2

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Turn off accessory heater power switch if applicable.

!

WARNING

INTRODUCTION

The 704A packaged air conditioner is fully self--contained and
designed for outdoor installation (See Fig. 1). See Fig. 2 and 3 for

unit dimensions. All unit sizes have discharge openings for both

horizontal and downflow configurations, and are factory shipped
with all downflow duct openings covered. The unit may be installed

either on a rooftop, gound--level cement slab, or directly on the
gound if local codes permit. (See Fig. 4 for roof curb dimensions.)

RECEIVING AND INSTALLATION

Step 1—Check Equipment

IDENTIFY UNIT
The unit model number and serial number are printed on the unit

informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage, have

it examined by transportation inspectors before removal. Forward

claim papers directly to transportation company. Manufacturer is
not responsible for any damage incurred in transit. Check all items

against shipping list. Immediately notify the nearest Bryant Air
Conditioning office if any item is missing. To prevent loss or

damage, leave all parts in original packages until installation.

Step 2—Provide Unit Support

For hurricane tie downs, contact distributor for details and PE

(Professional Engineering) Certificate if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4). Install insulation, cant strips, roofing, and

flashing. Ductwork must be attached to curb.

IMPORTANT

: The gasketing of the unit to the roof curb is critical

for a water tight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.

Curb should be level to within 1/4 in. (See Fig. 6). This is necessary
for unit drain to function properly. Refer to accessory roof curb

installation instructions for additional information as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4

in. thick with 2 in. above grade. The slab should extend
approximately 2 in. beyond the casing on all 4 sides of the unit (See

Fig. 7). Do not secure the unit to the slab

except

when required by

local codes.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground prepared

with gravel for condensate discharge.

Step 3—Provide Clearances

The required minimum service clearances are shown in Fig. 2 and
3. Adequate ventilation and outdoor air must be provided. The

outdoor fan draws air through the outdoor coil and discharges it

through the top fan grille. Be sure that the fan discharge does not

recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance

under a partial overhang (such as a normal house overhang) is 48 in.
above the unit top. The maximum horizontal extension of a partial

overhang must not exceed 48 in.

IMPORTANT

: Do not restrict outdoor airflow. An air restriction at

either the outdoor--air inlet or the fan discharge may be detrimental
to compressor life.

Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on

carpeting or other combustible materials. Slab--mounted units
should be at least 4 in. above the highest expected water and runoff

levels. Do not use unit if it has been under water.

Step 4—Field--Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical

discharge units. Do not connect ductwork to unit. For horizontal
applications, unit is provided with flanges on the horizontal

openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings

with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated

and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to

comply with applicable fire codes. A minimum clearance is not
required around ductwork. Cabinet return--air static shall not exceed

--.25 in. wc.

Step 5—Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many

reasons due to the installation location (roofs, elevated structures,
etc.).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment, and

any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:

1. Application of the lifter to the load, and adjustment of the

lifts to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting

kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work
gloves.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and
straps should be visually inspected for any damage, evidence of

wear, structural deformation, or cracks. Particular attention should
be paid to excessive wear at hoist hooking points and load support

areas. Brackets or straps showing any kind of wear in these areas

must not be used and should be discarded.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Turn off accessory heater power switch if applicable.

Tag disconnect switch with a suitable warning label.

!

WARNING

704A

Содержание 704A

Страница 1: ...iston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 C99062 Fig 1 Unit 704A SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components...

Страница 2: ...e that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a no...

Страница 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Страница 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Страница 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704A024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Страница 6: ...to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be i...

Страница 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Страница 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Страница 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Страница 10: ...nal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Страница 11: ...efrigerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes...

Страница 12: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Страница 13: ...13 A05112 Fig 13 Wiring Diagram 208 230 1 60 704A...

Страница 14: ...14 A06307 Fig 14 Wiring Diagram 208 230 3 60 704A...

Страница 15: ...15 A06485 Fig 15 Wiring Diagram 460 3 60 704A...

Страница 16: ...nit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and complete the circuit through compres...

Страница 17: ...se from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect and tag electrical powerto theunit beforecleaning...

Страница 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Страница 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Страница 20: ...TNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AI...

Отзывы: