CNPHP

Installation Instructions

Cased N Coils

Horizontal

Heating --- Cooling

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Right and Left with Pan Extension

2

. . . . . . . . .

Furnace Attachment

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Attic

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Horizontal Crawl Space

4

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Lines

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connect Refrigerant Liquid and Suction Lines

4

. . . . . . . . .

Condensate Drain Line Connection

5

. . . . . . . . . . . . . . . . . .

Waste Line Connection

6

. . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock or other conditions

which may cause death, personal injury or property damage.
Consult a qualified installer, service agency, or your distributor or

branch for information or assistance. The qualified installer or

agency must use factory--authorized kits or accessories when
modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing

and work gloves. Use quenching cloths for brazing operations.

Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to the unit.

Consult local building codes and the current editions of the
National Electrical Codes (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical

Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal words

DANGER

,

WARNING

and

CAUTION

. These words are used with the safety--alert symbol.

DANGER

identifies the most serious hazards which

will

result in

severe personal injury or death.

WARNING

signifies hazards

which

could

result in personal injury or death.

CAUTION

is used

to identify unsafe practices, which

may

result in minor personal

injury or product and property damage.

NOTE

is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

NOTE

: Nitrogen can leak out through the needle pierce hole in

the plugs. This does not indicate a leaking coil nor warrant return
of the coil.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying or servicing system, always turn

off main power to system. There may be more than one

disconnect switch. Lock out and tag switch with a suitable

warning label.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
This coil contains Nitrogen precharge of 15 PSIG. Release of

this pressure through the center of the rubber plugs is required

before removing the plugs.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
Take precautions to ensure Aluminum tubes do not come in

direct contact or allow for condensate run off with a dissimilar

metal. Dissimilar metals can cause galvanic corrosion and

possible premature failure.

CAUTION

!

INTRODUCTION

The CNPHP is a horizontal, multi--use furnace coil (see Fig. 1).
With the use of field--supplied transition duct, these furnace coils

can also be applied to other similar horizontal furnaces on the

market. The CNPHP is available in sizes 024 through 060. All
models are equipped with a factory--installed TXV and are used

with Puron

refrigerant (R--410A) systems.

Содержание CNPHP

Страница 1: ...t serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation NOTE Nitrogen can leak out throu...

Страница 2: ...ory installed hard shutoff TXV designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE All TXV S have preset superheat settings and are not field adjustable Cabinet Sweating If this unit is installed in a garage attic or other unconditioned space special attention needs to be given to the potential of cabinet sweating A 6 in 152 mm wide piece of insulatio...

Страница 3: ...plication E Application J Coil Ductwork Airflow Furnace Coil Furnace Ductwork Airflow A13416 Fig 4 Horizontal Installation Applications Table 1 Heat Pump Applications Furnace Width In mm Coil Width In mm 14 356 17 5 445 21 533 24 5 622 14 356 A B C D E D E 17 5 445 A B C D E D E 21 533 A B C D E 24 5 622 A Not permitted Table 2 Air Conditioner Applications Furnace Width In mm Coil Width In mm 14 3...

Страница 4: ... work platform using material in platform that will support the weight of an installer or a service person 2 Place work platform in front of discharge end of furnace 3 Secure platform to building joists Install coil To suspend CNPHP 1 Cut metal plumbers strap to desired lengths 2 Attach metal plumbers strap to four corners of coil casing see Fig 7 3 Use a minimum of two screws per corner to attach...

Страница 5: ...hten Finger tighten plus 1 1 2 turns Be sure to install plastic plug in unused condensate drain fitting Two 3 4 in female threaded pipe connections are provided in each coil condensate pan A trap is not necessary on the condensate line Consult local codes for additional restrictions or precautions If local codes require a trap then the following guidelines are suggested to assure proper drainage I...

Страница 6: ...ARD Failure to follow this warning could result in personal injury or death Provide trap with air gap in drain line when connecting to waste sewer line WARNING Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 01 ...

Отзывы: