Table 3—Wet Coil Air Delivery* — Horizontal Discharge

(Deduct 10% for 208--Volt Operation)

230 VOLT HORIZONTAL DISCHARGE

UNIT

SIZE

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (IN. WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

311

309

304

301

286

CFM

935

885

820

757

686

Med

Watts

379

357

357

345

327

CFM

957

868

769

647

365

High

Watts

447

435

421

CFM

970

853

712

030

Low

Watts

311

309

304

301

CFM

935

885

820

757

Med

Watts

411

405

398

390

379

357

357

CFM

1195

1155

1100

1028

957

868

769

High

Watts

477

467

447

435

CFM

1185

1088

970

853

036

Low

Watts

437

433

424

417

403

391

379

362

CFM

1353

1318

1283

1235

1187

1123

1059

975

Med

Watts

531

516

496

478

459

435

CFM

1489

1437

1362

1289

1208

1099

High

Watts

629

602

CFM

1470

1357

042

Low

Watts

625

606

586

571

550

534

509

483

457

CFM

1539

1496

1466

1437

1387

1330

1264

1183

1093

Med

Watts

741

715

694

669

645

610

573

544

CFM

1738

1698

1653

1604

1538

1457

1362

1271

High

Watts

798

772

738

700

CFM

1720

1648

1540

1414

048

Low

Watts

627

617

607

584

567

548

528

503

CFM

1550

1530

1493

1461

1414

1361

1320

1250

Med

Watts

771

755

734

711

690

665

639

607

572

CFM

1798

1771

1734

1687

1645

1595

1530

1449

1355

High

Watts

908

887

858

827

804

767

748

CFM

2000

1994

1876

1811

1735

1647

1555

060

Low

Watts

786

769

754

736

722

705

684

658

CFM

2027

1960

1901

1821

1759

1693

1616

1513

Med

Watts

873

849

833

815

798

782

763

748

CFM

2095

2026

1962

1887

1817

1748

1679

1583

High

Watts

1012

993

981

963

948

927

904

886

CFM

2184

2109

2036

1963

1886

1812

1729

1647

*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at air-
flows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

704A

Содержание 704A

Страница 1: ...iston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 C99062 Fig 1 Unit 704A SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components...

Страница 2: ...e that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a no...

Страница 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Страница 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Страница 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704A024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Страница 6: ...to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be i...

Страница 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Страница 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Страница 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Страница 10: ...nal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Страница 11: ...efrigerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes...

Страница 12: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Страница 13: ...13 A05112 Fig 13 Wiring Diagram 208 230 1 60 704A...

Страница 14: ...14 A06307 Fig 14 Wiring Diagram 208 230 3 60 704A...

Страница 15: ...15 A06485 Fig 15 Wiring Diagram 460 3 60 704A...

Страница 16: ...nit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and complete the circuit through compres...

Страница 17: ...se from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect and tag electrical powerto theunit beforecleaning...

Страница 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Страница 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Страница 20: ...TNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AI...