46
non
−
programmable models, pressing the features button shall toggle the state of
the dry contact.
In a heat pump application, when the mode is set to “em heat” the auxiliary heat
will turn on for 3 minutes. The clock display will count down from 180 to 0
during this test.
TO TEST FAN
Fan button switches FAN icon between AUTO and On. While On is displayed,
G output will be energized, turning fan on. On some fan coils, fan continues to
operate for 90 sec after G signal is removed.
Final Settings
Be sure to press DONE to exit installer setup mode. If the system is to be left in
operation after installation is complete, use MODE button to select between
HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or
auto.
On the programmable models, the default setpoints and programmed schedule
conform to the Energy Star
requirements of the U.S. Department of Energy for
both heating and cooling. These provide energy saving temperature settings.
Refer to Table 1.
Table 1 – Energy Star Default Schedule
SCHEDULE
HEAT
COOL
Wake 6:00 AM
68
F/20
C
78
F/26
C
Day 8:00 AM
60
F/16
C
85
F/29
C
Evening 5:00 PM
68
F/20
C
78
F/26
C
Sleep 10:00 PM
60
F/16
C
82
F/28
C