ACCESSORY DESCRIPTION AND USAGE (continued)

 

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes the chance of liquid slugging. 

Usage Guideline:

Required in low ambient applications.
Required in long line applications.
Suggested in all commercial applications.

6.

 

Evaporator Freeze Thermostat

 

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7.

 

Liquid-Line Solenoid Valve (LLS)  

 

This device serves two purposes. It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor oper-
ation. It maintains a column of refrigerant liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle
refrigerant migration. 

 

Note:

 

 When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in air conditioner long line applications with a piston indoor metering device to prevent off cycle refrigerant migration. A hard shut 
off TXV can be used instead of an LLS in single flow air conditioner applications. See Long Line Application Guideline.

8.

 

MotorMaster®—Low-Ambient Controller

 

A fan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ±
10°F (37.8°C ± –12°C).

Usage Guideline:

A MotorMaster®—Low-Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications.

9.

 

Outdoor Air Temperature Sensor

 

Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Bryant thermostats listed in this publication.

10.

 

Sound Hood

 

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft to quiet areas—bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft apart.

11.

 

Support Feet

 

Four stick-on plastic feet that raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing
corrosion.

Usage Guideline:

Suggested in the following applications:

Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.

12.

 

Thermostatic Expansion Valve (TXV) 

 

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.

 

Note:

 

 When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings. 
Hard shut off TXV or LLS required in air conditioner long line applications
Required for use on all zoning systems.

13.

 

Time-Delay Relay 

 

An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.

 

Note:

 

 Most indoor unit controls include this feature. For those that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

 

A-WTD. SOUND POWER (dBA)

 

NOTE: Tested in accordance with ARI Standard 270.95. (Not listed with ARI.)

 

UNIT

SIZE-SERIES

STANDARD 

RATING

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

125

250

500

1000

2000

4000

8000

 

024-G

71

62.0

61.5

63.0

65.0

62.0

57.5

48.0

030-F

71

60.5

59.0

62.5

65.0

63.0

59.5

52.0

036-F

73

60.0

62.0

65.0

68.0

64.0

61.0

52.5

042-F

73

60.0

63.0

67.0

68.0

66.0

62.0

54.0

048-B

76

57.5

63.5

69.0

71.0

63.0

58.0

50.5

060-A

78

56.5

67.0

71.5

70.5

70.5

60.5

53.0

Содержание DELUXE 556A

Страница 1: ...rgy Efficiency Ratio with enhanced ratings of up to 15 75 SEER Sophisti cated heat transfer surfaces utilized in Bryant s 556A design allow heat to easily be transferred to the outdoor air and require...

Страница 2: ...gle phase Wide Range of Sizes Available in six sizes 2 through 5 tons Cabinet Galvanized steel is coated with powder paint to pro vide a superior long lasting appearance Totally Enclosed Fan Motor Pro...

Страница 3: ...CKOUT 3 8 IN DIA TIEDOWN KNOCKOUTS 2 PLACES IN BASEPAN 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 L C F N G A B M K E D C L DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS...

Страница 4: ...1 8 1 1 8 UNIT SIZE SERIES REQUIRED SUBCOOLING F 024 G 10 030 F 8 036 F 9 042 F 7 048 B 10 060 A 10 M A N U F A C T U R E R CERTIFIED TO ARI AS C O M P L Y I N G W I T H A RI STANDARD 210 U N I T A R...

Страница 5: ...AACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA Start Assist PTC Type KAACS0201PTC TXV Hard Shutoff KSATX0201PUR Piston Body KSAPX0101PIS Filter Drier Suction Line KH45LG140 RCD Evaporator...

Страница 6: ...ter KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA Start Assist PTC Type KAACS0201PTC TXV Hard Shutoff KSATX0301PUR Piston Body KSAPX0101PIS Filter Drier Suction Line KH45LG141 RCD Evapor...

Страница 7: ...oll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 12 00 15 00 CONDENSER COIL FAN Coil Face Area Sq Ft 18 3 24 5 Fins per In Rows Circuits 20 2 4 20 2 6 Fan...

Страница 8: ...device which gives a soft boost to the reciprocating compressor at each start up Usage Guideline Suggested in installations with marginal power supply DESCRIPTION ACCESSORY Evolution Control Deluxe 7...

Страница 9: ...ble special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Bryant thermostats listed in this publication 10 Sound Hood Wraparound sound reducing cover for the co...

Страница 10: ...0 TDR 13 50 11 95 FF1DNA030 23 400 TDR 13 50 11 75 FF1DNE024 23 000 TDR TXV 13 50 11 95 FF1DNE030 23 400 TDR TXV 13 50 11 75 FG3AAA024 22 400 NONE 13 50 11 50 FG3AAA036 23 000 NONE 13 50 11 85 FK4DNF0...

Страница 11: ...00 TDR 15 00 13 15 CK5A CK5BW036 23 600 TDR 15 00 13 35 CK5PW036 23 600 TDR TXV 15 00 13 35 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CC5A CD5AW036 23 600 TDR 15 00 13 35 CE3AA024 22 800 TDR 14 50...

Страница 12: ...6 23 600 TDR TXV 15 00 13 30 CK5PW024 22 800 TDR TXV 14 50 12 95 CK5PW030 23 000 TDR TXV 14 50 13 10 CK5PW036 23 600 TDR TXV 15 00 13 30 COILS 355MAV060100 VARIABLE SPEED FURNACE CC5A CD5AA036 23 600...

Страница 13: ...TDR TXV 15 50 12 60 FK4DNF005 30 000 TDR TXV 15 75 14 00 FV4ANF002 29 600 TDR TXV 15 20 13 15 FV4ANF003 29 800 TDR TXV 15 60 13 60 FV4ANF005 30 000 TDR TXV 15 75 14 00 FV4BNF002 29 600 TDR TXV 15 20 1...

Страница 14: ...E3AA030 29 000 TDR 15 00 13 25 CE3AA036 29 600 TDR 15 00 13 45 CK5A CK5BW036 29 600 TDR 15 00 13 70 CK5PW036 29 600 TDR TXV 15 00 13 70 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CC5A CD5AW036 29 6...

Страница 15: ...5 000 NONE 13 70 11 95 CK3BA042 35 600 NONE 13 70 11 95 CK3BA048 36 000 NONE 14 00 12 05 CK5A CK5BA036 35 000 NONE 13 70 11 95 CK5A CK5BA042 35 600 NONE 13 70 11 95 CK5A CK5BA048 36 000 NONE 14 00 12...

Страница 16: ...000 TDR TXV 15 00 13 15 CK5PW036 35 000 TDR TXV 14 50 12 95 COILS 315 A J AV060110 VARIABLE SPEED FURNACE CC5A CD5AA036 35 000 TDR 14 50 12 60 CC5A CD5AA042 35 600 TDR 15 00 12 95 CC5A CD5AC048 36 00...

Страница 17: ...TDR 14 50 12 65 CC5A CD5AW048 36 000 TDR 14 50 12 75 CK5A CK5BA042 35 600 TDR 14 50 12 80 CK5A CK5BW036 35 000 TDR 14 50 12 70 CK5A CK5BW048 36 000 TDR 15 00 12 90 CK5PA042 35 600 TDR TXV 14 50 12 80...

Страница 18: ...41 000 NONE 13 50 11 75 CK5A CK5BX060 42 000 NONE 13 70 12 10 CK5PA042 40 000 TXV 13 30 11 70 CK5PA048 41 000 TXV 13 50 11 75 CK5PE042 40 500 TXV 13 50 11 75 CK5PT042 40 000 TXV 13 30 11 70 CK5PT048...

Страница 19: ...LE SPEED FURNACE CC5A CD5AA042 40 000 TDR 14 50 12 65 CC5A CD5AA060 41 500 TDR 14 50 12 85 CC5A CD5AC048 40 000 TDR 14 50 12 70 CC5A CD5AW042 40 000 TDR 14 50 12 55 CC5A CD5AW048 41 000 TDR 14 50 12 8...

Страница 20: ...R 14 00 12 25 CC5A CD5AC048 40 500 TDR 14 00 12 05 CC5A CD5AW060 42 000 TDR 14 50 12 60 CD5AA048 41 000 TDR 14 00 12 25 CK3BA042 40 000 TDR 14 00 12 20 CK3BA048 41 000 TDR 14 00 12 35 CK3BA060 41 500...

Страница 21: ...500 TDR TXV 13 50 11 90 FX4BNF048 47 000 TDR TXV 13 50 11 90 COILS 315 A J AV048090 VARIABLE SPEED FURNACE CC5A CD5AC048 45 500 TDR 13 50 11 80 CD5AA048 46 000 TDR 14 00 12 00 CE3AA048 46 500 TDR 14 0...

Страница 22: ...048 46 000 TDR 14 00 11 95 CD5PX060 47 500 TDR TXV 14 50 12 40 CE3AA048 46 500 TDR 14 00 12 00 CE3AA060 47 000 TDR 14 00 12 35 CK3BA048 46 500 TDR 14 00 12 05 CK3BA060 47 000 TDR 14 00 12 35 CK5A CK5B...

Страница 23: ...000 TDR TXV 15 00 12 80 FX4BNB060 58 500 TDR TXV 14 00 12 00 COILS 315 A J AV060110 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 13 50 11 45 CD5PX060 58 000 TDR TXV 14 00 11 90 CE3AA060 58 000 TDR...

Страница 24: ...19 25 17 72 2 83 72 29 77 16 61 1 59 28 25 16 06 1 80 26 65 15 48 2 04 24 95 14 87 2 29 23 10 14 22 2 56 21 05 13 51 2 84 Multipliers for Determining the Performance With Other Indoor Sections Indoor...

Страница 25: ...61 1 59 28 25 16 06 1 80 26 65 15 48 2 04 24 95 14 87 2 29 23 10 14 22 2 56 21 05 13 51 2 84 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Страница 26: ...6 2 54 19 25 17 72 2 83 72 29 77 16 61 1 59 28 25 16 06 1 80 26 65 15 48 2 04 24 95 14 87 2 29 23 10 14 22 2 56 21 05 13 51 2 84 Multipliers for Determining the Performance With Other Indoor Sections...

Страница 27: ...9 28 8 28 8 2 52 27 5 27 5 2 79 25 9 25 9 3 08 24 0 24 0 3 39 57 31 6 31 6 2 08 30 3 30 3 2 29 28 9 28 9 2 53 27 4 27 4 2 79 25 7 25 7 3 07 24 1 24 1 3 39 Multipliers for Determining the Performance W...

Страница 28: ...39 57 31 6 31 6 2 08 30 3 30 3 2 29 28 9 28 9 2 53 27 4 27 4 2 79 25 7 25 7 3 07 24 1 24 1 3 39 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indo...

Страница 29: ...8 3 34 62 31 0 29 5 2 03 29 8 28 8 2 24 28 3 28 0 2 48 26 8 26 8 2 74 25 2 25 2 3 03 23 5 23 5 3 34 57 30 7 30 7 2 03 29 4 29 4 2 24 28 1 28 1 2 47 26 6 26 6 2 74 25 0 25 0 3 02 23 5 23 5 3 34 1125 7...

Страница 30: ...7 37 7 37 7 2 48 36 1 36 1 2 74 34 4 34 4 3 04 32 5 32 5 3 36 30 4 30 4 3 71 28 0 28 0 4 08 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Se...

Страница 31: ...34 3 34 3 3 04 32 4 32 4 3 36 30 3 30 3 3 70 27 9 27 9 4 07 57 37 7 37 7 2 48 36 1 36 1 2 74 34 4 34 4 3 04 32 5 32 5 3 36 30 4 30 4 3 71 28 0 28 0 4 08 Multipliers for Determining the Performance Wit...

Страница 32: ...4 32 4 3 36 30 3 30 3 3 70 27 9 27 9 4 07 57 37 7 37 7 2 48 36 1 36 1 2 74 34 4 34 4 3 04 32 5 32 5 3 36 30 4 30 4 3 71 28 0 28 0 4 08 Multipliers for Determining the Performance With Other Indoor Se...

Страница 33: ...33 6 33 6 4 80 57 44 6 44 6 2 90 42 6 42 6 3 21 40 6 40 6 3 55 38 4 38 4 3 93 36 0 36 0 4 34 33 7 33 7 4 80 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size C...

Страница 34: ...4 4 78 62 44 6 44 0 2 90 42 5 42 5 3 21 40 5 40 5 3 55 38 3 38 3 3 92 35 9 35 9 4 34 33 6 33 6 4 80 57 44 6 44 6 2 90 42 6 42 6 3 21 40 6 40 6 3 55 38 4 38 4 3 93 36 0 36 0 4 34 33 7 33 7 4 80 Multipl...

Страница 35: ...62 44 6 44 0 2 90 42 5 42 5 3 21 40 5 40 5 3 55 38 3 38 3 3 92 35 9 35 9 4 34 33 6 33 6 4 80 57 44 6 44 6 2 90 42 6 42 6 3 21 40 6 40 6 3 55 38 4 38 4 3 93 36 0 36 0 4 34 33 7 33 7 4 80 Multipliers fo...

Страница 36: ...2 41 83 26 78 5 60 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 97 1 00...

Страница 37: ...3 26 30 81 4 25 49 82 29 58 4 66 46 09 28 26 5 12 41 83 26 78 5 60 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capaci...

Страница 38: ...7 26 4 51 58 78 45 79 5 01 54 81 44 20 5 56 50 40 42 45 6 14 45 36 40 50 6 71 72 71 99 39 04 4 06 68 32 37 68 4 52 64 29 36 20 5 03 59 87 34 59 5 58 54 92 32 82 6 17 49 26 30 83 6 75 2250 57 61 66 61...

Страница 39: ...27 0 2 64 18 8 136 0 2 96 40 TCG SDT KW 32 9 69 8 1 29 31 2 79 4 1 46 29 5 89 1 1 65 27 8 98 7 1 86 26 0 108 0 2 09 24 3 118 0 2 36 22 5 127 0 2 65 20 6 137 0 2 97 45 TCG SDT KW 36 0 71 1 1 30 34 1 80...

Страница 40: ...1 10 38 40 35 60 32 60 29 30 74 30 83 40 92 60 101 70 110 90 120 00 128 90 137 90 2 36 2 67 3 02 3 41 3 84 4 32 4 84 5 41 40 TCG SDT KW 54 00 51 10 48 10 45 20 42 10 39 00 35 70 32 10 76 00 85 10 94 1...

Страница 41: ...see Accessory Usage Guideline in this literature 6 For vapor line sizing and capacity losses for interconnecting refrigerant tubing lengths greater than 50 ft consult the Application Guideline and Se...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...z The unit will be capable of satisfactory opera tion within voltage limits of _____ v to _____ v Unit electrical power will be single point connection Control circuit will be 24v Special Features Ref...

Отзывы: