GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system air conditioner unit

suitable for ground or rooftop installation. Unit consists of a

hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply air

upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil

unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition

of AHRI Standard 210.

— Unit will be certified for capacity and efficiency, and

listed in the latest AHRI directory.

— Unit construction will comply with latest edition of

ANSI/ ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval. Unit
will have c--UL--us approval.

— Unit cabinet will be capable of withstanding Federal

Test Method Standard No. 141 (Method 6061) 500--hr

salt spray test.

— Air--cooled condenser coils will be leak tested at 150

psig and pressure tested at 450 psig.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is

stored

and

handled

per

unit

manufacturer’s

recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air--cooled air conditioner unit.

Contained within the unit enclosure is all factory wiring, piping,

controls, compressor, refrigerant charge Puron

r

(R--410A), and

special features required prior to field start--up.
Unit Cabinet

— Unit cabinet will be constructed of galvanized steel,

bonderized, and coated with a powder coat paint.

AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER

113A

1--1/2 TO 5 NOMINAL TONS

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated

bearings. Shafts will be corrosion resistant.

— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated

steel wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,
dehydrated, and sealed.

Refrigeration Components

— Refrigeration

circuit

components

will

include

liquid--line shutoff valve with sweat connections,

vapor--line shutoff valve with sweat connections,
system charge of Puron

r

(R--410A) refrigerant, and

compressor oil.

— Unit will be equipped with high--pressure switch, low

pressure switch and filter drier for Puron refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____

Btuh at a suction temperature of _____

_

F/

_

C. The

power consumption at full load will not exceed _____

kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____

_

F/

_

C wet

bulb and _____

_

F/

_

C dry bulb, and air entering the

unit at _____

_

F/

_

C.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v
to _____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available
enhancements.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

E

2009 Bryant Heating & Cooling Systems

D

7310 W. Morris St.

D

Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 03/09

Replaces: PDS113A--- 06

Catalog No. PDS113A---07

113A

Содержание AIR CONDITIONER WITH PURON 113A

Страница 1: ...most up to date ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 13 14 SEER 10 55 12 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sou...

Страница 2: ...owever proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency Installation of this product should follow all manufacturing refrigerant charging and air flo...

Страница 3: ...18 2218 2954 3167 3365 3129 Motor HP 1 12 1 10 1 10 1 4 1 5 1 4 1 4 Motor RPM 1100 1100 1100 1100 1100 1100 800 COND COIL Face Area Sq ft 8 4 8 4 9 80 13 13 17 25 19 40 12 93 Fins per In 20 25 25 25 2...

Страница 4: ...250 250 250 250 250 230 160 60000 AC with Puron 3 8 3 8 250 250 250 225 190 150 110 Maximum actual length not to exceed 200 ft 61 m Total equivalent length accounts for losses due to elbows or fitting...

Страница 5: ...On Same Level Outdoor Below Indoor Outdoor Above Indoor 1 4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 53 3 5 16 120 36 6 50 15 2 120 36 6 3 8 80 24...

Страница 6: ...LAY X X X X X X X KSALA0301410 LOW AMBIENT PSW X X X X X X X KSALA0601AAA MOTORMASTER 230V X X X X X X X HC32GE234 MOTOR FAN BALL BEARING X HC34GE239 MOTOR FAN BALL BEARING X X HC40GE226 MOTOR FAN BAL...

Страница 7: ...es the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Cycle Protector The cycle pr...

Страница 8: ...he superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter tubes and external equalizer tube Hard shut off types are available NOTE When using a hard shut off TXV with singl...

Страница 9: ...t is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies with 2007 requir...

Страница 10: ...217 32 3 8 X 35 1 2 X 35 15 16 113A048 E X O O O 31 3 16 35 3 4 3 7 8 7 8 6 9 16 24 11 16 9 1 8 2 15 16 5 8 16 3 8 15 3 8 15 1 4 186 224 32 3 8 X 35 1 2 X 39 3 8 113A060 F G X O O O 31 3 16 25 1 2 3 7...

Страница 11: ...12 8 113A048 E X O O O 792 2 908 0 98 4 22 2 166 7 627 1 231 8 74 6 15 9 415 9 390 5 387 4 84 4 101 6 822 3 X 901 7 X 1000 1 113A060 F G X O O O 792 2 647 7 98 4 22 2 166 7 627 1 231 8 74 6 15 9 358 8...

Страница 12: ...7 2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well o...

Страница 13: ...A W 018 D CSPH 2412A 353AAV036060 18000 12 20 15 00 3250638 113AN A W 018 D CSPH 2412A 355 A C AV042060 17900 12 20 14 50 3250639 113AN A W 018 D CSPH 2412A 355 A C AV042080 17900 12 20 14 50 3250637...

Страница 14: ...3AN A W 024 D CNPV 3017A 353AAV036060 23800 12 20 14 50 3251108 113AN A W 024 D CNPV 3017A 353AAV036080 23600 12 20 14 50 3251104 113AN A W 024 D CNPV 3017A 355 A C AV042060 23400 12 20 14 50 3251103...

Страница 15: ...4 00 3251259 113AN A W 030 E CNPH 3017A 315 A J AV066155 27400 12 00 14 00 3251262 113AN A W 030 E CNPH 3017A 353AAV036040 27600 12 00 14 00 3251263 113AN A W 030 E CNPH 3017A 353AAV036060 27800 11 70...

Страница 16: ...14 00 3251310 113AN A W 030 E CSPH 3612A 315 A J AV036070 27800 12 00 14 00 3251311 113AN A W 030 E CSPH 3612A 315 A J AV048090 27800 12 00 14 50 3251312 113AN A W 030 E CSPH 3612A 315 A J AV060110 27...

Страница 17: ...070 33600 11 20 13 50 3251061 113AN A W 036 E CNPH 4221A 313 AV048090 34000 12 00 14 00 3251062 113AN A W 036 E CNPH 4221A 313 AV060110 34000 12 00 14 00 3251002 113AN A W 036 E CNPH 4221A 315 A J AV0...

Страница 18: ...A 355AAV042040 33600 11 50 13 50 3251008 113AN A W 036 E CSPH 3612A TDR 33800 11 00 13 00 3251066 113AN A W 036 E CSPH 4212A 313 AV048070 34400 11 70 14 00 3251067 113AN A W 036 E CSPH 4212A 313 AV048...

Страница 19: ...090 41000 12 00 14 00 3250672 113AN A W 042 C CNPH 4821A 313 AV060110 41000 12 00 14 00 3250673 113AN A W 042 C CNPH 4821A 313 AV060135 41000 12 00 14 00 3250752 113AN A W 042 C CNPH 4821A 315 A J AV0...

Страница 20: ...000 11 20 13 50 3250779 113AN A W 048 E CAP 4824A 313 AV060135 45500 11 70 13 50 3250777 113AN A W 048 E CAP 4824A 315 A J AV066135 45000 11 70 14 00 3250778 113AN A W 048 E CAP 4824A 315 A J AV066155...

Страница 21: ...76 113AN A W 048 E CSPH 4812A 353AAV060120 45000 11 70 14 00 3250831 113AN A W 048 E CSPH 4812A 355 A C AV060080 44500 11 50 13 50 3250832 113AN A W 048 E CSPH 4812A 355 A C AV060100 45000 11 20 13 50...

Страница 22: ...13AN A W 060 G FX4CN B F 060 57500 11 20 13 20 Tested combination EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio TDR Time Delay Relay UI User Interface NOTES 1 In most cases only 1...

Страница 23: ...03 14 58 12 56 2 25 63 17 2 18 41 14 06 1 32 17 55 13 70 1 48 16 63 13 31 1 64 15 67 12 92 1 83 14 64 12 49 2 03 13 54 12 03 2 26 62 16 7 18 28 18 11 1 32 17 55 17 55 1 48 16 79 16 79 1 64 15 99 15 99...

Страница 24: ...6070 CSPH 3012A 1 00 0 92 315 A J AV036070 CAP 2417A 1 00 0 90 315 A J AV048090 CAP 3017A 1 01 0 91 315 A J AV048090 CNPH 2417A 0 99 0 91 315 A J AV048090 CNPH 3017A 1 01 0 91 315 A J AV048090 CNPV 24...

Страница 25: ...090 CAP 3617A 1 00 0 90 315 A J AV048090 CNPH 3017A 1 00 0 92 315 A J AV048090 CNPH 3617A 1 00 0 92 315 A J AV048090 CNPV 3017A 1 00 0 92 315 A J AV048090 CNPV 3617A 1 00 0 92 315 A J AV048090 CNPV 42...

Страница 26: ...17A 1 01 0 93 313 AV048070 CNPH 3017A 1 00 0 94 313 AV048070 CNPH 3617A 1 00 0 94 313 AV048070 CNPV 3017A 1 00 0 94 313 AV048070 CNPV 3617A 1 00 0 94 313 AV048070 CSPH 3012A 1 01 0 95 313 AV048070 CSP...

Страница 27: ...9 0 93 315 A J AV036070 CAP 3617A 0 99 0 92 315 A J AV048090 CNPH 3617A 0 98 0 93 315 A J AV048090 CNPH 4221A 0 99 0 93 315 A J AV048090 CNPH 4821A 1 01 0 90 315 A J AV048090 CNPV 3617A 0 98 0 93 315...

Страница 28: ...355AAV042040 CNPH 3617A 0 98 0 93 355AAV042040 CNPH 4221A 0 99 0 94 355AAV042040 CSPH 3612A 0 99 0 94 355AAV042040 CSPH 4212A 0 99 0 93 355AAV042040 CAP 3617A 0 99 0 96 313 AV048070 CAP 4817A 1 02 0...

Страница 29: ...A 1 00 0 96 315 A J AV060110 CNPV 4221A 0 99 0 94 315 A J AV060110 CNPV 4821A 1 00 0 96 315 A J AV060110 CAP 4224A 0 99 0 94 315 A J AV066135 CAP 4824A 1 00 0 94 315 A J AV066135 CNPV 4824A 1 00 0 94...

Страница 30: ...CNPH 6024A 1 00 0 92 315 A J AV060110 CNPV 4821A 0 98 0 92 315 A J AV060110 CSPH 4812A 0 98 0 92 315 A J AV060110 CSPH 6012A 1 00 0 92 315 A J AV060110 CAP 4824A 0 98 0 92 315 A J AV066135 CAP 6024A...

Страница 31: ...7 13 9 60 47 60 47 4 45 58 19 58 19 4 90 55 73 55 73 5 40 53 10 53 10 5 94 50 23 50 23 6 54 47 00 47 00 7 18 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CAP 6024A 1 00 1 00 CAP 6021A 0 98 0 98 C...

Страница 32: ...5 12 78 TCG 32 60 30 80 29 10 27 30 25 60 23 90 22 10 20 20 SDT 80 30 89 20 98 20 107 10 116 10 125 20 134 20 143 10 KW 1 09 1 25 1 41 1 60 1 81 2 03 2 28 2 55 113AN A W 030 E 30 1 11 TCG 25 40 24 00...

Страница 33: ...122 60 131 80 141 00 KW 2 24 2 51 2 82 3 15 3 53 3 93 4 38 4 85 45 7 22 TCG 54 30 51 60 48 80 46 00 43 10 40 10 36 90 33 60 SDT 78 50 87 50 96 60 105 70 114 70 123 80 132 90 142 00 KW 2 27 2 54 2 85 3...

Страница 34: ...manently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Comp...

Отзывы: