GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system heat pump unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI
Standard 240.
Unit will be certified for capacity and efficiency, and listed in the
lastest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have C-UL approval.
Unit cabinet will be capable of withstanding Federal Test Method
Standard No. 141 (Method 6061) 500-hr salt spray test.
Air-cooled condenser coils will be leak tested at 217 psig and
pressure tested at 450 psig.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled heat pump unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (Puron®), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type, discharging air
upward.

Air-Cooled, Split-System

Heat Pump

650A

2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire safety
guards.

Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically bonded
to copper tubes which are then cleaned, dehydrated, and
sealed.
Refrigeration Components
Refrigeration circuit components will include liquid tube shutoff
valve with sweat connections, suction tube shutoff valves with
sweat connections, system charge of Puron® refrigerant, POE
compressor oil, accumulator, and reversing valve.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a
suction temperature of _____ °F. The power consumption at full
load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of _____ Btuh or greater at
conditions of _____ CFM entering air temperature at the
evaporator at _____ °F wet bulb and _____ °F dry bulb, and air
entering the unit at _____ °F.
The system will have a SEER of _____ Btuh/watt or greater at
DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, _____
phase, 60 hz. The unit will be capable of satisfactory operation
within voltage limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.

Содержание QUANTUM PLUS 650A

Страница 1: ...frequency sound and pres sure pulsation generated by compressor discharge gas WEATHER PROTECTIVE CABINET The casing steel is galva nized and coated with a layer of zinc phosphate A layer of modified p...

Страница 2: ...7 8 DIA HOLE WITH 1 1 8 DIA KNOCKOUT AND 1 3 8 DIA KNOCKOUT 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 C F 2 15 16 G A B M DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS...

Страница 3: ...DIAMETER IN VAPOR TUBE DIAMETER IN 0 to 50 Ft Tube Length 0 to 50 Ft Tube Length 0 to 50 Ft Alternate 024 3 8 5 8 3 4 ACR 030 3 8 3 4 5 8 7 8 036 3 8 3 4 5 8 7 8 042 048 3 8 7 8 3 4 7 8 060 3 8 1 1 8...

Страница 4: ...d 18 In KHASS0206MPK Time Delay Relay KAATD0101TDR Ball Bearing Fan Motor HC38GE231 RCD MotorMaster Low Ambient Controller KSALA0401AAA Outdoor Thermostat KHAOT0301FST Secondary Outdoor Thermostat KHA...

Страница 5: ...266 295 ELECTRICAL Unit Volts Hertz Phase 208 230 60 1 Operating Voltage Range 187 253 Compressor Rated Load Amps 21 1 20 5 21 8 27 6 Compressor Locked Rotor Amps 104 0 109 0 117 0 158 0 Condenser Fa...

Страница 6: ...rogrammable F C 2 Stage Heat 1 Stage Cool Heat Pump TSTATBBBHP01 Outdoor Air Temperature Sensor TSTATXXSEN01 B Backplate for Non Programmable Thermostat TSTATXXNBP01 Backplate for Programmable Thermos...

Страница 7: ...lled at the outdoor unit to control refrigerant off cycle migration in the heating mode Usage Guideline An LLS is required in all long line heat pump applications to control refrigerant off cycle migr...

Страница 8: ...g pad This allows sand dirt and other debris to be flushed from the unit base minimizing corrosion Usage Guideline Suggested in the following applications Coastal installations Windy areas or where de...

Страница 9: ...CC5A CD5AA030 23 400 TDR 13 20 11 75 23 400 3 06 15 000 2 26 7 5 CC5A CD5AA036 24 200 TDR 14 00 12 10 24 000 3 28 15 200 2 36 7 8 CC5A CD5AW030 23 400 TDR 13 20 11 75 23 200 3 06 15 000 2 26 7 5 CC5A...

Страница 10: ...0 28 600 3 48 17 200 2 40 7 8 CC5A CD5AW036 28 600 TDR 14 00 12 30 28 600 3 50 17 200 2 40 7 8 CK5A CK5BW036 29 200 TDR 14 00 12 35 28 800 3 74 17 900 2 52 8 0 CK5PW036 29 200 TDR TXV 14 00 12 35 28 8...

Страница 11: ...5 36 000 3 64 22 200 2 60 8 5 CK5A CK5BA048 34 600 TDR 14 00 11 55 36 000 3 70 22 600 2 68 8 8 CK5A CK5BT042 34 400 TDR 13 50 11 45 35 800 3 64 22 200 2 60 8 5 CK5A CK5BT048 34 600 TDR 14 00 11 55 36...

Страница 12: ...8 33 400 TDR 13 50 11 15 35 200 3 34 22 400 2 52 8 0 CC5A CD5AW042 33 400 TDR 13 50 11 15 35 200 3 36 22 400 2 52 8 0 CC5A CD5AW048 34 000 TDR 13 50 11 35 35 400 3 56 22 600 2 58 8 5 CD5AA048 34 000 T...

Страница 13: ...3 50 11 25 40 500 3 32 25 200 2 46 7 5 CD5AA048 40 000 TDR 13 50 11 25 40 500 3 32 25 200 2 46 7 5 CE3AA048 40 500 TDR 13 50 11 15 40 500 3 36 25 400 2 48 7 6 CK3BA048 40 000 TDR 13 50 11 20 40 500 3...

Страница 14: ...10 90 48 000 3 54 28 600 2 38 8 1 FX4BNF048 45 000 TDR TXV 12 50 10 75 48 000 3 42 28 400 2 34 8 0 COILS 315 A J AV048090 VARIABLE SPEED FURNACE CE3AA060 44 500 TDR 13 00 11 40 47 500 3 64 27 400 2 50...

Страница 15: ...800 2 44 8 3 CK5PA060 45 000 TDR TXV 13 00 11 25 47 000 3 50 27 800 2 40 8 2 CK5PT060 45 000 TDR TXV 13 00 11 25 47 000 3 50 27 800 2 40 8 2 CK5PX060 45 500 TDR TXV 13 50 11 45 47 500 3 54 27 800 2 44...

Страница 16: ...MPERATURE F 10 0 10 20 30 40 50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 kW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 650AN BALANCE POINT WORKSHEET 650AN024 E FX4A0...

Страница 17: ...8 17 4 2 89 19 1 16 7 3 19 62 25 9 24 7 1 92 24 7 24 1 2 13 23 5 23 3 2 37 22 3 22 3 2 62 21 1 21 1 2 89 19 7 19 7 3 19 57 25 5 25 5 1 91 24 5 24 5 2 13 23 4 23 4 2 37 22 3 22 3 2 62 21 1 21 1 2 89 1...

Страница 18: ...31 0 2 17 29 7 29 7 2 41 28 3 28 3 2 68 26 8 26 8 2 98 25 1 25 1 3 31 23 2 23 2 3 67 57 31 0 31 0 2 17 29 7 29 7 2 41 28 3 28 3 2 68 26 8 26 8 2 98 25 1 25 1 3 31 23 2 23 2 3 67 Multipliers for Deter...

Страница 19: ...7 9 4 48 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 02 CK5A CK5B...

Страница 20: ...27 9 4 48 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK3BA 042 1 00 0 93 CK5PA 042 0...

Страница 21: ...0 8 40 8 3 34 39 0 39 0 3 74 37 1 37 1 4 19 35 1 35 1 4 68 32 8 32 8 5 20 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling...

Страница 22: ...4 14 34 2 34 2 4 62 32 0 32 0 5 15 1575 72 50 0 26 7 3 04 47 7 25 9 3 41 45 3 25 1 3 81 42 7 24 2 4 26 39 9 23 2 4 74 36 8 22 2 5 26 67 46 0 34 7 3 00 43 9 33 9 3 37 41 6 33 0 3 77 39 3 32 1 4 22 36 7...

Страница 23: ...ndoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 07 CK5PA 060 0 98 0 98 CC5A CD5AW 060 0 98 1 05 CK5PT 060 0 98 0 98 CD5PX 060 0 98 1 03 CK5PX 060 1 00 0 99 CE3AA 060 1 0...

Страница 24: ...4 37 1 7 30 62 59 2 55 1 4 29 56 4 53 7 4 78 53 5 52 3 5 33 50 5 50 4 5 93 47 5 47 5 6 60 44 2 44 2 7 32 57 57 8 57 8 4 27 55 6 55 6 4 77 53 1 53 1 5 32 50 5 50 5 5 93 47 5 47 5 6 60 44 2 44 2 7 32 20...

Страница 25: ...15 9 14 5 2 13 18 5 16 4 2 22 21 5 19 6 2 33 24 9 24 9 2 47 28 7 28 7 2 65 33 0 33 0 2 89 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Sect...

Страница 26: ...4 1 2 36 18 6 16 9 2 41 21 9 19 5 2 45 25 7 23 4 2 51 30 1 30 1 2 58 35 0 35 0 2 67 40 6 40 6 2 81 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating In...

Страница 27: ...3 48 50 3 50 3 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 0...

Страница 28: ...W 048 0 98 0 95 CK5A CK5BT 042 0 92 0 97 COILS 315 A J AV066155 VARIABLE SPEED FURNACE 048 0 92 0 94 CC5A CD5AW 042 0 96 0 98 CK5PA 042 0 99 1 00 048 0 96 0 94 048 0 98 0 99 CD5AA 048 0 95 0 94 CK5PT...

Страница 29: ...h Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AC 048 1 00 1 11 CK5A CK5BT 048 1 00 0 98 CC5A CD5AW 048 1 01 1 07 CK5A CK5BW 048...

Страница 30: ...6 3 66 56 9 56 9 4 00 75 1225 16 2 14 9 2 88 20 6 18 9 3 03 25 1 22 8 3 19 29 3 26 0 3 34 34 3 31 2 3 51 39 9 39 9 3 73 46 7 46 7 4 01 54 6 54 6 4 39 1400 16 5 15 2 2 88 20 9 19 2 3 02 25 3 23 1 3 17...

Страница 31: ...00 CC5A CD5AW 060 1 01 1 06 CK5PX 060 1 00 0 99 CD5PX 060 0 98 1 10 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CE3AA 060 1 01 1 06 CC5A CD5AW 060 0 99 1 08 CK3BA 060 1 01 1 03 CE3AA 060 0 99 1 02 C...

Страница 32: ...rmance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AW 060 0 98 1 06 COILS 315 A J AV066110 VARIABLE SPEED FURNACE CD5PX 060...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...d of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Heat Pump 650A 2 to 5 Tons No...

Отзывы: