background image

OPTION 14—HEAT/COOL DEAD BAND ADJUSTMENT

This option selects the minimum difference between heat and cool
set points. A larger difference saves energy and a smaller differ-
ence decreases temperature difference between heating and cool-
ing. Factory default is 2, which means cooling set point must be a
minimum of 2° above heating set point. An attempt to move them
closer will result in one "pushing" the other to maintain the
required difference.

Depending on set points, moving dead band closer than 2° may
result in regular cycling between heat and cool when AUTO mode
is selected. However, this cycling cannot occur more often than 1
transition every 20 minutes. The system has a built-in requirement
that it cannot switch between heat and cool without a 20 minute
"off" time between the 2 operations. Specifically, to switch from 1
mode to the other, there must be no demand for the old mode and
a demand for the new mode, and this must exist continually for 20
minutes before transition to the new mode will occur.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4

"To enter Configuration Mode." Use up and down buttons
to make small (now flashing) display indicate 14.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up or down buttons to move between 0, 1, 2, 3, 4, 5, or

6 on large display. Factory default is 2.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

OPTION 15—ENABLE AUTO MODE

This option allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE
button are used to move between OFF, HEAT, COOL, and
EHEAT (in heat pump systems). Factory default is ON (AUTO
enabled).

TO SELECT:

1. Enter configuration mode if not already there. See Step 4

"To Enter Configuration Mode." Use up and down buttons
to make small (now flashing) display indicate 15.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between OF and ON on

large display. Factory default is ON (AUTO enabled).

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

OPTION 16—RESERVED FOR FUTURE USE

OPTION 17—ENABLE NON-PROGRAMMABLE OPERA-
TION

This option converts the programmable Thermidistat Control to a
non-programmable control for those users who do not want
programmability. The clock is retained, but the days of the week
and the daily schedules have been eliminated, making it operate as
if HOLD were permanently ON. Some of the buttons (used in
programming only and now not needed) are redefined to simplify
the non-programmable operation. To match these redefined but-
tons, a new keypad label, included with the Thermidistat, must be
placed over the original keypad label. Fig. 2 shows both the
original keypad label and the non-programmable keypad label.
When this option is selected, the new keypad label must be applied
over (or in place of) the original. Because these adhesive-backed
keypad labels are not designed to be removed, this conversion
should be considered permanent. Once the change to non-
programmable operation is done, a procedure is not provided to
easily change it back. Should this change be needed, it is best to
trade the Thermidistat for one which has not been converted.

Both programmable and non-programmable versions of the Ho-
meowner’s Manual are available.

Once it has been determined that a particular installation is to be
made non-programmable, the only changes required are:

Attach non-programmable keypad label over original program-
mable one.

Set Configuration Option No. 17 to ON.

To attach the provided non-programmable keypad label, carefully
peel off its backing and apply it over the original keypad label.
PLEASE HEED: Once the new keypad label makes contact, it will
stick firmly in place and adjustments cannot be made. CARE-
FULLY locate an edge of the keypad label, making sure its
position and orientation are correct. Then, from the attached edge,
smooth the rest of the keypad label over the original. Make sure the
new keypad label does not interfere with the motion of the buttons
which it surrounds.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4

"To Enter Configuration Mode." Use up and down buttons
to make small (now flashing) display indicate 17.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between OF and ON on

large display. Factory default is OF.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

E.

Redefinition of Buttons

Fig. 2 shows the original (programmable) button labels on the left
and the redefined (non-programmable) buttons on the right. In the
figure, the buttons are numbered for easy reference. They are not
numbered on the actual product. Six of the buttons (numbers 1
through 5 and 9) have been redefined.

Button 3 originally alternated between time, cool set point, and
heat set point with each press. Now, button 1 selects the cool set
point, button 2 selects the heat set point, and button 3 selects time,
now used only to set the clock. Note that the days of the week are
gone.

Button 5 used to alternate between humidify and dehumidify. Now
button 4 selects dehumidify and button 5 selects humidify.

Button 9 now loses the HOLD label, making it END only. This
button is only used to END the humidity screen and the configu-
ration mode.

These changes both simplify operation for the homeowner and find
use for the buttons which are no longer needed when programma-
bility is removed.

V.

SYSTEM START-UP AND CHECKOUT

The Thermidistat Control is designed with a built-in installer test
capability. It allows easy operation of equipment without delays or
set point adjustments to force heating or cooling.

To enable installer test mode, move DIP switch No. 4 to ON
position. To access this switch, open case as described in Step 2.
Use the corner of a small screwdriver to slide switch No. 4 to ON
position.

While in installer setup mode, clock will display "InSt," FAN
button will control fan, and MODE button will control heating and
cooling.

A.

To Test Fan:

F,an button switches FAN icon between AUTO and ON. While
ON is displayed, G output will be on, turning fan on. Allow up to
10 sec after button is pressed for fan to turn on and off. On some
fan coils, fan continues to operate for 90 sec after G signal is
removed.

—6—

Содержание II TSTAT-0-16

Страница 1: ...mable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal mem...

Страница 2: ...O SET OFF for normal operation This is factory default ON for installer test mode III INSTALL THERMIDISTAT CONTROL WARNING Before installing Thermidistat Control turn off all power to equipment There...

Страница 3: ...small display and available selections within each option large display D Configuration Options Selection OPTION 1 ANTICIPATOR ADJUSTMENT This adjustment controls sensitivity and cycle rate of Thermi...

Страница 4: ...ll Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode...

Страница 5: ...ons 1 2 and 3 For most heaters W1 is lower wattage heater and W2 is higher although some have equal elements for W1 and W2 Consult fan coil heater combination for the actual wattage connected to each...

Страница 6: ...ould be considered permanent Once the change to non programmable operation is done a procedure is not provided to easily change it back Should this change be needed it is best to trade the Thermidista...

Страница 7: ...he U S Department of Energy for both heating and cooling These provide energy saving tempera ture settings Refer to Table 3 If programmed schedule is to be used make sure HOLD icon is off This feature...

Страница 8: ...equipment type and dehumidify selection choice The 3 available selections are described below The amount of extra dehumidification available is very dependent on the type of equipment in the home With...

Страница 9: ...n on high humidity thus removing a 24 vac signal to initiate dehumidification Equip ment has been designed to operate in this manner so the Thermidistat Control must now accommodate the existing equip...

Страница 10: ...TEM PERATURE button C Fifteen Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning on until preceding stage has been on for 15 minutes This timer is...

Страница 11: ...TDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 1 6 13 and 15 Fig 6 Typical Fan Coil With 2 Speed Heat Pump A97385 O W2 Y1 W2 W W1 G R E W3 THERMIDISTAT TYPICAL FAN COIL 2 SPEE...

Страница 12: ...1 2 6 13 and 15 REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 FK Series Fan Coil With 2 Speed Heat Pump A98281 O W2 W W1 Y1 W2 G R O Y1 THERMIDISTAT FK SERIES FAN COIL...

Страница 13: ...OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR Fig 14 Single Stage Furnace With 2 Speed Heat Pump Dual Fuel A97394 O W2 W W1 Y1 W2 G R THERMIDISTAT 1 STAGE FURNACE 2 SPEED HEAT PUMP W...

Страница 14: ...UTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 13 and 15 Fig 18 Two Stage Furnace With 2 Speed Heat Pump Dual Fuel A97398 O W2 W W1 Y1 W2 G R THERMIDISTAT 2 STAGE FURNACE 2...

Страница 15: ...SOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 12 13 and 15 Fig 22 Variable Speed 2 Stage Non Condensing Furnace With 2 Speed Heat Pump Dual Fuel A97437 O W2 W W1 Y1 W2 G R THERM...

Страница 16: ...NNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 and 15 DH HUM Fig 26 Variable Speed 2 Stage Condensing Furnace Without DE Connection With 2 Speed Heat Pump Dual Fuel A97421 O W2 W...

Страница 17: ...R SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 15 and 18 Fig 30 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump A98285 O W2 Y1 W2 W...

Страница 18: ...attached in all dual fuel applications 10 Refer to indoor equipment Installation Instructions for proper setup 11 To activate dehumidify feature on older style variable speed furnaces Bryant 335MAV t...

Страница 19: ...ed recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time The fixed time period is 1 5 hr It operates in both heating and cooling This o...

Страница 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Отзывы: