background image

 

 

7

 

 

Figure 7: Thermostat wiring, heating and air cond. heat 

pump with ECM v. speed motor 

 

 

Note: On units with 2 stage cooling or heat pump, terminal Y1 
must be used. When Y1 on the electronic control receives a 24 
VAC signal, the air flow is reduced by 20%. Do not use 
terminal Y1 with a single stage cooling or heat pump. 

2.5 INSTALLATION

 

OF

 

THE

 

BURNER

 

 

Refer to the burner manufacturer’s instructions. Also, the 
burner must be installed always in the same way 
independently of the furnace orientation.  

 

1.  Position the mounting gasket between the mounting 

flange and the burner mounting plate. Align the holes in 
the burner mounting plate with the studs on the mounting 
flange and bolt securely in place. 

2.  Remove the burner drawer assembly or the air tube 

assembly; 

3.  Install the nozzle, refer to Technical Specifications Table 

6; 

4.  Check the electrode settings; 

5.  Make the electrical connections; 

6.  Complete oil line connections. 

2.5.1 Nozzles 

The burner comes equipped with an appropriate nozzle. 
However, if another size or a replacement nozzle is 
required, use the manufacturer’s recommended spray 
angle and type a shown in Table 6 and based on a pump 
pressure of 100 psi.  

 

Always select nozzle sizes by working back from the 
desired flow rate at operating pressure and not the nozzle 
marking. 

2.5.2  Air and Turbulator Settings 

Before starting the burner for the first time, adjust the air 
and turbulator settings to those listed in this manual, Table 
6. Once the burner becomes operational, final 
adjustments will be required. Refer to section 3 of this 
manual. 

2.5.3  Post purge delay adjustment 

The post purge delay on the oil-fired burners is factory set 
to zero second. This delay is applicable for all installations 
with chimney venting. For heating units installed with side 
wall venting and a burner equipped with this feature, the 
post purge delay must be set to 15 seconds.  Refer to the 
burner control instruction manual and markings for proper 
adjustment of the post purge delay. 

2.6 VENTING 

WARNING 

 

Poisonous carbon monoxide gas, fire and explosion 
hazard. 

 

Read and follow all instructions in this section. 
Failure to properly vent this furnace can result in in 
death, bodily injury and/or property damage. 

 

To ensure the safe and proper functioning of an oil 
furnace, it must always be connected to a flue with 
sufficient draft or to an approved side-wall venting system. 
In addition, it is strongly recommended to perform a 
complete inspection of all the existing venting systems. 

 

WARNING

 

 

Poisonous carbon monoxide gas hazard. 

 

Never install a hand operated damper in the vent pipe. 
However, any Underwriters Laboratories listed, 
electrically operated automatic type vent damper may 
be installed if desired. Be sure to follow the 
instructions provided with vent damper. Also, read 
and follow all instructions in this section of the 
manual. 

 

Failure to properly vent this furnace or other 
appliances can result in death, bodily injury and/or 
property damage. 

Содержание OBM098

Страница 1: ...on in this booklet to service the appliance and affix the booklet adjacent to the appliance after servicing C US Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the progr...

Страница 2: ...VENTING 8 2 8 COMBUSTION AIR SUPPLY AND VENTILATION 8 2 9 OIL TANK 9 2 10 DUCTING 9 2 11 SUPPLY AIR ADJUSTMENTS 4 SPEED MOTORS 9 2 12 SUPPLY AIR ADJUSTMENTS ECM VARIABLE SPEED MOTORS 10 2 13 INSTALLA...

Страница 3: ...d motor PSC 23 Table 11 Parts list with variable speed motor ECM 25 FIGURES Figure 1 Location and dimensions of ventilation air openings in a closet door 5 Figure 2 Upflow installation 5 Figure 3 Down...

Страница 4: ...ired information such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must c...

Страница 5: ...nstallation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to premature failure of the...

Страница 6: ...2 3 ELECTRICAL SYSTEM CAUTION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied wit...

Страница 7: ...he air and turbulator settings to those listed in this manual Table 6 Once the burner becomes operational final adjustments will be required Refer to section 3 of this manual 2 5 3 Post purge delay ad...

Страница 8: ...se of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furna...

Страница 9: ...ance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal duct...

Страница 10: ...OSITION Input USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel b...

Страница 11: ...stop delays are satisfactory 9 The thermostat of the room is in the heating mode and is set higher than the ambient temperature To start the unit turn the main electrical switch on 3 2 OPERATING SEQU...

Страница 12: ...located above the burner is a measurement necessary to determine if there is a blockage in the heat exchanger or the flue pipe Refer to the Technical Specifications in this manual for overfire pressu...

Страница 13: ...xchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the burn...

Страница 14: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure Lb in 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 15: ...t turbulator damper 0 3 25 0 4 1 5 25 0 3 25 0 4 1 5 25 AFUE FromCSA B212 standard and Canadian regulation 85 0 84 2 81 9 85 0 84 2 81 9 AFUE FromASHRAE103 standard and USregulation 85 0 83 9 81 9 85...

Страница 16: ...F 2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 30 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Le...

Страница 17: ...URNACE2 N A 5 08 cm 2 N A FLUEPIPE AROUND FLUEPIPE 22 86 cm 9 22 86 cm 9 22 86 cm 9 FRONT FURNACE BURNER SIDE 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 1 These are horizontal dimensions 2 These are vertic...

Страница 18: ...18 Figure 9 Furnace dimensions...

Страница 19: ...19 Figure 10 Wiring diagram 4 speed motor PSC...

Страница 20: ...20 Figure 11 Wiring diagram variable speed motor ECM...

Страница 21: ...21 COMPONENTS AND REPLACEMENT PARTS...

Страница 22: ...22 Figure 12 Parts list with 4 speed motor PSC B50064G...

Страница 23: ...PANEL ASSEMBLY LEFT Panel insulation and baffle included 31 B03480 FILTER RACK KIT 32 B03450 02 LATERAL BAFFLE 33 B30513 BLOWER SLIDE One slide included 34 B03441 BLOWER DIVIDER 35 B03451 REAR BAFFLE...

Страница 24: ...24 Figure 13 Parts list with variable speed motor ECM B50074H...

Страница 25: ...8 B03470 FLOOR 29 B03426 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 30 B03480 FILTER RACK KIT 31 B03450 02 LATERAL BAFFLE 32 B30513 BLOWER SLIDE One slide included 33 B03441 BLOW...

Страница 26: ...RVICE Utiliser l information contenue dans ce manuel afin d effectuer l entretien de l appareil Garder ce manual pr s de l unit pour r f rences ult rieures C US Use of the AHRI Certified TM Mark indic...

Страница 27: ...R SERVOIR DE MAZOUT 10 2 10 SYST ME DE DISTRIBUTION D AIR 10 2 11 AJUSTEMENT DES D BITS D AIR DE VENTILATION MOTEUR 4 VITESSES 10 2 12 AJUSTEMENT DES D BITS D AIR DE VENTILATION MOTEUR VITESSE VARIABL...

Страница 28: ...11 Diagramme lectrique moteur vitesse variable ECM 21 Figure 12 Liste de pi ces avec moteur 4 vitesses PSC 23 Figure 13 Liste de pi ces avec moteur vitesse variable ECM 25 TABLEAUX Tableau 1 Ajusteme...

Страница 29: ...iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service ayez en main la page de la fiche technique section 5 de ce manuel pou...

Страница 30: ...e chauffage au mazout ANSI NFPA 90B Syst mes de chauffage air chaud et syst me d air climatis ANSI NFPA 211 Chemin e Foyers vents et appareils de chauffage ANSI NFPA 70 Code National d lectricit CSA C...

Страница 31: ...e pour un retour par le plancher FRB 101 ou KLARB0101DET Le br leur doit toujours tre install dans le m me sens peu importe l orientation de la fournaise Voir figure 3 pour plus de d tails Figure 3 D...

Страница 32: ...uffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 4 INSTALLATION DU THERMOSTAT L installation d un thermostat de contr le de la temp rature de l...

Страница 33: ...contr le du br leur pour plus de d tail concernant l ajustement du d lai post purge 2 6 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions...

Страница 34: ...rme APPELER UN TECHNICIEN QUALIFI 2 8 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone R f rer aux codes d installation des appareils...

Страница 35: ...tour de mazout vers le r servoir avec une pompe appropri une l vation de 2 4 m 8 et plus requi rent une pompe deux stage et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives...

Страница 36: ...T Chauffage Position interrupteurs DIP 1 2 POSITION Consommation USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL Tableau 3 Ajustements des d bits d air mode climatisation SW2 COOL Climati...

Страница 37: ...br leur est conforme aux tableaux des sp cifications de ce manuel 7 L ajustement des vitesses de ventilation en chauffage et climatisation sont ad quats et selon les sp cifications de ce manuel 8 Les...

Страница 38: ...es pins l horizontale et le devant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r gulateur de tirage apr s que l appareil ait fonctionn e au moins cinq minut...

Страница 39: ...l interrupteur d alimentation principal de la fournaise est en position ON 4 Ajuster le thermostat au dessus de la temp rature ambiante 5 Si l allumage du br leur de s effectue pas couper l alimentati...

Страница 40: ...ILE Filtre du r servoir Remplacer le filtre du r servoir au besoin Suivre les instructions du fabriquant Filtre secondaire Remplacer les cartouches des filtres de 10 microns ou moins une fois par ann...

Страница 41: ...AFUE partir du standard CSAB212 et des lois canadiennes 85 0 84 2 81 9 85 0 84 2 81 9 AFUE partir du standard ASHRAE103 et des lois am ricaines 85 0 83 9 81 9 85 0 83 9 81 9 BR LEUR RIELLO MOD LE40 B...

Страница 42: ...0 D 1 ON 2 ON 1 5 600 660 540 SW4 D LAI Position interrupteurs DIP Consommation Chauffage USGPH PreRun D lai On Niveau PCM Temps ShortRun D lai On NiveauPCM Temps D lai Off Niveau PCM Temps A 1 OFF 2...

Страница 43: ...cm 2 N A TUYAU DE RACCORDEMENT DEVANT FOURNAISE C T BR LEUR 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 1 Ce sont des dimensions horizontales 2 Ce sont des dimensions verticales 3 Pour respecter cette dime...

Страница 44: ...19 Figure 9 Dimensions de la fournaise...

Страница 45: ...20 Figure 10 Diagramme lectrique moteur 4 vitesses PSC...

Страница 46: ...21 Figure 11 Diagramme lectrique moteur vitesse variable ECM...

Страница 47: ...22 COMPOSANTES ET PI CES DE REMPLACEMENT...

Страница 48: ...23 B50064G Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...

Страница 49: ...t d flecteur 31 B03480 KIT SUPPORT A FILTRE 32 B03450 02 DEFLECTEUR LATERAL 33 B30513 GLISSIERE DU VENTILATEUR Comprend une seule glissi re 34 B03441 SEPARATEUR DU VENTILATEUR 35 B03451 DEFLECTEUR ARR...

Страница 50: ...25 B50074G Figure 13 Liste de pi ces avec moteur vitesse variable ECM...

Страница 51: ...UCHE Comprend panneau isolation et d flecteur 30 B03480 KIT SUPPORT A FILTRE 31 B03450 02 DEFLECTEUR LATERAL 32 B30513 GLISSIERE DU VENTILATEUR Comprend une seule glissi re 33 B03441 SEPARATEUR DU VEN...

Отзывы: