230-v applications. Units are factory wired at 230v. The T2
terminal is a dummy.

C.

Indoor Fan

1. Wiring--The fan connects to F1, F2, F3, and F4 as shown in

Fig. 8. Note that F2 and F3 are dummy terminals. The
desired fan speed is connected to F4 and the common is
connected to F1. Units are factory wired at medium speed.

2. Functional Control

a. Thermostat and Relay Control--When the thermostat

calls for the fan in cooling, heat pump, electric heat, or
fan-only mode, a 24-v dc signal is sent to the relay. This
causes the relay to close its normally open contacts, thus
turning on the fan. When the thermostat no longer calls
for the fan, the signal sent to the relay is turned off and
the relay opens causing the fan to turn off. The
HK61GA003 board contains a 90-sec fan-off delay when
Y is de-energized.

b. Sequencer Interlock--The fan will also turn on whenever

there is any call for electric heat, even if the fan relay is
not energized. This happens because the fan is inter-
locked with the first stage of electric heat through the
normally closed contact of the fan relay.

D.

Electric Heat

When the thermostat calls for electric heat, a 24-v signal is sent to
the PCB through W2, causing the first stage to turn on. W3 and E
also receive the signal if the tabs are not broken off the PCB. The
signal sent to W2 causes the first stage to turn on. If the tabs are
broken off the PCB, the sequencers can be controlled individually
to stage the electric heat. The sequence control is described in the
following section:

1. W2--When the thermostat sends a signal to W2, a 24-v dc

signal is applied across sequencer number 1, causing it to
close. When sequencer number 1 closes, the first stage of
electric heat energizes after a short delay. In straight electric
heat, the fan is also energized through the normally closed
contacts of the fan relay. In cooling, heat pump, or manual
fan mode, the fan will already be running since the fan relay
would have been energized. When the thermostat stops
calling for electric heat, the 24-v dc signal to sequencer
number 1 turns off and the sequencer opens after a delay of
60 to 90 sec. When the sequencer opens, the first stage of
heat turns off along with the fan, providing that the
thermostat is not calling for the fan. Note that the electric
heat cannot be turned on without the fan being turned on at
the same time. This is a fan interlock system.

2. W3--When a signal is sent to W3, 2 control signals are sent

out to the sequencers; a 24-v dc signal to sequencer number
1 through the diode interlock, and a 24-v ac signal to
sequencer number 2. The 24-v ac signal applied to sequence
number 2 causes the sequencer to close, with the second
stage of electric heat turning on after a short delay.

The 24-v dc signal applied to sequencer number 1 causes the first
stage of electric heat to turn on in the same manner as described in
W2 above. Note that W3 is interlocked with the fan, since
sequencer number 1 is turned on whenever W3 has a signal sent to
it. Timing is such that sequencer number 1 will turn on before
sequencer number 2. When the signal to W3 is turned off,
sequencer number 2 opens after a short delay. If W2 is also
satisfied, the first stage of electric heat and the fan will also turn
off, providing the thermostat is not calling for the fan to be on.
E--When the thermostat sends a signal to E 2 signals are sent out
to the sequencers. A 24-v ac signal is sent to sequencer number 3
and a 24-v dc signal is sent to sequencer number 1. The 24-v ac
signal applied to sequencer number 3 turns on the third stage of
electric heat. The 24-v dc signal applied to sequencer 1 turns on the
first stage of electric heat and the fan in the same manner as W3.
Note that E is also interlocked with the fan.
When the thermostat stops calling for electric heat, the signals to
sequencers 1 and 3 are turned off and the sequencers open. This
causes the electric heat to turn off with the fan if the thermostat is
not calling for the fan.

E.

Accessories

1. EAC1 and EAC2 for Electronic Air Cleaners

a. There are 240-v electronic air cleaner contacts provided

at EAC1 and EAC2. The electronic air cleaner is
connected in parallel with the fan so that it is on
whenever the fan is on. A 120-v installation is similar in
function but connected between EAC2 and neutral of
230-v: 120-v transformer connected to EAC1 and EAC2.
Refer to electronic air cleaner literature for further
information.

2. AUX1 and AUX2 for 2-Speed Fan Relay Kit

a. Use to control fan speed operation, high speed for

cooling, heat pump, and fan-only modes. Low speed is
used for electric heat. Fig. 9 shows proper connection for
24-v dc 2-speed fan relay kit. Note that kit’s relay coil is
in parallel with fan relay coil on PCB connected to
AUX1 and AUX2. Make sure the normally closed
contact is connected to the lower speed.

b. The latent capacity control kit is used to control fan

speed operation when the relative humidity is above a set
point on humidistat. Humidistat opens and 2-speed fan
relay remains in normally closed position with fan motor
running at a lower speed for maximum humidity control.
Fig. 10 shows proper connection for latent capacity
control kit. Note that it is connected in the same manner
as 2-speed fan relay kit but with relay connected to
humidistat (orange wires).

c. Time delay-off relay kit is used to increase the efficiency

of the system by delaying the fan from turning off after
the thermostat is satisfied on the HK61GA001 board.
The HK61GA003 board has this feature as standard. The
proper wiring and mounting of the time delay-off relay
kit is shown in Fig. 11.

d. Latent capacity control and time delay-off connections

are shown in Fig. 12, for the HK61GA001 board only.

III.

TROUBLESHOOTING

THE

PRINTED-CIRCUIT

BOARD

Use Fig. 13 wiring schematic as a guide in troubleshooting the
PCB unless otherwise noted.

—11—

Содержание SM03-4

Страница 1: ...Troubleshooting PCB 32 Troubleshooting ICM2 34 Condensed Version of Troubleshooting FK4C FV4A Motor and Controls 34 Accessories 34 THERMOSTATIC EXPANSION VALVES TXV 35 Problems Affecting TXV 36 PISTO...

Страница 2: ...3A 1 The low voltage stripped leads are used to connect the 24 v side of transformer to indoor thermostat and outdoor section 2 A 5 amp fuse is used to protect the low voltage transformer secondary 3...

Страница 3: ...w 2 Downflow 3 Horizontal 4 Multipoise 5 Upflow Downflow Airflow 018 1 1 2 Ton 024 2 Ton 001 Multi Tons 002 Multi Tons Etc Cooling Size 10th 11th 12th Positions Fan Coil 005 010 Etc Heating Size KW 6t...

Страница 4: ...ultipoise Single Piece FV4ANB 006 Multipose Modular NOTE Multipoise units are approved for upflow downflow and horizontal left and right applications TABLE 2 PSC FAN MOTOR SPEED TAPS MODEL UNIT SIZE N...

Страница 5: ...e in troubleshooting PCB unless otherwise noted A If Fan Will Not Turn On from Thermostat IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER 1 Check plug receptacle connection This supplies power from heaters...

Страница 6: ...voltage transformer needs to be replaced B If Electric Heat Stages Will Not Turn On But Fan Will Turn On IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER 1 Check plug connection between heaters and board T...

Страница 7: ...BLK AND LOW BLU OR RED 12 CONNECT R TO R G TO G ETC SEE OUTDOOR INSTRUCTION FOR DETAILS 13 IF WIRE CRIMP IS REMOVED AN EMERGENCY HEAT RELAY IS REQUIRED SEE OUTDOOR THERMOSTAT INSTRUCTIONS THIS COMPAR...

Страница 8: ...e 5 Use 60 amp class K fuses only for replacement 6 3 speed motor shown Optional 2 speed motor uses HI BLK and LOW BLU or RED 7 Connect R to R Gto G etc see outdoor instruction for details 8 Smaller h...

Страница 9: ...listed as follows along with their functional control 1 R is used to connect the secondary side of the transformer The red wire provides low voltage 24v to the PCB and the thermostat R is fused on th...

Страница 10: ...fan off delay which begins timing when the Y is de energized 5 O is used as a junction for a heat pump reversing valve circuit Fig 7 HK61GA003 Printed Circuit Board A97026 3 6 9 12 2 5 8 11 1 4 7 10 L...

Страница 11: ...be turned on without the fan being turned on at the same time This is a fan interlock system 2 W3 When a signal is sent to W3 2 control signals are sent out to the sequencers a 24 v dc signal to seque...

Страница 12: ...FUSE MAX FAN TDB YEL LS 5 HTR5 BLK BLK 10 9 YEL FU5 FU6 SEQ 3 LS 6 HTR6 BLK BLK 12 11 YEL LS 5 HTR5 BLK BLK 6 5 YEL FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK BLU MED BLU MED RED LO RED...

Страница 13: ...G RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O N D U M M Y T 3 L 2 L 1 F 1 F 2 F 3 F...

Страница 14: ...LD POWER WIRING AUX 1 AUX 2 F4 24 VDC RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC NO C HST ORG ORG COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M...

Страница 15: ...WIRING FIELD POWER WIRING AUX 1 AUX 2 F4 24 VDC TDR YEL FAN COMMON UNUSED LEAD UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O...

Страница 16: ...NG AUX 1 AUX 2 F4 24 VDC TDR FR ORG ORG RED YEL FAN COMMON UNUSED LEAD LOW MTR SPD HI MTR SPD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R COM NO NC T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O...

Страница 17: ...MAX AUX2 L1 EAC1 FAN R L G E C O Y W2 INDOOR THERMOSTAT YEL YEL BLK LS 3 HTR3 BLK BLK 6 5 YEL FU1 FU2 FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK 2 1 YEL SEQ 1 LS 2 HTR2 BLK BLK 4 3 SEQ...

Страница 18: ...the PCB transformer and the fan Make sure the plug is connected properly 2 Check sequencer number 1 and the plug wiring The yellow wire should be connected to pin number 9 of the plug and the limit s...

Страница 19: ...m temperatures cool sufficiently the switch will automatically reset to its closed position Normal failure mode for this switch is open If a limit switch has been determined to be defective NEVER BYPA...

Страница 20: ...w due to dirty filters blocked registers or undersized duct 2 Check blower motor and wheel for proper operation Excessive current draw of motor will cause internal over load to trip 3 The fan speed ma...

Страница 21: ...ied together by jumpers JW1 and JW2 These jumpers are provided for field staging of electric heater banks through use of thermostats When staging is a requirement installer cuts jumpers and wires in t...

Страница 22: ...ses selected taps to modify its operation to a pre programmed table of airflows Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such...

Страница 23: ...flow supplied for all operational modes except non heat pump heating modes 10 percent and 10 percent respec tively The adjust selection options are provided to adjust airflow supplied to meet individu...

Страница 24: ...option 24 vdc 0 187 X 0 032 M1 Common connection to blower motor T1 Common connection for transformer RED Common to R screw terminal and SEC2 TABLE 4 CONNECTIONS ON SINGLE BARRIER STRIP MOUNTED CROSS...

Страница 25: ...L RECP 3 RECP 4 ICM BRN YEL RED VIO RED ORN BRN VIO ORN GRY BLU BLK BLK 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 PLUG 2 BLK YEL ORN GRN RED BRN VIO SEE NOTE 3 SEE NOTE 2 HPTB E Y1 Y0 W2 O L R NOTES 1 Us...

Страница 26: ...orted or system is trying to draw more VA than transformer rating allows When fuse blows because of high voltage the system has mixed high and low voltage signals 1 Check transformer and thermostat wi...

Страница 27: ...it board terminals AUX1 and AUX2 See Fig 16 This signal is present when either G or W is present and is active in all heating and cooling modes Because 24 vdc relays may not be readily available to in...

Страница 28: ...2 is fed high voltage AC power through the 5 pin connector See Fig 23 The AC power is then rectified to DC by a diode module After rectification DC signal is electronically communicated and fed in seq...

Страница 29: ...se of thermostats When staging is a requirement remove J2 jumper and wire in thermostats as is the common practice with other fan coils To ensure motor operation if any 1 of the inputs is energized mo...

Страница 30: ...operation to a pre programmed table of airflows Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need for de humidificati...

Страница 31: ...it installed in all operational modes See Fig 24 C System Type The type of system must be selected 1 AC air conditioner 2 HP COMFORT provides lower airflow than air condi tioner selection approximatel...

Страница 32: ...Check low voltage fuse shown in Fig 24 If fuse is blown replace it The transformer cannot supply power to board with fuse blown or loose If fuse blows when unit has power applied to it the system most...

Страница 33: ...WHT PLUG 3 230V 208V Com YEL BLK BLK YEL ICM RECP 4 RECP 3 GRY 1 BRN 12 11 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 G R N Y E L B L K W H T RED VIO V I O R E D B R N O R N BRN PLUG 1 G R Y 16 15 14 13 12 11 10...

Страница 34: ...continues to run remove all thermostat wires If motor stops check thermostat wiring to thermostat or outdoor unit for shorts or miswire XV CONDENSED VERSION OF TROUBLESHOOTING FK4C AND FV4A MOTOR AND...

Страница 35: ...heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at outlet of evaporator coil The volume of refrigerant metered through valve seat is dependent up...

Страница 36: ...place seal ring on retainer 8 Reconnect refrigerant tube to piston body 9 Pressurize tubing and coil then leak check 10 Evacuate tubing and coil as necessary CAUTION Use a backup wrench and do not ove...

Страница 37: ...id and vapor refrigerant tubes and conden sate drain tube Install new liquid line filter drier 20 Evacuate tube set and indoor coil to 500 microns back seat open liquid and vapor service valves 21 Tur...

Страница 38: ...tube from original coil and install it in same position on new coil See Fig 31 12 Place coil assembly in plastic condensate pan and secure using 4 screws through delta plate See Fig 31 13 Horizontal...

Страница 39: ...llow filter to dry No oiling or coating of filter is required New filters are available from your local distributor Place filter in slot with cross mesh binding up or facing cooling coil and replace f...

Страница 40: ...rmer A 40 VA transformer supplies 24 v power for control circuit Check for 208 230v on primary side of transformer If present check for 24v on secondary side NOTE Transformer is fused Do not short cir...

Страница 41: ...LK BLK HTR LS YEL VIO BLK BLK RED BLU TRANS DISCONNECT SEE RATING PLATE FOR VOLTS HZ FIELD POWER SUPPLY CHASSIS GROUND RED VIO ORN BRN BRN CHASSIS GROUND RED ORN T A P2 B BRN BRN 5 6 SEQ CHASSIS GROUN...

Страница 42: ...be a trap in condensate line Trap must be at least 3 in deep not higher than the bottom of unit condensate drain opening and pitched downward to an open drain or sump CAUTION Do not use caustic househ...

Страница 43: ...SFORMER PIGTAILS BLUE 208V RED 230V INSULATE UNUSED LEAD 2 FAN MOTOR PIGTAILS RED LOW BLACK HIGH INSULATE UNUSED LEAD 3 FAN MOTOR THERMALLY PROTECTED 4 SUITABLE FOR USE WITH COPPER OR COPPER CLAD ALUM...

Страница 44: ...ction of this manual C Transformer A 60 VA transformer supplies 24 v power for control circuit Check for 208 230 v on primary side of transformer If present check for 24 v on secondary side Replace tr...

Страница 45: ...every 5 years if motor is used on intermittent operation thermostat FAN switch at AUTO position or every 2 years if motor is in continuous operation thermostat FAN switch at ON position Remove motor...

Страница 46: ...ump signaling control board that heat pump is in defrost g W2T terminal provides input from thermostat signaling for supplemental or emergency heat h W3 terminal provides input from outdoor thermostat...

Страница 47: ...ycle down indoor fan remains on 60 sec to recover heat stored in indoor coil C Defrost The Smart Heat PCB stages the correct amount of supplemental heat during defrost If too much heat is added system...

Страница 48: ...gh speed through terminals F1 and HI The LED indicator on control signals 5 flashes indicating cooling operation The call for cooling signals can be confirmed by placing voltmeter leads across low vol...

Страница 49: ...s sequencer relay terminal 4 of sequencer relay 1 and terminal 4 of limit switch 3 The reading should be 208 230v and heater should be energized If 208 230v is not observed at terminals specified chec...

Страница 50: ...EFERENCE GUIDE FOR INSTALLERS AND TECHNICIANS Puron R 410A refrigerant operates at 50 70 percent higher pressures than R 22 Be sure that servicing equipment and replacement components are designed to...

Страница 51: ...AT E W2 O G Y C R LVTB Yo W3 W2T W2D O G Y C R YEL BLK VIO BRN 7 8 9 6 5 4 1 2 3 YEL YEL YEL SEQ 3 HTR3 3 SEQ1 8 7 4 SEQ2 6 5 SEE NOTE 1 SEE NOTES 2 7 AND 8 YEL COM CAP BRN FM BRN GRN YEL GND BLK HI B...

Страница 52: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays...

Отзывы: