background image

3. Auto Humidify

This feature is designed to eliminate the problem of
sweating windows in very cold weather. When selected, the
set point is automatically reduced by 1 percent for every
drop of 2°F in outdoor temperature between 50°F and 0°F.
The set point may be changed at any time, and it will
continue to track outdoor temperature from the new set
point and current outdoor temperature. The adjusted set
point range is still limited to between 10 and 45 percent
relative humidity. To use this feature, an outdoor tempera-
ture sensor MUST be attached. If not, E3 error message will
be displayed.

4. Auto and Fan Humidify

The 2 choices of AUTO and FAN can be selected together.
This provides both functions simultaneously.

5. Humidify Off

The humidify function can be turned off completely. This
does not require changing existing set points.

TO SELECT HUMIDIFICATION (BETWEEN NORMAL,
FAN, AUTO, FAN AND AUTO, OR OFF) (SEE TABLE 4.)

Press HUMIDITY button to bring up humidity select screen. It is
indicated by "hu" or "dhu" in clock display. Successive presses
will change between "hu" and "dhu" in clock display. Select "hu"
for humidity functions. The large display shows actual humidity
level. The smaller display (in heat set point location) shows
humidity set point (HSP) or OF (off). When HSP value is
displayed, its value can be changed with up and down buttons.
Successive presses of MODE button will move between 5 choices
described above and each will be indicated as shown in Table 4.

To exit humidity select screen, press END button.

ADDITIONAL HUMIDIFY COMMENTS

The humidifier is actually turned on when humidity is 2 percent
below set point and turned off when it reaches 2 percent above set
point. This built-in hysteresis prevents humidify output from
toggling on and off when humidity level is near set point.

The vacation mode provides some additional humidification func-
tions. These are specially designed to provide protection for an
unoccupied home while simultaneously minimizing energy use.
Refer to "Vacation" section for additional information.

B.

Dehumidification

Dehumidification is done only during cooling. Depending on type
of equipment used, compressor speed, blower speed, set point
adjustment, and equipment cycling are modified to provide added

dehumidification. A dehumidification set point (separate from
humidification set point) is available to the homeowner. It can
range from 50 to 90 percent relative humidity. When actual
humidity is higher than set point, a dehumidification demand
exists. The Thermidistat Control responds by activating its dehu-
midify output. It may also control the compressor and blower,
depending on equipment type and dehumidify selection choice.
The 3 available selections are described below.

The amount of extra dehumidification available is very dependent
on the type of equipment in the home. Without a variable-speed
blower, the system’s ability to adjust dehumidification is very
limited.

1. Normal Dehumidify Operation

When normal dehumidify is selected, the compressor will
not turn on without a cooling demand. If dehumidify
demand exists while cooling, dehumidify output will also
be active (24vac removed). This output commands variable-
speed blowers to reduce their airflow, which improves
water removal from the cooled air.

2. Cool to Dehumidify

The cool to dehumidify selection tells the system to operate
the compressor, within limits, when there is a dehumidify
demand even if there is no cooling demand. The limits are
that the system may overcool up to 3°, but no more, while
attempting to satisfy a dehumidify demand. Within this 3°
range, there is an additional balance between overcooling
and humidity satisfaction. When overcooling must occur,
the dehumidify set point is adjusted upward by 2 percent per
degree of overcooling. For example, a cooling set point of
76°F and a dehumidify set point of 60 percent is equivalent
to a cooling set point of 75°F and a dehumidify set point of
62 percent. This dehumidify set point change is internal to
the Thermidistat Control and is not shown on the display.

During cool-to-dehumidify demand, the compressor runs a
maximum of 10 minutes on, followed by 10 minutes off.
When the compressor turns off, the fan (G output) is also
turned off immediately. The immediate fan shutoff prevents
re-evaporation of water on the coil, improving dehumidifi-
cation. If fan is set to continuous, the G (fan on) signal is
removed for 5 minutes starting when compressor turns off.

In most furnaces and fan coils, the blower operates for 90
sec after both Y and G disappear. This 90-sec delay should
be removed, if possible, for maximum dehumidification
performance. Consult furnace or fan coil Installation In-
structions to see if delay can be disabled.

TABLE 2—EQUIPMENT OUTPUTS

1-SPEED AC

2-SPEED AC

1-SPEED HP

2-SPEED HP

Cool—0 to 2 minutes

Y, G

Y1, G

Y, G, O

Y1, G, O

Cool—2 to 4 minutes

Y, G

Y1, Y2, G

Y, G, O

Y1, Y2, G, O

Heat—0 to 2 minutes

W1

W1

Y, G

Y1, G

Heat—2 to 4 minutes

W1, W2

W1, W2

Y, G

Y1, Y2, G

Eheat—0 to 2 minutes

---

---

W1

W1

Eheat—2 to 4 minutes

---

---

W1, W2†

W1*

* Two-stage heat not available

NOTE: For Y—use terminal Y/Y2, for Y1—use terminal Y1/W2, for W2—use terminal O/W2,

for O—use terminal O/W2, for W1—use terminal W/W1, for W2†, use terminal Y1/W2

TABLE 4—HUMIDIFICATION SELECTIONS

SELECTION

MODE DISPLAY

FAN DISPLAY

HUMIDIFY SP

DISPLAY

Normal Humidify

Blank

Blank

HSP Value

Fan Humidify

Blank

FAN

HSP Value

Auto Humidify

AUTO

Blank

HSP Value

Auto and Fan

AUTO

FAN

HSP Value

Humidify Off

Blank

Blank

OF

—8—

Содержание II TSTAT-0-16

Страница 1: ...mable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal mem...

Страница 2: ...O SET OFF for normal operation This is factory default ON for installer test mode III INSTALL THERMIDISTAT CONTROL WARNING Before installing Thermidistat Control turn off all power to equipment There...

Страница 3: ...small display and available selections within each option large display D Configuration Options Selection OPTION 1 ANTICIPATOR ADJUSTMENT This adjustment controls sensitivity and cycle rate of Thermi...

Страница 4: ...ll Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode...

Страница 5: ...ons 1 2 and 3 For most heaters W1 is lower wattage heater and W2 is higher although some have equal elements for W1 and W2 Consult fan coil heater combination for the actual wattage connected to each...

Страница 6: ...ould be considered permanent Once the change to non programmable operation is done a procedure is not provided to easily change it back Should this change be needed it is best to trade the Thermidista...

Страница 7: ...he U S Department of Energy for both heating and cooling These provide energy saving tempera ture settings Refer to Table 3 If programmed schedule is to be used make sure HOLD icon is off This feature...

Страница 8: ...equipment type and dehumidify selection choice The 3 available selections are described below The amount of extra dehumidification available is very dependent on the type of equipment in the home With...

Страница 9: ...n on high humidity thus removing a 24 vac signal to initiate dehumidification Equip ment has been designed to operate in this manner so the Thermidistat Control must now accommodate the existing equip...

Страница 10: ...TEM PERATURE button C Fifteen Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning on until preceding stage has been on for 15 minutes This timer is...

Страница 11: ...TDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 1 6 13 and 15 Fig 6 Typical Fan Coil With 2 Speed Heat Pump A97385 O W2 Y1 W2 W W1 G R E W3 THERMIDISTAT TYPICAL FAN COIL 2 SPEE...

Страница 12: ...1 2 6 13 and 15 REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 FK Series Fan Coil With 2 Speed Heat Pump A98281 O W2 W W1 Y1 W2 G R O Y1 THERMIDISTAT FK SERIES FAN COIL...

Страница 13: ...OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR Fig 14 Single Stage Furnace With 2 Speed Heat Pump Dual Fuel A97394 O W2 W W1 Y1 W2 G R THERMIDISTAT 1 STAGE FURNACE 2 SPEED HEAT PUMP W...

Страница 14: ...UTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 13 and 15 Fig 18 Two Stage Furnace With 2 Speed Heat Pump Dual Fuel A97398 O W2 W W1 Y1 W2 G R THERMIDISTAT 2 STAGE FURNACE 2...

Страница 15: ...SOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 12 13 and 15 Fig 22 Variable Speed 2 Stage Non Condensing Furnace With 2 Speed Heat Pump Dual Fuel A97437 O W2 W W1 Y1 W2 G R THERM...

Страница 16: ...NNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 and 15 DH HUM Fig 26 Variable Speed 2 Stage Condensing Furnace Without DE Connection With 2 Speed Heat Pump Dual Fuel A97421 O W2 W...

Страница 17: ...R SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 15 and 18 Fig 30 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump A98285 O W2 Y1 W2 W...

Страница 18: ...attached in all dual fuel applications 10 Refer to indoor equipment Installation Instructions for proper setup 11 To activate dehumidify feature on older style variable speed furnaces Bryant 335MAV t...

Страница 19: ...ed recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time The fixed time period is 1 5 hr It operates in both heating and cooling This o...

Страница 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Отзывы: