background image

3

NOTE

: Accessory wind baffles should be used on all units with

accessory low ambient temperature control.
Field--fabricated snow or ice stands may be used to raise unit when

operation will be required during winter months. Units may also be

wall mounted using the accessory wall mounting kit.

A07396

Fig. 3

---

Lifting Unit with Sling

COMPLETE REFRIGERANT PIPING

CONNECTIONS

Outdoor units may be connected to indoor units using

field--supplied tubing of refrigerant grade and condition. See
Product Data for correct line sizes. Do not use less than 10 ft (3.05

m) of interconnecting tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4

mm) vertical rise to the valve connections on the outdoor

unit. If more than the recommended length is buried,

refrigerant may migrate to cooler, buried section during

extended periods of system shutdown. This causes refrigerant

slugging and could possibly damage the compressor at

start--up.

When more than 80 ft (24.4 m) of interconnecting tubing and more

than 20 ft (6.1 m) of vertical lift is used, consult the residential

Long Line Application Guide for required accessories. If either
refrigerant tubing or indoor coil is exposed to the atmosphere, the

system must be evacuated following good refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding unnecessary

turns and bends. Suspend refrigerant tubes so they do not damage
insulation on vapor tube and do not transmit vibration to structure.

Also, when passing refrigerant tubes through a wall, seal the

opening so that vibration is not transmitted to structure. Leave
some slack in refrigerant tubes between structure and outdoor unit

to absorb vibration. Refer to separate indoor unit installation
instructions for additional information.

Filter Drier

Refer to Fig. 4 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from

step 1.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05227

Fig. 4

---

Filter Drier Components

The filter drier must be replaced whenever the refrigeration system

is exposed to the atmosphere.
Only use factory specified liquid--line filter driers with rated
working pressures less than 600 psig.

NOTE

: Do not install a suction--line filter drier in liquid line.

Make Piping Sweat Connections

Remove plastic caps from liquid and suction service valves. Use

refrigerant grade tubing. Service valves are closed from the factory

and are ready for brazing. After wrapping the service valve with a
wet cloth, the tubing set can be brazed to the service valve using

either silver bearing or non--silver bearing brazing material.
Consult local code requirements. Refrigerant tubing and the indoor

coil are now ready for leak testing.

NOTE

: Unit is shipped with Puron (R--410A) refrigerant factory

charge indicated on nameplate.
Pass nitrogen or other inert gas through piping while brazing to

prevent formation of copper oxide.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to unit or service valves observe the

following:

S

Use a brazing shield.

S

Wrap service valves with wet cloth or use a heat sink

material.

Provide Safety Relief

A fusible plug is located in unit suction line; do not cap this plug.

If local code requires additional safety devices, install as directed.

MAKE ELECTRICAL CONNECTIONS

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

538B

Содержание PREFERRED 538B Series

Страница 1: ...n literature and attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current editions of the Canadian Electrica...

Страница 2: ...pes Matching of outdoor unit with indoor unit may require field replacement of piston Replace piston if required before connecting refrigerant lines See Fig 2 Piston replacement instructions are inclu...

Страница 3: ...formation Filter Drier Refer to Fig 4 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to 5 in 127 mm lon...

Страница 4: ...ction in unit control box A07429 Fig 6 538B Typical Control Circuit Connections NOTE Use No 18 AWG color coded insulated 35_C minimum wire If thermostat is located more than 100 ft 30 5 m from unit as...

Страница 5: ...alve indicated by a sudden rise of suction pressure before suction pressure reaches 20 psig If this occurs shut off unit immediately then frontseat the suction valve and remove and recover excess refr...

Страница 6: ...er on check for correct voltage at solenoid coil and for burned or overheated solenoid With unit operating other items can be checked such as frost or condensate on refrigerant lines Using a remote me...

Страница 7: ...operly charged system If the indoor temperature is above 80_F 27_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temper...

Страница 8: ...22 6 26 3 30 1 33 1 90 32 5 15 9 13 13 11 16 9 20 7 24 4 27 3 31 1 95 36 6 14 10 12 14 10 18 8 22 6 25 4 29 2 100 38 8 13 12 11 15 9 20 7 23 5 27 3 105 41 5 15 9 13 13 11 17 8 22 6 26 3 110 43 6 14 1...

Страница 9: ...NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07435 Fig 10 Troubleshootin...

Страница 10: ...tdoor Thermostat A07436 Fig 11 Troubleshooting the Heating Cycle Always Ask For Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and withou...

Отзывы: