Table 3—Wet Coil Air Delivery* — Horizontal Discharge
(Deduct 10% for 208--Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (IN. WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
024
Low
Watts
311
309
304
301
286
—
—
—
—
—
CFM
935
885
820
757
686
—
—
—
—
—
Med
Watts
—
—
—
—
379
357
357
345
327
—
CFM
—
—
—
—
957
868
769
647
365
—
High
Watts
—
—
—
—
—
—
447
435
421
—
CFM
—
—
—
—
—
—
970
853
712
—
030
Low
Watts
311
309
304
301
—
—
—
—
—
—
CFM
935
885
820
757
—
—
—
—
—
—
Med
Watts
411
405
398
390
379
357
357
—
—
—
CFM
1195
1155
1100
1028
957
868
769
—
—
—
High
Watts
—
—
—
—
477
467
447
435
—
—
CFM
—
—
—
—
1185
1088
970
853
—
—
036
Low
Watts
437
433
424
417
403
391
379
362
—
—
CFM
1353
1318
1283
1235
1187
1123
1059
975
—
—
Med
Watts
—
—
—
531
516
496
478
459
435
—
CFM
—
—
—
1489
1437
1362
1289
1208
1099
—
High
Watts
—
—
—
—
—
—
—
629
602
—
CFM
—
—
—
—
—
—
—
1470
1357
—
042
Low
Watts
625
606
586
571
550
534
509
483
457
—
CFM
1539
1496
1466
1437
1387
1330
1264
1183
1093
—
Med
Watts
—
741
715
694
669
645
610
573
544
—
CFM
—
1738
1698
1653
1604
1538
1457
1362
1271
—
High
Watts
—
—
—
—
—
798
772
738
700
—
CFM
—
—
—
—
—
1720
1648
1540
1414
—
048
Low
Watts
627
617
607
584
567
548
528
503
—
—
CFM
1550
1530
1493
1461
1414
1361
1320
1250
—
—
Med
Watts
771
755
734
711
690
665
639
607
572
—
CFM
1798
1771
1734
1687
1645
1595
1530
1449
1355
—
High
Watts
—
—
908
887
858
827
804
767
748
—
CFM
—
—
2000
1994
1876
1811
1735
1647
1555
—
060
Low
Watts
786
769
754
736
722
705
684
658
—
—
CFM
2027
1960
1901
1821
1759
1693
1616
1513
—
—
Med
Watts
873
849
833
815
798
782
763
748
—
—
CFM
2095
2026
1962
1887
1817
1748
1679
1583
—
—
High
Watts
1012
993
981
963
948
927
904
886
—
—
CFM
2184
2109
2036
1963
1886
1812
1729
1647
—
—
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at air-
flows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.