9
ELECTRICAL DATA
UNIT
SIZE---
VOLTAGE,
SERIES
V/PH
OPER
VOLTS*
COMPR
FAN
MCA
MIN WIRE
SIZE
{
MIN WIRE
SIZE
{
MAX
LENGTH
ft. (m)
}
MAX
LENGTH
ft. (m)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
018---D
208/230/1
253
197
48.0
9.0
0.5
11.8
14
14
66 (20.1)
63 (21.0)
15
024---D
58.3
13.5
0.77
17.6
14
14
44 (13.4)
42 (12.8)
25
030---E
64.0
12.8
0.77
16.8
14
14
46 (14.0)
44 (13.4)
25
036---E
77.0
14.1
1.4
20.5
12
12
61 (18.6)
58 (17.7)
30
042---C
112.0
17.9
1.1
23.5
12
12
53 (16.2)
51 (15.5)
40
048---E
109.0
19.9
1.4
26.2
10
10
76 (23.2)
72 (22.2)
40
060---G
134.0
26.4
1.2
34.2
8
10
62 (18.9)
55 (16.8)
50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
_
C , consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade
name ROMEX, shall be that of 60
_
C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75
_
C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
}
Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER (dBA)
UNIT SIZE---
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
018---D
72
53.5
59.5
63.5
67.0
63.5
59.0
52.5
024---D
76
55.0
61.5
67.0
71.5
69.0
61.0
55.0
030---E
74
55.0
63.5
68.5
68.5
65.5
61.0
54.0
036---E
75
59.5
63.0
68.5
70.0
65.5
61.5
53.5
042---C
78
57.5
65.0
71.0
73.0
70.5
67.5
62.5
048---E
80
58.5
67.5
73.5
75.0
70.5
67.5
64.5
060---G
78
59.0
67.5
71.5
73.5
69.0
66.0
63.5
NOTE
: Tested in accordance with ARI Standard 270---2008 (not listed in AHRI).
A--WEIGHTED SOUND POWER WITH SOUND BLANKET (dBA)
UNIT SIZE---
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
018---D
71
55.5
60.5
64.0
66.0
63.0
58.5
52.0
024---D
74
55.5
60.5
68.5
70.0
67.0
61.0
53.6
030---E
73
55.5
64.0
68.0
67.0
64.0
60.0
52.5
036---E
74
59.5
63.0
68.0
69.5
65.0
60.5
50.5
042---C
77
57.5
65.0
70.5
72.0
70.0
67.0
62.0
048---E
79
60.5
67.5
73.5
74.5
71.0
68.0
63.5
060---G
78
59.0
68.0
70.5
72.5
68.0
67.0
63.0
NOTE
: Tested in accordance with ARI Standard 270---2008 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
018---D
10 (5.6)
024---D
10 (5.6)
030---E
10 (5.6)
036---E
14 (7.8)
042---C
10 (5.6)
048---E
15 (8.3)
060---G
13 (7.2)
113A