background image

6

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit
control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT

PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 5 -- Line Power Connections

Connect Control Wiring

Route low voltage control wires through control wiring grommet
and connect leads to control board.
For Evolution, connect to ABCD only.

For standard

non--communicating thermostats, connect to standard thermostat

connections R, C, W, Y1, Y2, and O.

General Information

Use No. 18 AWG color--coded, insulated (35

°

C minimum) wire for

all installations.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum. The outdoor
unit requires a minimum of 27va/24vac control power.

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

Furnish power to crankcase heater a minimum of 24 hr before

starting unit. To furnish power to heater only, set thermostat to
OFF and close electrical disconnect to outdoor unit.

NOTE

: On 286A models, starting the compressor without a

minimum of 12 hours of crankcase heat prior to initial start--up
may result in a compressor chattering noise and possible damage to
the compressor.

Install Accessories

Refer to the individual instructions packaged with kits or
accessories when installing.

Make Airflow Selections

Airflow Setup for Evolution Control Furnace of FE

Fan coil (communicating)

When using an Evolution User Interface, airflow is

automatically selected based on equipment size. See User

Interface

Installation

Instructions

for

available

adjustments.

Airflow Selection for Variable Speed Furnaces for

Non--Communicating (non--Evolution) Thermostats

The variable speed furnaces provide blower operation to match the

capacities of the compressor during high and low stage cooling

operation, The furnace control board allows the installing
technician to select the proper airflows for each stage of cooling.

Below is a summary of required adjustments. See furnace
installation instructions for more details:

1. Turn SW1--5 ON for 400 CFM/ton airflow or OFF for 350

CFM/ton airflow. Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high

stage cooling operation. Select the A/C DIP switch setting

corresponding to the available airflow shown in the furnace
installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data

for HIGH speed.

3. The CF DIP switch setting determines airflow during low

stage cooling operation. Select the CF DIP switch setting
corresponding to the available airflow shown in the furnace

installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data
for LOW speed.

If a higher or lower Continuous Fan speed is desired, the
Continuous Fan speed can be changed using the fan switch on the

thermostat. Refer to the furnace installation instructions for details

of how to use this feature.

Airflow Selection for FV4 Fan Coils for Non--Commu-

nicating (Non--Evolution) Thermostats

The FV4B provides high-- and low--stage blower operation to

match the capacities of 286A compressor at high-- and low--stage.

The FV4C provides high-- and low--stage blower operation to

match the capacities of 288A compressor at high-- and low--stage

(units containing circuit board HK38EA015 or newer). To select
recommended airflow, refer to FV4 Installation Instructions. The

FV4 utilizes an Easy Select control board that allows the installing

technician to select proper airflows. For adjustments to control
board, select appropriate HP SIZE and CFM ADJUST setting. This

fan coil has an adjustable blower off delay factory set at 90 sec for
high-- and low--stage blower operation.

286A

/288A

Содержание Evolutiont 286A

Страница 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Страница 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Страница 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Страница 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Страница 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Страница 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Страница 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Страница 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Страница 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Страница 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Страница 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Страница 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Страница 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Страница 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Страница 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Страница 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Отзывы: