800SA/801SA: Installation, Start–Up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

12

Table 4 – Air Delivery - CFM (With Filter)*

Furnace

Wire Lead 

Color

Function

Test Airflow Delivery @ Various External Static Pressures

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

36045E14

Gray

Cooling. Do not use for heating.

1230

1190

1155

1120

1080

1045

1010

975

935

895

Yellow

Alt Cooling or alt Heating

980

945

920

890

855

815

770

735

690

645

Orange

Alt Cooling or alt Heating

770

720

685

640

600

560

520

475

430

385

Blue

Heating or alt Cooling

710

660

620

580

540

490

455

415

375

335

Red

Alt Cooling. Do not use for heating.

600

540

500

455

415

385

345

305

235

-

36045E17

Gray

Cooling. Do not use for heating.

1370

1335

1295

1255

1215

1175

1135

1095

1055

1020

Yellow

Alt Cooling or alt Heating

1130

1085

1040

995

955

910

865

825

780

730

Orange

Alt Cooling or alt Heating

930

885

835

795

745

700

655

600

545

495

Blue

Heating or alt Cooling

760

720

670

625

580

515

460

410

355

300

Red

Alt Cooling. Do not use for heating.

610

500

445

375

320

260

200

135

-

-

36070E14

Gray

Cooling. Do not use for heating.

1205

1170

1143

1105

1070

1035

1000

960

925

885

Blue

Heating or alt Cooling

1095

1060

1030

995

960

925

885

840

800

735

Yellow

Alt Cooling or alt Heating

920

880

845

805

765

730

685

620

560

510

Orange

Alt Cooling. Do not use for heating.

715

650

610

575

520

465

410

380

305

245

Red

Alt Cooling. Do not use for heating.

635

490

445

375

315

270

205

230

190

140

36070E17

Gray

Cooling. Do not use for heating.

1185

1140

1095

1055

1005

960

915

865

820

780

Yellow

Alt Cooling or alt Heating

1000

940

895

850

800

750

695

650

600

555

Blue

Heating or alt Cooling

990

935

895

845

790

740

690

640

590

535

Orange

Alt Cooling or alt Heating

855

775

720

660

605

560

495

435

385

335

Red

Alt Cooling. Do not use for heating.

860

685

515

445

385

340

275

205

-

-

48070E17

Gray

Cooling. Do not use for heating.

1650

1615

1580

1545

1515

1480

1445

1415

1380

1350

Yellow

Alt Cooling. Do not use for heating

1405

1365

1325

1285

1250

1215

1175

1140

1100

1065

Orange

Alt Cooling or alt Heating

1255

1215

1175

1130

1090

1090

1010

970

930

895

Blue

Heating or alt Cooling

1185

1140

1095

1050

1005

1005

920

880

840

800

Red

Alt Cooling. Do not use for heating.

1100

1050

1005

960

915

915

825

785

740

700

48070E21

Gray

Cooling. Do not use for heating.

1735

1685

1640

1595

1545

1495

1450

1405

1360

1310

Yellow

Alt Cooling or alt Heating

1480

1435

1395

1340

1290

1240

1190

1135

1085

1030

Blue

Heating or alt Cooling

1315

1275

1225

1180

1135

1085

1030

975

915

860

Orange

Alt Cooling or alt Heating

1135

1080

1030

985

935

885

835

770

705

645

Red

Alt Cooling. Do not use for heating.

980

930

875

820

775

715

665

595

530

455

42090E17

Gray

Cooling. Do not use for heating.

1355

1320

1285

1245

1210

1165

1125

1080

1025

815

Yellow

Alt Cooling or alt Heating

1295

1255

1220

1185

1140

1100

1055

1005

955

815

Blue

Heating or alt Cooling

1220

1185

1150

1105

1065

1025

975

915

840

740

Orange

Alt Cooling or alt Heating

1030

985

940

900

845

790

715

655

590

535

Red

Alt Cooling. Do not use for heating.

945

905

855

800

750

670

600

540

490

435

48090E21

Gray

Cooling. Do not use for heating.

1625

1580

1535

1490

1445

1395

1340

1260

1135

995

Yellow

Alt Cooling or alt Heating

1425

1380

1335

1290

1235

1185

1125

1075

1020

640

Blue

Heating or alt Cooling

1440

1395

1350

1305

1255

1200

1145

1090

1040

950

Orange

Alt Cooling or alt Heating

1260

1210

1160

1105

1050

990

935

880

820

755

Red

Alt Cooling. Do not use for heating.

1095

1040

980

905

845

780

720

650

585

520

60090E21

Gray

Cooling. Do not use for heating.

2180

2130

2080

2030

1980

1925

1870

1805

1745

1680

Yellow

Alt Cooling or alt Heating

1900

1845

1795

1740

1685

1635

1570

1500

1435

1375

Blue

Heating or alt Cooling

1685

1620

1565

1505

1455

1385

1320

1260

1200

1140

Orange

Alt Cooling or alt Heating

1390

1315

1240

1175

1095

1030

970

900

825

760

Red

Alt Cooling. Do not use for heating.

1240

1155

1075

990

915

835

765

690

615

555

60090E24

Gray

Cooling. Do not use for heating.

2190

2135

2075

2015

1960

1900

1835

1775

1705

1630

Yellow

Alt Cooling or alt Heating

1870

1810

1745

1685

1625

1565

1495

1420

1345

1280

Blue

Heating or alt Cooling

1580

1510

1445

1385

1320

1240

1175

1115

1050

970

Orange

Alt Cooling or alt Heating

1305

1220

1160

1075

1000

930

865

770

690

610

Red

Alt Cooling. Do not use for heating.

1210

1075

1000

915

845

765

675

595

515

425

60110E21

Gray

Cooling. Do not use for heating.

2255

2205

2150

2100

2040

1985

1920

1835

1735

1615

Blue

Heating or alt Cooling

1945

1890

1830

1770

1715

1655

1600

1545

1480

1430

Yellow

Alt Cooling or alt Heating

1600

1525

1465

1400

1335

1275

1210

1150

1080

1015

Orange

Alt Cooling. Do not use for heating.

1420

1340

1280

1200

1140

1065

1005

925

865

790

Red

Alt Cooling. Do not use for heating.

1280

1205

1140

1055

990

910

840

760

695

630

Содержание 800SA

Страница 1: ...r Hour 21 EXTERIOR MASONRY CHIMNEY FAN NAT INSTALLATIONS WITH TYPE B DOUBLE WALL VENT CONNECTORS NFPA AGA 22 VENTING NOTES FOR Fig 31 Fig 43 25 START UP ADJUSTMENT AND SAFETY CHECK 25 GENERAL 25 Table...

Страница 2: ...residential garage must be installed as specified in the warning box in the Location section 9 The furnace may be used for construction heat provided that the furnace installation and operation compli...

Страница 3: ...tion in a Garage CODES AND STANDARDS Follow all national and local codes and standards in addition to these instructions The installation must comply with regulations of the serving gas supplier local...

Страница 4: ...tic discharge can affect electronic components Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control...

Страница 5: ...a volume of at least 50 cubic feet per 1 000 Btuh input rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 Btuh require the OUTDOOR COMBUSTION AIR MET...

Страница 6: ...ns from the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 1 For other than fan assisted appliances such as a draft hood equipped water heater A04002 1 SQ IN PER 4000 BTUH DUCTS TO OUTD...

Страница 7: ...and dilution of flue gases However in buildings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section 4 Unusually...

Страница 8: ...Table 3 and Fig 9 3 Construct plenum to dimensions specified see Table 3 and Fig 9 4 If downflow subbase KGASB is used install as shown see Table 10 If Coil Assembly Part No CNPV CNRV CAP and CNR or...

Страница 9: ...red 11 13 16 284 19 483 13 7 16 341 20 5 8 600 Downflow Applications on Combustible Flooring with Cased Coil subbase not required 12 5 16 319 19 483 13 5 16 338 20 508 17 1 2 445 Upflow Applications o...

Страница 10: ...revent screws from pulling out use 2 8 x 3 4 in 19 mm screws into the side and 2 8 x 3 4 in 19 mm screws in the bottom of the furnace casing for each strap see Fig 14 and Fig 15 If the screws are atta...

Страница 11: ...0 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the latest edit...

Страница 12: ...915 915 825 785 740 700 48070E21 Gray Cooling Do not use for heating 1735 1685 1640 1595 1545 1495 1450 1405 1360 1310 Yellow Alt Cooling or alt Heating 1480 1435 1395 1340 1290 1240 1190 1135 1085 10...

Страница 13: ...side inlets a combination of 1 side and the bottom or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM Fig 17 Dimensional Drawing 60110E24 Gray Cooling...

Страница 14: ...of Massachusetts 1 Gas supply connections MUST be performed by a licensed plumber or gas fitter 2 When flexible connectors are used the maximum length shall not exceed 36 inches 915 mm 3 When lever h...

Страница 15: ...NPT plugged tapping accessible for test gauge connection MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve WARNING FIRE OR EXP...

Страница 16: ...electrical circuit with a properly sized fuse or circuit breaker for this furnace See Table 7 for wire size and fuse specifications A readily accessible means of electrical disconnect must be located...

Страница 17: ...WITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be...

Страница 18: ...es into electrical box 9 Remove cover from furnace J Box 10 Route field ground wire through holes in electrical box and casing and into furnace J Box 11 Reattach furnace J Box to furnace casing with s...

Страница 19: ...board thermostat strip The HUM terminal is energized when the pressure switch closes during a call for heat see Fig 28 NOTE DO NOT connect furnace control HUM terminal to HUM humidifier terminal on Th...

Страница 20: ...or condensation in the venting system These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the NFGC the lo...

Страница 21: ...appliances connected to the venting system are not in operation 1 Seal any unused openings in venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the curre...

Страница 22: ...on in the furnace and or venting system Derating is permitted only for altitudes above 2000 ft 610 M 3 Adjust the air temperature rise to the midpoint of the rise range or slightly above Low air tempe...

Страница 23: ...the furnace being vented Follow all manufacturer s installation requirements for venting and termination included with the listed mechanical venter Caution For the following applications use the mini...

Страница 24: ...lication Vent Elbow Left A03208 Fig 36 Upflow Application Vent Elbow Up A03212 Fig 37 Downflow Application Vent Elbow Up then Right A03218 Fig 38 Horizontal Right Application Vent Elbow Right SEE NOTE...

Страница 25: ...Data Sheet for accessory listing 6 Factory authorized accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration See Product Data Sheet for accessory listing 7...

Страница 26: ...ure will not operate if any thermostat signal is present at the control 4 Component test sequence is as follows see service label attached to furnace or Fig 44 a LED will display previous status code...

Страница 27: ...fices See EXAMPLE 1 3 Adjust manifold pressure to obtain correct input rate a Turn gas valve ON OFF switch to OFF b Remove manifold pressure tap plug from gas valve see Fig 21 c Connect a water column...

Страница 28: ...When thermometer readings stabilize subtract return air temperature from supply air temperature to determine air temperature rise NOTE If the temperature rise is outside this range first check 1 Gas i...

Страница 29: ...Ammeter WARNING FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace life Recheck temperature rise It must be within limits specified on the rating plate Recommende...

Страница 30: ...urn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF then back ON 3 Check Pressure Switch This control proves operation of the draft inducer blower a Turn off 115 v power...

Страница 31: ...S switch until LED goes out then reconnect it NOTE If wire to LS or DSS is disconnected longer than 4 sec main blower starts and status code is overwritten with a limit circuit 33 code 2 When above it...

Страница 32: ...wheel as follows 1 Turn off electrical supply to furnace 2 Remove outer door 3 For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door a...

Страница 33: ...eavy build up of soot and carbon indicates that a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air incorrect size...

Страница 34: ...TV sealant G E 162 P771 9003 is available through RCD in 3 oz tubes 12 Apply new sealant to flange of collector box and attach to cell panel using existing screws making sure all screws are secure 13...

Страница 35: ...zing the humidifier terminal HUM The inducer motor IDM will remain energized for a 5 second post purge period The blower motor BLWM and air cleaner terminal EAC 1 will remain energized for 90 120 150...

Страница 36: ...tart Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 WIRING DIAGRAM A19...

Страница 37: ...f s u o i v e r p o n s a w r a t s l l i w r e c u d n i e h T e c n e u q e s t s e t t n e n o p m o c f e i r b a h g u o r h t o g l l i w n u r d n a t w o l b I S H e h T t s e t t n e n o p m...

Страница 38: ...estricted duct system Loose blower wheel Defective switch or connections Defective blower motor or capacitor Inadequate combustion air supply flame rollout switch open Restricted vent Proper vent sizi...

Страница 39: ...ealer listing by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number series numb...

Страница 40: ...46231 Edition Date 03 20 Catalog No II800SA 04 Replaces II800SA 03 800SA 801SA Installation Start Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any...

Отзывы: