background image

8

One Minute Stage Change Time Delay on 286A Models

When compressor changes stages from high to low or low to high,

there is a 1--minute time delay before compressor restarts. The
outdoor fan motor remains running.

Compressor Operation on 286A Models

When the compressor operates in high stage operation, the
compressor motor rotates clockwise. Both the lower and upper

pistons are eccentric with the rotating crankshaft and both

compress refrigerant.
When the compressor operates in low stage operation, the

compressor motor reverses direction (rotates counterclockwise).
The lower piston becomes idle and the upper piston compresses

refrigerant.

The start and run windings are reversed.

Crankcase Heater Operation

The crankcase heater is energized during unit off cycle regardless
of outside air temperature (OAT) on 286A models.
The crankcase heater is energized during off cycle below 65

°

F

(18.33

°

C) on 288A models.

Outdoor Fan Motor Operation

The outdoor unit control energizes outdoor fan anytime

compressor is operating, except for defrost or low--ambient
cooling. The outdoor fan remains energized if a pressure switch or

compressor overload should open. Outdoor fan motor will

continue to operate for one minute after the compressor shuts off
when the outdoor ambient is greater than or equal to 100

°

F

(37.78

°

C). This reduces pressure differential for easier starting on

next cycle. On 286A models, the outdoor fan remains energized

during the 1--minute compressor staging time delay.
On 286A models, the outdoor fan motor is a PSC type. A fan relay
on the control board turns the fan off and on by opening and

closing a high voltage circuit to the motor. It does not change
speeds between low and high stage operation.
On 288A models, the outdoor fan is an ECM type. The motor

control is continuously powered with high voltage. The motor
speed is determined by electrical pulses provided by the PWM

outputs on the control board. The ECM motor RPM adjusts to
outdoor conditions as described in Table 3. The PWM output can

be measured between the PWM1 and PWM2 terminals on the
circuit board with a volt meter set to DC volts.
In low ambient cooling (below 55

_

F/12.78

_

C) on 286A and 288A

models, the control board cycles the fan off and on.

Table 3 – Outdoor Fan Motor PWM

Outdoor Temp (DC volts, Tol/-- 2%)

Model

Low Stage

(OAT

104

_

F / 40

_

C

)

High Stage

(OAT

104

_

F / 40

_

C

)

Low & High

Stage

(OAT

>

104

_

F / 40

_

C

)

288A024

8.72

9.35

11.9

288A036

9.06

10.23

11.9

288A048

9.91

11.04

11.9

288A060

10.83

11.7

11.9

NOTE

: For 288A models in low---ambient cooling, the PWM output for

both high--- and low---stage equals the value for low---stage opera---

tion below 55

_

F (12.8

_

C)

.

Time Delays

The unit time delays include:

S

Five minute time delay to start cooling or heating operation

when there is a call from the thermostat or user interface. To

bypass this feature, momentarily short and release Forced

Defrost pins.

S

Five minute compressor re--cycle delay on return from a

brown--out condition.

S

Two minute time delay to return to standby operation from

last valid communication (with Evolution only).

S

One minute time delay of outdoor fan at termination of

cooling mode when outdoor ambient is greater than or equal

to 100

_

F (37.78

_

C).

S

Fifteen second delay at termination of defrost before the

auxiliary heat (W1) is de--energized.

S

Twenty second delay at termination of defrost before the

outdoor fan is energized (unless fan delay defeated).

S

Thirty second compressor delay when quiet shift enabled.

S

On 286A models there is a 1 minute time delay between

staging from low to high and from high to low capacity. On

288A models there is no delay; the compressor will change

from low to high and from high to low capacity “on the fly”

to meet the demand.

Compressor Operation on 288A Models:

The basic scroll design has been modified with the addition of an

internal unloading mechanism that opens a by--pass port in the first
compression pocket, effectively reducing the displacement of the

scroll. The opening and closing of the by--pass port is controlled
by an internal electrically operated solenoid. The modulated scroll

uses a single step of unloading to go from full capacity to
approximately 67% capacity.
A single speed, high efficiency motor continues to run while the

scroll modulates between the two capacity steps. Modulation is
achieved by venting a portion of the gas in the first suction pocket

back to the low side of the compressor, thereby reducing the
effective displacement of the compressor.
Full capacity is achieved by blocking these vents, thus increasing

the displacement to 100%. A DC solenoid in the compressor
controlled by a rectified 24 volt AC signal in the external solenoid

plug moves the slider ring that covers and uncovers these vents.
The vent covers are arranged in such a manner that the compressor

operates at approximately 67% capacity when the solenoid is not

energized and 100% capacity when the solenoid is energized. The
loading and unloading of the two step scroll is done ”on the fly”

without shutting off the motor between steps.

NOTE

: 67% compressor capacity translates to approximately

75% cooling or heating capacity at the indoor coil.
The compressor will always start unloaded and stay unloaded for

five seconds even when the thermostat is calling for high stage
capacity.

286A

/288A

Содержание Evolutiont 286A

Страница 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Страница 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Страница 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Страница 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Страница 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Страница 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Страница 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Страница 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Страница 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Страница 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Страница 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Страница 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Страница 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Страница 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Страница 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Страница 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Отзывы: