background image

B.

To Test Cooling and Dehumidification:

Press MODE button until COOL icon turns on. Cooling begins
within 10 sec and remains on for 4 minutes. If system is 2-speed,
low speed comes on for first 2 minutes, followed by high speed for
second 2 minutes. At the end of 4-minute run, cooling stops, and
MODE reverts back to OFF. At any time during 4-minute run time,
cooling may be turned off by pressing MODE button until OFF
appears. While cooling is on, successive presses of HUMIDITY
button turn dehumidify output on and off. While this output is
active, "dhu" appears in cool set point display. Equipment outputs
for different equipment types are listed in Table 2.

C.

To Test Primary Heating and Humidification:

Press MODE button until HEAT icon turns on. Primary heating
begins within 10 sec and remains on for 4 minutes. This will be
furnace or electric heat in AC system and heat pump heating in
heat pump system. If system has 2 stages of primary heat, first
stage will be on for 2 minutes followed by second stage for 2
minutes. At the end of 4-minute run, heating stops, and MODE
reverts back to OFF. At any time during 4-minute run time, heating
may be turned off by pressing MODE button until OFF appears.
While heating is on, successive presses of HUMIDITY button turn
humidify output on and off. While this output is active, "hu"
appears in heat set point display. Equipment outputs for different
equipment types are listed in Table 2.

D.

To Test Auxiliary Heating:

Auxiliary heating only exists in heat pump systems. To test, press
MODE button until EHEAT icon turns on. This will be electric
heat in standard heat pump systems and furnace in dual fuel
systems. Auxiliary heating begins within 10 sec and remains on for
4 minutes. If there are 2 stages of auxiliary heat, first stage comes
on for 2 minutes followed by second stage for 2 minutes. At the
end of 4-minute run, heating stops and MODE reverts back to
OFF. At any time during 4-minute run time, heating may be turned
off by pressing MODE button until OFF appears. Actual outputs
for different equipment types are listed in Table 2.

VI.

FINAL SETTINGS

Be sure to return DIP switch No. 4 back to OFF position to exit
installer setup mode. Assuming system is to be left in operation
after installation is complete, use MODE button to select between
HEAT, COOL, or AUTO to provide desired operation of heating,
cooling, or both.

The default set points and programmed schedule conform to the
Energy Star® requirements of the U.S. Department of Energy for
both heating and cooling. These provide energy saving tempera-
ture settings. Refer to Table 3.

If programmed schedule is to be used, make sure HOLD icon is
off. This feature is turned on and off by HOLD button.
If fixed temperatures are desired, use HOLD button to turn on
HOLD icon. This will maintain set points, not allowing them to
change with programmed schedule.
The FAN button may be used to select between AUTO (fan on
only with equipment) and FAN (fan on continuously) fan modes.
For further information on temperature selection and program-
ming, refer to Homeowner’s Guide.

HUMIDITY CONTROL FEATURES

The various humidity control features of the Thermidistat Control
are explained below. They are grouped into 2 sections: humidifi-
cation and dehumidification. At the end of each section, instruc-
tions on how to select each feature are given.

A.

Humidification

The Thermidistat Control directly connects to a standard 24-vac
humidifier to control humidification in the home. A humidify set
point between 10 and 45 percent relative humidity is selected by
the homeowner, or all humidification can be turned off. When
humidity in home drops below set point, humidifier will be turned
on to raise humidity level. Humidification can only occur in
heating mode (HEAT or AUTO/HEAT). Five different humidifi-
cation selections are available and are described below.

1. Normal Humidify

In normal humidify, humidifier will be on if there is a
humidity demand and any heating equipment is on. This
will include furnace, heat pump, or auxiliary heat. In heat
pump applications, this is an improvement over using an
external humidistat, which only supplies humidity when
auxiliary heat is on.

2. Fan Humidify

This configuration allows a humidify demand to turn on fan
and humidifier together, even if there is no heat demand. It
is particularly useful when the furnace is oversized, result-
ing in short heating cycles. It allows the humidifier to run
longer, supplying more humidity to the home. Note that fan
hours will increase, using more electricity. Also, the hu-
midifier delivers less moisture to cooler air than it does to
heated air.

Fig. 2—Programmable/Non-Programmable Keypad Labels

A98286

SET COOL

SET DHUM

MODE

SET HEAT

SET HUM

Reset

Filter

FAN

SET TIME

VACATION

END

1

2

5

8

4

7

3

6

9

Reset

Filter

1

2

5

8

4

7

3

6

9

NON-PROGRAMMABLE CONFIGURATION

(OPTION 17 ON)

PROGRAMMABLE CONFIGURATION

(OPTION 17 OFF)

COPY PREVIOUS DAY

PROGRAM

MODE

SET TIME/TEMP

VACATION

HOLD/END

CHANGE DAY

HUMIDITY

FAN

TABLE 3—ENERGY STAR DEFAULT SCHEDULE

SCHEDULE

HEAT

COOL

Wake 6:00 AM

68°F

78°F

Day 8:00 AM

60°F

85°F

Evening 5:00 PM

68°F

78°F

Sleep 10:00 PM

60°F

82°F

—7—

Содержание II TSTAT-0-16

Страница 1: ...mable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal mem...

Страница 2: ...O SET OFF for normal operation This is factory default ON for installer test mode III INSTALL THERMIDISTAT CONTROL WARNING Before installing Thermidistat Control turn off all power to equipment There...

Страница 3: ...small display and available selections within each option large display D Configuration Options Selection OPTION 1 ANTICIPATOR ADJUSTMENT This adjustment controls sensitivity and cycle rate of Thermi...

Страница 4: ...ll Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode...

Страница 5: ...ons 1 2 and 3 For most heaters W1 is lower wattage heater and W2 is higher although some have equal elements for W1 and W2 Consult fan coil heater combination for the actual wattage connected to each...

Страница 6: ...ould be considered permanent Once the change to non programmable operation is done a procedure is not provided to easily change it back Should this change be needed it is best to trade the Thermidista...

Страница 7: ...he U S Department of Energy for both heating and cooling These provide energy saving tempera ture settings Refer to Table 3 If programmed schedule is to be used make sure HOLD icon is off This feature...

Страница 8: ...equipment type and dehumidify selection choice The 3 available selections are described below The amount of extra dehumidification available is very dependent on the type of equipment in the home With...

Страница 9: ...n on high humidity thus removing a 24 vac signal to initiate dehumidification Equip ment has been designed to operate in this manner so the Thermidistat Control must now accommodate the existing equip...

Страница 10: ...TEM PERATURE button C Fifteen Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning on until preceding stage has been on for 15 minutes This timer is...

Страница 11: ...TDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 1 6 13 and 15 Fig 6 Typical Fan Coil With 2 Speed Heat Pump A97385 O W2 Y1 W2 W W1 G R E W3 THERMIDISTAT TYPICAL FAN COIL 2 SPEE...

Страница 12: ...1 2 6 13 and 15 REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 FK Series Fan Coil With 2 Speed Heat Pump A98281 O W2 W W1 Y1 W2 G R O Y1 THERMIDISTAT FK SERIES FAN COIL...

Страница 13: ...OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR Fig 14 Single Stage Furnace With 2 Speed Heat Pump Dual Fuel A97394 O W2 W W1 Y1 W2 G R THERMIDISTAT 1 STAGE FURNACE 2 SPEED HEAT PUMP W...

Страница 14: ...UTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 13 and 15 Fig 18 Two Stage Furnace With 2 Speed Heat Pump Dual Fuel A97398 O W2 W W1 Y1 W2 G R THERMIDISTAT 2 STAGE FURNACE 2...

Страница 15: ...SOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 12 13 and 15 Fig 22 Variable Speed 2 Stage Non Condensing Furnace With 2 Speed Heat Pump Dual Fuel A97437 O W2 W W1 Y1 W2 G R THERM...

Страница 16: ...NNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 and 15 DH HUM Fig 26 Variable Speed 2 Stage Condensing Furnace Without DE Connection With 2 Speed Heat Pump Dual Fuel A97421 O W2 W...

Страница 17: ...R SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 15 and 18 Fig 30 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump A98285 O W2 Y1 W2 W...

Страница 18: ...attached in all dual fuel applications 10 Refer to indoor equipment Installation Instructions for proper setup 11 To activate dehumidify feature on older style variable speed furnaces Bryant 335MAV t...

Страница 19: ...ed recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time The fixed time period is 1 5 hr It operates in both heating and cooling This o...

Страница 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Отзывы: