7

S

Recovery cylinder service pressure rating must be 400
psig, DOT (Department of Transportation) 4BA400 or
DOT BW400.

S

Puron systems should be charged with liquid refrigerant.
Use a commercial type metering device in the manifold
hose when charging into suction line with compressor op-

erating.

S

Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low--side retard.

S

Use hoses with 700 psig service pressure rating.

S

Puron refrigerant, as with other HFCs, is only compatible
with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Polyol Ester oils absorb moisture rapidly. Do not expose oil
to atmosphere.

S

Polyol Ester oils may cause damage to certain plastics and
roofing materials.

S

Wrap all filter driers and service valves with wet cloth when
brazing.

S

factory approved, liquid--line filter drier is required on ev-

ery unit.

S

Do not use a TXV (thermostatic expansion valve) designed
for use with R--22 refrigerant. Refer to separate indoor unit

installation instructions for more details.

S

If using a suction line drier, do not leave in place for more
than 72 hours.

Heating Check Chart Procedure -- Heating Mode

To check system operation during heating cycle, refer to the

Heating check Chart on outdoor unit. This chart indicates whether
a correct relationship exists between system operating pressure and

air temperature entering indoor and outdoor units. If pressure and

temperature do not match on chart, system refrigerant charge may
not be correct. Do not use chart to adjust refrigerant charge.

NOTE

: When charging is necessary during heating season, charge

must be weighed in accordance with unit rating plate

±

0.6 oz./ft. of

3/8--in. liquid line above or below 25 ft. (7.6 m) respectively.
To calculate additional charge required for a 35--ft. (11 m) line set:
35 ft. (10.6 m) -- 25 ft. (7.6 m) = 10 ft. X 0.6 oz./ft. = 6 oz. of

additional charge.

CHECK CHARGE -- UNITS WITH TXV COOLING

METERING DEVICE

Factory charge amount and desired subcooling are shown on unit
rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F (21

_

C

and 38

_

C), and the indoor temperature is between 70

_

F and 80

_

F

(21

_

C and 27

_

C). Follow the procedure below:

Unit is factory charged for 15 ft (4.6 m) of line--set. Adjust charge

by adding or removing 0.6 oz/ft of 3/8 liquid line above or below
15 ft (4.6 m) respectively.
For standard refrigerant line lengths (80 ft/24 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any
adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (27

_

C), and the outdoor

temperature is in the favorable range, adjust system charge by
weight based on line length and allow the indoor temperature to

drop to 80

_

F (27

_

C) before attempting to check system charge by

subcooling method as described above.

If the indoor temperature is below 70

_

F (21

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15 ft (4.6 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.4 m) or greater than 20 ft

(6 m) vertical separation, See Long Line Guideline for special
charging requirements.

Units with Indoor Pistons

Units installed with indoor pistons require charging by the
superheat method. The following procedure is valid when indoor

airflow is within

±

21% of its rated CFM.

1. Operate unit a minimum of 10 minutes before checking

charge.

2. Measure suction pressure by attaching an accurate gauge to

suction valve service port.

3. Measure suction temperature by attaching an accurate

thermistor type or electronic thermometer to suction line at

service valve.

4. Measure

outdoor

air

dry--bulb

temperature

with

thermometer.

5. Measure indoor air (entering indoor coil) wet--bulb

temperature with a sling psychrometer.

6. Refer to Table 1. Find outdoor temperature and evaporator

entering air wet--bulb temperature. At this intersection, note

superheat.

7. Refer to Table 2. Find superheat temperature located in item

6 and suction pressure. At this intersection, note suction line
temperature.

8. If unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is
reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is
reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow--restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated
on chart.

MAINTENANCE

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

LUBRICATION
Compressor

Compressor contains factory oil charge; replace oil when lost. Use

Mobile 3MA--POE oil.

CLEANING COILS

Coil should be washed out with water or blown out with
compressor air. Note that the blow--thru design causes dirt and

debris to build up on the inside of the coils. Clean coil annually or
as required by location and outdoor air conditions. Inspect coil

monthly and clean as required. Fins are not continuous through

538B

Содержание PREFERRED 538B Series

Страница 1: ...n literature and attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current editions of the Canadian Electrica...

Страница 2: ...pes Matching of outdoor unit with indoor unit may require field replacement of piston Replace piston if required before connecting refrigerant lines See Fig 2 Piston replacement instructions are inclu...

Страница 3: ...formation Filter Drier Refer to Fig 4 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to 5 in 127 mm lon...

Страница 4: ...ction in unit control box A07429 Fig 6 538B Typical Control Circuit Connections NOTE Use No 18 AWG color coded insulated 35_C minimum wire If thermostat is located more than 100 ft 30 5 m from unit as...

Страница 5: ...alve indicated by a sudden rise of suction pressure before suction pressure reaches 20 psig If this occurs shut off unit immediately then frontseat the suction valve and remove and recover excess refr...

Страница 6: ...er on check for correct voltage at solenoid coil and for burned or overheated solenoid With unit operating other items can be checked such as frost or condensate on refrigerant lines Using a remote me...

Страница 7: ...operly charged system If the indoor temperature is above 80_F 27_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temper...

Страница 8: ...22 6 26 3 30 1 33 1 90 32 5 15 9 13 13 11 16 9 20 7 24 4 27 3 31 1 95 36 6 14 10 12 14 10 18 8 22 6 25 4 29 2 100 38 8 13 12 11 15 9 20 7 23 5 27 3 105 41 5 15 9 13 13 11 17 8 22 6 26 3 110 43 6 14 1...

Страница 9: ...NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07435 Fig 10 Troubleshootin...

Страница 10: ...tdoor Thermostat A07436 Fig 11 Troubleshooting the Heating Cycle Always Ask For Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and withou...

Отзывы: