background image

30

SYSTEMS COMMUNICATION FAILURE
If communication with the Evolution Control is lost with the UI,

the controls will flash the appropriate fault codes. Check the
wiring to the UI, indoor and outdoor units.
MODEL PLUG
The HP/AC control board must have a valid model plug to
operate. If a valid model plug is not detected, it will not operate

and the control will flash the appropriate fault code, shown in
Table 5.
PRESSURE SWITCH PROTECTION--REFRIGERANT
The unit is equipped with high-- and low--pressure switches. If the
control senses the opening of a high-- or low--pressure switch, it

will respond as follows:

1. De--energize the compressor contactor (HPS1 & LPS) or

the compressor solenoid contactor (HPS2).

2. Keep the outdoor fan operating for 15 minutes.
3. Display the appropriate fault codes.
4. After a 15 minute delay, if there is still a call for cooling

and the LPS or HPS is reset, the compressor contactor is
energized.

5. If LPS or HPS has not closed after a 15 minute delay, the

outdoor fan is turned off. If the open switch closes anytime

after the 15--minute delay, then resume operation with a
call for cooling.

6. If LPS or HPS trips 3 consecutive cycles, the unit

operation is locked out for 4 hours.

7. In the event of a high--pressure switch trip or high pressure

lockout, check the refrigerant charge, outdoor fan
operation and outdoor coil for airflow restrictions.

8. In the event of a low--pressure switch trip or low pressure

lockout, check the refrigerant charge and indoor airflow.

CONTROL FAULT
If the HP/AC control board has failed, the control will flash the

appropriate fault code (See Table 5). The control board should

be replaced.
BROWN OUT PROTECTION
If the line voltage is less than 187v for at least 4 seconds, the
appropriate compressor contactor and fan relay are de--energized.

Compressor and fan operation are not allowed until voltage is a
minimum of 190v. The control will flash the appropriate fault

code (See Table 5).
230V LINE (POWER DISCONNECT) DETECTION
If there is no 230v at the compressor contactor when the unit is

powered and cooling demand exists, the appropriate error code is
displayed. Verify that the disconnect is closed and 230v wiring is

connected to the unit.
COMPRESSOR VOLTAGE SENSING
The control board input terminals VS and L2 (See Fig. 17) are

used to detect compressor voltage status, and alert the user of
potential problems. The control continuously monitors the high

voltage on the run capacitor of the compressor motor. Voltage

should be present any time the compressor contactor is energized,
and voltage should not be present when the contactor is

de--energized.
CONTACTOR SHORTED DETECTION
If there is compressor voltage sensed when there is no demand for
compressor operation, the contactor may be stuck closed or there

is a wiring error. The control will flash the appropriate fault code.
COMPRESSOR THERMAL CUTOUT
If the control senses the compressor voltage after start--up, and is

then absent for 10 consecutive seconds while cooling demand

exists, the thermal protector is open. The control de--energizes
the compressor contactor for 15 minutes, but continues to operate

the outdoor fan.

The control Status LED will flash the

appropriate code shown in Table 5. After 15 minutes, with a call

for low or high stage cooling, the compressor contactor is

energized. If the thermal protector has not re--set, the outdoor fan
is turned off. If the call for cooling continues, the control will

energize the compressor contactor every 15 minutes. If the
thermal protector closes (at the next 15 minute interval), check

the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code
is displayed.
NO 230V AT COMPRESSOR
If the compressor voltage is not sensed when the compressor

should be starting, the contactor may be stuck open or there is a
wiring error. The control will flash the appropriate fault code.

Check the contactor and control box wiring.
TROUBLESHOOTING UNIT FOR PROPER SWITCHING

BETWEEN LOW & HIGH STAGES
Check the suction pressures at the service valves.

Suction

pressure should be reduced by 3--10% when switching from low

to high capacity.

NOTE

: The liquid pressures are very similar between low and

high stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20--45% when switching

from low to high stage.

The compressor solenoid, when

energized in high stage, should measure 24vac.
COMPRESSOR INTERNAL RELIEF
The compressor is protected by an internal pressure relief (IPR)
which relieves discharge gas into compressor shell when

differential between suction and discharge pressures exceeds 550
-- 625 psi. The compressor is also protected by an internal

overload attached to motor windings.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As

the temperature increases, the resistance decreases. Thermistors
are used to sense outdoor ambient (OAT) and coil temperature

(OCT). Refer to Fig. 24 for resistance values versus temperature.
See Fig. 25 for OCT location.
If the outdoor ambient or coil thermistor should fail, the HP/AC

control will flash the appropriate fault code (See Table 5).

IMPORTANT

: Coil thermistor is factory mounted. Check to

insure thermistor is mounted properly. Outdoor air thermistor
(OAT) is field mounted and connected. Verify that the OAT has
been properly installed.

0

10

20

30

40

50

60

70

80

90

0

20

40

60

80

100

120

TEMPERATURE (DEG. F)

RESISTANCE (KOHMS)

THERMISTOR CURVE

A91431

Fig. 24 -- Resistance Values Versus Temperature

577D

Содержание EVOLUTION 577D

Страница 1: ...and Heating Control Operation 25 Checking and Adjusting Refrigerant Charge 25 Refrigerant Charge 25 No Charge 25 Low Charge Cooling 25 To Use Cooling Charging Charts 25 Non Communicating Emergency Cooling Heating Mode 25 MAINTENANCE 27 29 Air Filter 27 Indoor Fan and Motor 27 Inducer Blower 27 Limit Switch 27 A06047 Fig 1 Unit 577D Burner Ignition 27 Main Burners 27 Inducer Pressure Switch 27 Outd...

Страница 2: ...w NOx units designed for California installations These models meet the California maximum oxides of nitrogen NOx emissions requirements of 40 nanograms joule or less as shipped from the factory and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists NOTE Low NOx requirements apply only to natural gas installations RECE...

Страница 3: ...t CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 024 030 CPRFCURB007A00 14 356 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 036 060 CPRFCURB008A00 8 203 16 3 16 411 17 3 8 441 40 1 4 1022 41 15 16 1065 44 7 16 1129 46 1 ...

Страница 4: ...4 A06604 Fig 5 577D024 030 Unit Dimensions ...

Страница 5: ...5 A06605 Fig 6 577D036 060 Unit Dimensions ...

Страница 6: ...sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface instructions for more information Efficiency 700 700 875 875 1050 1050 1225 1225 Max 800 800 1000 1000 1200 1200 1400 1400 Furnace gas ht airflow Low Stage 475 727 475 727 745 875 745 875 Furnace gas ht airflow High Stage 844 11...

Страница 7: ...velocity of 300 ft minute for throwaway type or 450 ft minute for high capacity type Air filter pressure drop for non standard filters must not exceed 0 08 in wg Step 3 Provide Clearances The required minimum service clearances are shown in Fig 5 and 6 Adequate ventilation and outdoor air must be provided The outdoor fan draws air through the outdoor coil and discharges it through the top fan gril...

Страница 8: ...t strip screws when re securing the unit If a screw is stripped replace the stripped one with a larger diameter screw included WARNING Rigging Lifting of Unit 1 Bend top of brackets down approximately 30 degrees from the corner posts 2 Attach straps of equal length to the rigging brackets at opposite ends of the unit Be sure straps are rated to hold the weight of the unit See Fig 7 3 Attach a clev...

Страница 9: ...ow latest Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to building structure Flash weatherproof and vibration isolate duct openings in wall or roof according to good construction practices CONVERTING HORIZONTAL DISCHARG...

Страница 10: ...13 Fig 9 Condensate Trap Step 8 Install Gas Piping The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on the gas valve Install a gas supply line that runs to the heating section Refer to Table 2 and the current edition of NFGC in the U S and the current NSCNGPIC in Canada Do not use cast iron pipe It is recommende...

Страница 11: ...nector Do not use a connector which has previously serviced another gas appliance WARNING 8 Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been completed Use soap and water solution or method specified by local codes and or regulations Step 9 Install Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could res...

Страница 12: ...O HUMIDITY CONTROL COMFORT ROLLBACK ETC WILL BE LOST IF THE OAT IS NOT CONNECTED For detailed mounting instructions for the OAT sensor please refer to TSTATXXSEN01 B installation instructions catalog no 63TS TA13 Procedures 1 through 3 The OAT input is used to supply outdoor temperature data for systemlevel functionsand fortemperature displayon UserInterface UI Using two wires of the field supplie...

Страница 13: ...L BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 12 Line Power Connections A06306 Fig 13 Control Plate 577D ...

Страница 14: ...t shall be Power Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire I fother than 60 C wire is used or if length exceeds wire length in table determine size from NEC 3 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply volt age is greater than 2 Use the following formula to determ...

Страница 15: ...is correctly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hub is positioned correctly with respect to motor housing See Fig 23 d Make sure that air filter s is in place e Make sure that condensate drain trap is filled with water to ensure proper drainage f Make sure that all tools and miscellaneous loose parts have been removed 5 Compre...

Страница 16: ... alone can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Particularly at low airflow requests This is normal do not assume a fault exists 2 Recheck airflow and system static pressure using UI service screens with access panel in place NOTE Blower motor faults will not cause a lockout of blower operation The fan ...

Страница 17: ...17 6 0 A06310 Fig 16 Wiring Schematic 577D Single Phase 577D ...

Страница 18: ... system defective switch or connections or inadequate combustion air supply flame roll out switch open STATUS CODE 34 IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs If flame signal lost during blower on delay period blower will come on for the selected blower off delay Check for oxide buildup on flame sensor clean with fine steel wool proper flame sense microam...

Страница 19: ...r suction pressure will be higher than a standard single stage system or high stage operation NOTE Outdoor fan motor will continue to operate for one minute after compressor shuts off when outdoor ambient is greater than or equal to 100 F UTILITY INTERFACE WITH Evolution CONTROL The utility curtailment relay should be connected to factory supplied pigtails PINK connected to R VIOLET connected to Y...

Страница 20: ...pears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error No 230V at Compressor 74 Compressor voltage not sensed when compressor should be start ing Contactor may ...

Страница 21: ...at the ignition control will changetheinducerspeedtolow speedand keepthe gasvalve energized on low stage If the UI is asking for high stage gas heat the ignition control will maintain running the inducer on high speed and energize the gas valve s high stage relay to increase gas flow If the burner flame is not proved within 2 seconds the control will close the gas valve and repeat the ignition seq...

Страница 22: ...W PLASTIC ADJUST SCREW LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT MANIFOLD PRESSURE TAP INLET PRESSURE TAP ON OFF SWITCH REGULATOR SPRING HIGH STAGE GAS PRESSURE REGULATOR ADJUSTMENT A04167 Fig 18 Redundant Automatic Gas Control Valve NOTE DO NOT set low stage manifold pressure less than 1 4 in wc or more than 2 0 in wc for natural gas If manifold pressure is outside this range change main burner...

Страница 23: ...t one revolution takes 84 sec and the heating value of the gas is 1050 Btu ft3 Proceed as follows a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90 090 Btuh input In this example the nominal input rate for high stage is 90 000 Btu hr so the high stage manifold pressure is correctly set If the measured high stage rate is too low increase the mani...

Страница 24: ...lem in the case of a gas component failure To initiate the component test procedure ensure that there arenoUIinputstothecontrol theABCDconnectorcan beremoved from the Evolution control board for this operation and all time delays have expired Turn on setup switch SW1 6 NOTE The component test feature will not operate if the control is receiving any UI signals or until all time delays have expired ...

Страница 25: ...affect the reading Indoor air CFM must be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to determine what the liquid line temperature should be NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section NON COMMUNICATIN...

Страница 26: ...02 97 87 2578 41 39 36 30 384 108 103 98 88 2647 42 40 37 31 394 110 105 100 90 2716 44 41 38 32 404 112 107 102 92 2785 45 42 39 33 414 114 109 104 94 2854 46 43 40 34 424 116 111 106 96 2923 47 44 41 35 434 118 113 108 98 2992 48 45 42 36 444 119 114 109 99 3061 48 46 43 37 454 121 116 111 101 3130 49 47 44 38 464 123 118 113 103 3199 50 48 45 39 474 124 119 114 104 3268 51 48 46 40 484 126 121 ...

Страница 27: ...mensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes clogged with dust and lint Step 2 Indoor Fan and Motor NOTE All motors are pre lubricated Do not attempt ...

Страница 28: ...and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected malfunction has occurred check each electrical component with the proper electrical instrumentation Refer to the unit wiring label when making these checks...

Страница 29: ... performing any service that may risk exposure ofcompressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage include but are not limited to compressor replacement repairing refrigerant leaks and replacing refrigerant components such as filter drier pressure switch metering device coil accumulator or reversing valve Synthetic Roof Precautionary Proce...

Страница 30: ...emand for compressor operation the contactor may be stuck closed or there is a wiring error The control will flash the appropriate fault code COMPRESSOR THERMAL CUTOUT If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is open The control de energizes the compressor contactor for 15 minutes but...

Страница 31: ...r should fail low ambient cooling will not be allowed Defrost will occur at each time interval during heating operation but will terminate after 5 minutes If there is a thermistor out of range error defrost will occur at each time interval during heating operation but will terminate after 5 minutes Refer to the Troubleshooting Chart Table 10 for additional troubleshooting information A06311 Fig 25...

Страница 32: ...th 520 psig low side retard S Use hoses with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Only use factory specified liquid line filter driers with rated working pressures no less than 600 psig S Do not install a suction line filter drier ...

Страница 33: ... capacitor Replace Restriction in refrigerant system Locate restriction and remove Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Compressor operates continuously Low refrigerant charge Locate leak repair and recharge Co p esso ope ates co t uous y Air in system Recover refrigerant evacuate system and re char...

Страница 34: ...ight unit 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Dirty air filter Clean or replace filter as necessary Gas input to unit too low Check gas pressure at manifold match with that on unit nameplate Inadequate heating Unit undersized for application Replace with proper unit or add additional unit Inadequa...

Страница 35: ...35 577D ...

Страница 36: ..._ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB GAS HEAT SUPPLY AIR ___________ PRESSURES REFRIGERANT SUCTION ___________PSIG SUCTION LINE TEMP ___________ REFRIGERANT DISCHARGE ___________PSIG DISCHARGE TEMP ___________ VERIFY REFRIGERANT CHARGE US...

Отзывы: