67

Thermostat

RVS/Heat Stage 2

O/B W2

Heat Stage 1

W/W1

Compressor Low

Y1

Compressor High

Y/Y2

Fan

G

G

24VAC Hot Heating

Rh

R

24VAC Hot Cooling

Rc

Dry Contact 1

D1

Dry Contact 2

D2

24VAC Common

C

C

Humidify

HUM

Outdoor Air Temp

OAT

Remote Room Sensor

RRS

OAT/RRS Com

OAT/RRS

A06581

Fig. 26 -- Thermidistat Control w/Dry Contact Control for Fan Run Time

* Indicates connection may not be required/available.

Содержание PREFERRED T6-NRH

Страница 1: ...stallation Instructions T6 PRH T6 NRH PREFERREDt SERIES THERMIDISTAT A07045 A07044 Programmable Control Non Programmable Control NOTE Read the entire instruction manual before starting the installatio...

Страница 2: ...tt Control Recognize safety information This is the safety alert symbol When you see this symbol on the equipment and in the instruction manual be alert to the potential for personal injury Understand...

Страница 3: ...parate setpoints for heating and cooling in addition to humidification and dehumidification In the Preferred Series Thermidistat Control s programmable configuration different heating and cooling setp...

Страница 4: ...e outdoor unit to the Rc terminal Then break jumper on the circuit board The W and HUM signals are taken from the Rh power and the G signal is taken from the Rc power If Thermidistat Control has been...

Страница 5: ...rid Heatt installations allowing it to be used in place of all Bryant thermostats Programmable Thermidistat Controls may be configured as non programmable if user desires Humidify Equipment and Connec...

Страница 6: ...available The dry contact must be configured for dehumidification in setup Option 19 See Wiring Diagrams for more information Outdoor Temperature Sensor Outdoor air temperature sensor is included in t...

Страница 7: ...split into two pieces and mounted in separate locations As a single piece unit all required wiring must be brought to the Equipment Control Module for connection to the terminal strip In two piece con...

Страница 8: ...following components See Fig 2 for T6 PRH or Fig 3 for T6 NRH A07752 Fig 2 T6 PRH Carton Contents 1 Display Module 2 Stand off for Equipment Control Module 3 Outside Air Temperature Sensor screws and...

Страница 9: ...Module Thermidistat Control Location Thermidistat Control should be mounted S Approximately 5 ft 1 5m from floor S Close to or in a frequently used room preferably on an inside parti tioning wall S On...

Страница 10: ...ontrol will be installed as single piece or two piece In single piece configuration as many as 14 wires may need to run to wall mounting location for connection to the control In two piece configurati...

Страница 11: ...roceeding with installation or turning on power CAUTION 1 Turn off all power to equipment 2 If an existing Thermidistat Control is being replaced a Remove existing control from wall b Disconnect wires...

Страница 12: ...e Installation The following steps should be followed for the installation of the two piece configuration NOTE The 2 wire pigtail is not intended to support the weight of the User Interface Do not han...

Страница 13: ...13 A07225 Fig 4 Press Tabs to Remove Backplate A07226 Fig 5 Take Apart...

Страница 14: ...marked Thermidistat may be mounted to a standard junction box if desired Hole pattern on Thermidistat Control mounting base matches junction box mounting holes 4 Secure rear plastic mounting base to w...

Страница 15: ...Fig 7 8 and 9 Relays OAT RRS SRTN HUM D1 D2 V Vg Rc Rh W W1 G Y Y2 Y used for single stage cooling C O W2 B Y1 Y1 used for multi speed cooling Y1 stage 1 Y2 stage 2 Control Module Wiring Guide connect...

Страница 16: ...16 A07166 Fig 8 Secure Wires to Terminal Strip A07167 Fig 9 Connect Pigtail Wires to Display Module...

Страница 17: ...nt air leaks Leaks can affect operation and cause incorrect temperature and or humidity measurement 8 Make sure 2 wire pigtail is attached to Display Module mounting base This should come attached fro...

Страница 18: ...MPORTANT NOTE Equipment Control Module should not be mounted to duct work or below any other controls or equipment i e humidistat humidifier etc A07217 Fig 11 Equipment Control Module on Equipment 11...

Страница 19: ...ot to over tighten the screws Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base If wires are con nected incorr...

Страница 20: ...2 digit code appears on large display which identifies Thermidistat Control configuration Refer to Option 33 a AC 1 stage air conditioner b HP 1 stage heat pump c A2 2 stage air conditioner d H2 2 st...

Страница 21: ...mark wall through 2 mounting holes 2 Drill two 3 16 in mounting holes in wall where marked Thermidistat Control may be mounted to a standard junction box if desired Hole pat tern on Equipment Control...

Страница 22: ...ffect operation and cause incorrect temperature and or humidity measurement 7 Remove 2 wire pigtail from Thermidistat Control mounting base and at tach to Equipment Control Module terminal block termi...

Страница 23: ...it code appears on large display which identifies Thermidistat Control configuration Refer to Option 33 a AC 1 stage air conditioner b HP 1 stage heat pump c A2 2 stage air conditioner d H2 2 stage he...

Страница 24: ...e up to 33 selections can be made Description of each selection and how to use the configuration mode follows CONFIGURATION OPTIONS SUMMARY Option 01 Equipment Type Option 02 Clean Filter Timer Adjust...

Страница 25: ...klight Configuration Option 19 Dry Contact Option 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout Option 22 High Cool Latch Temperature Option 23 High Heat Latch Temperature Opti...

Страница 26: ...the T6 PRH programmable model a box will surround the option number The mode button is used to move the box between the two displayed values The soft keys below the listed values may also be used to m...

Страница 27: ...on is displayed With OF selected icon will never come on disabling this feature Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9 Time is 800 X number selected Default is 4...

Страница 28: ...Below 55_F This selection disables cooling when outdoor temperature is below 55_F It requires an outdoor temperature sensor Setting is not available if valid outdoor sensor is not connected Set to OF...

Страница 29: ...ways start with heat pump heating 5 55_F the outdoor temperature below which heat pump operation is not allowed When emergency heat mode is selected only auxiliary heat will operate Default is OF off...

Страница 30: ...s programmed Not available with non programmable Thermidistat Controls or when Thermidistat Control is configured as non programmable Default is 90 Option 13 Room Air Temperature Offset Adjust The num...

Страница 31: ...puts will be energized no more than 4 times per hour When an output is energized it will not be energized again for 15 minutes 6 The heating and cooling outputs will be energized no more than 6 times...

Страница 32: ...ction is changed from OF to 1 the period icons are shown and the minute segments of the clock display are shown The triangle icon next to the WAKE period will be on and a value between 0 and 60 will b...

Страница 33: ...t When configured for dehumidification the Rc terminal must be connected to one of the dry contact terminals This provides power to energize the dehumidify terminal on the cooling equipment when the d...

Страница 34: ...Lockout non programmable models only This selection allows the installer to limit access to the keypad Selections are OF off 1 2 OF off The user has full access to the keypad 1 The user has access to...

Страница 35: ...ng cycle on high stage If the cooling equipment is energized to satisfy a dehumidify demand only no cooling demand the latch will not be applied On The Y1 and Y Y2 outputs are simultaneously energized...

Страница 36: ...Two periods is a common commercial application and four periods is more common for residential This selection is not available if Option 24 has been set to nP to configure the Thermidistat Control for...

Страница 37: ...to the homeowner that it is time to call the dealer to have the UV Lights replaced Selections available are OF off 6 12 18 24 30 36 42 48 OF off The UV Light reminder is turned off and will never be...

Страница 38: ...d period time Default is OF off Option 31 Daylight Savings Time Configuration programmable models only This selection allows the installer to set the Thermidistat Control to automatically change by on...

Страница 39: ...llation This configuration allows the Thermidistat Control to compensate for the amount of heat generated by the Thermidistat Control electronics to allow more accurate sensing of the temperature sens...

Страница 40: ...mode press and hold the fan button for 15 seconds After 10 seconds the Thermidistat Control will enter Configuration Mode Continuing to hold the Fan button through 15 seconds will cause the Thermidist...

Страница 41: ...mable models pressing the button below the dehumidify icon shall toggle the state of the dry contact output On the non programmable models pressing the features button shall toggle the state of the dr...

Страница 42: ...icon through the FOLLOW SCHEDULE HOLD and VACATION selections If fixed temperatures are desired use SCHEDULE button to turn on arrow icon next to HOLD This will maintain setpoints not allowing them to...

Страница 43: ...lection to be adjusted and the UP DOWN buttons are used to change the setting Humidify setting may only be changed when heat mode is selected and Dehumidify setting may only be changed when cool mode...

Страница 44: ...the outdoor temperature de creases the humidity setpoint also decreases Settings ranging from 1 to 9 1 being the lowest and 9 the highest will be visible to the homeowner See Fig 15 for outdoor temper...

Страница 45: ...ed blower speed setpoint adjustment and equipment cycling are modified to provide added dehumidification A dehumidification setpoint separate from humidification setpoint is available to the homeowner...

Страница 46: ...ts when there is a dehumidify demand even if there is no cooling demand The limits are that the system may overcool up to 3_F but no more while attempting to satisfy a dehumidify demand Within this 3_...

Страница 47: ...ompletely This can be done without changing existing setpoints To Select Dehumidification programmable between NORMAL COOL TO and OFF Press the soft key below the dehumidify icon button to bring up de...

Страница 48: ...coils have the capability of removing this off delay On FK or FV Fan Coils set delay tap to 0 0 On standard fan coils a jumper can be cut to disable off delay Refer to fan coil Installation Instructio...

Страница 49: ...hich would occur during the normal 90 sec blower off delay See fan coil installation instructions for more information See Wiring Diagram Reference Chart and Fig 2 through 19 in Wiring Diagram section...

Страница 50: ...oor temperature the same as when occupied Vacation humidification can be turned off independently of occupied humidification While setting the Vacation setpoints the Vacation humidify setpoint is acce...

Страница 51: ...ceding stage has been on for 10 minutes When staging between compressor and electric heat or between compressor and furnace heat the time is configurable The timer is configurable via Option 17 This t...

Страница 52: ...anceled allowing the equipment to turn off immediately when the demand is removed Heat Cool Setpoints Desired Temperature A minimum difference of 1_F and maximum of 6_F is enforced between heating and...

Страница 53: ...fan output can be programmed based on period of the day When programming for each day and period the fan can be set to On or AUTO Dry Contact On the programmable models the dry contact that can be us...

Страница 54: ...as programmable fan Option 30 See Wiring Diagrams for more information TROUBLESHOOTING If the display module doesn t power up after power is applied check the Rc Rh and C terminals for 24VAC If 24VAC...

Страница 55: ...indicate in the outdoor temperature location E4 If Thermidistat Control s internal memory fails E4 will be displayed Replace Thermidistat Control E5 If Thermidistat Control cannot properly read humid...

Страница 56: ...Single stage HP RVS H HP Y Y2 Y Y2 O W2 B Y Y2 W W1 O W2 B W W1 Single stage HP RVS C 2S Y Y2 O W2 B Y Y2 Y Y2 W W1 W W1 Single stage HP RVS H 2S Y Y2 Y Y2 O W2 B Y Y2 W W1 O W2 B W W1 Two stage AC 2S...

Страница 57: ...AGE 1 COOL STAGE 2 HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 EM HEAT STAGE 1 Two stage Hybrid Heat RVS C 2S Y1 O W2 B Y1 Y Y2 O W2 B Y1 Y1 Y Y2 W W1 W W1 Two stage Hybrid Heat RVS H 2S Y1 Y1 Y Y2 Y1 O W2...

Страница 58: ...ge 1 W W1 W2 Compressor Y Y2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS...

Страница 59: ...G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sen...

Страница 60: ...Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor S...

Страница 61: ...c Dry Contact 1 D1 Dry Contact 2 D2 Aux Connection 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room...

Страница 62: ...24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor...

Страница 63: ...Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Se...

Страница 64: ...ng Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux Connection 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote R...

Страница 65: ...24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor...

Страница 66: ...4VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier S...

Страница 67: ...G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS A06581 Fig 26 Thermidista...

Страница 68: ...AC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Hu...

Страница 69: ...Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sens...

Страница 70: ...t Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidif...

Страница 71: ...an G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor...

Страница 72: ...eating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier...

Страница 73: ...G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor S...

Страница 74: ...ing Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier So...

Страница 75: ...Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier...

Страница 76: ...h Y Y2 Y Y2 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com...

Страница 77: ...Cooling Rc R Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote...

Страница 78: ...__________ Cooling Setpoint Value __________ Fan Auto or On C Home Away Sleep Settings Heat Cool Home ____ ____ Away ____ ____ Sleep ____ ____ D Schedule For Programmable Thermidistat Controls Period...

Страница 79: ...___ Auxiliary Heat Lockout Temperature Setting only available when heat pump is used and when outdoor air temperature sensor is present Option 09 _____ Heat Pump Lockout Temperature Option 10 _____ Re...

Страница 80: ...___ Maximum Heating Setpoint Option 28 _____ UV Light Reminder Option 29 _____ Humidifier Pad Reminder Option 30 _____ Programmable Fan programmable models only Option 31 _____ Daylight Savings Time C...

Отзывы: