Bryant 704A Скачать руководство пользователя страница 18

18

inner condenser coil, be sure to clean between the coils. Be sure to
flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the
coils. Clean the drain pan and condensate drain by removing all

foreign matter from the pan. Flush the pan and drain trough with

clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted, clear it with a “plumbers

snake” or similar probe device.
OUTDOOR FAN

UNIT OPERATION HAZARD

Failure to follow this caution may result in damage to unit

components.
Keep the condenser fan free from all obstructions to ensure

proper cooling operation. Never place articles on top of the

unit.

CAUTION

!

1. Remove 6 screws holding outdoor grille and motor to top

cover.

2. Turn motor/grille assembly upside down on top cover to

expose fan blade.

3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off

motor shaft.

5. When replacing fan blade, position blade so that the hub is

1/8 in. away from the motor end (1/8 in. of motor shaft will
be visible) (See Fig. 12).

6. Ensure that set screw engages the flat area on the motor shaft

when tightening.

7. Replace grille.

ELECTRICAL CONTROLS AND WIRING
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring.
Check all electrical connections for tightness. Tighten all screw

connections. If any smoky or burned connections are noticed,

disassemble the connection, clean all the parts, re--strip the wire end
and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling

cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check

each

electrical

component

with

the

proper

electrical

instrumentation. Refer to the unit wiring label when making these

checks.
REFRIGERANT CIRCUIT
Inspect all refrigerant tubing connections and the unit base for oil

accumulation annually. Detecting oil generally indicates a
refrigerant leak.

EXPLOSION, PERSONAL INJURY HAZARD

Failure to follow this warning could result in property

damage, personal injury or death.
System under pressure. Relieve pressure and recover all

refrigerant before system repair or final unit disposal. Use all

service ports and open all flow--control devices, including

solenoid valves.

!

WARNING

If oil is detected or if low performance is suspected, leak test all
refrigerant tubing using an electronic leak detector, or liquid--soap

solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,

refer to Checking and Adjusting Refrigerant Charge section.
INDOOR AIRFLOW
The cooling airflow does not require checking unless improper
performance is suspected. If a problem exists, be sure that all

supply-- and return--air grilles are open and free from obstructions,

and that the air filter is clean.
METERING DEVICES--ACCURATER PISTON
This metering device is a fixed orifice and is contained in the brass
body in the liquid line feeding the indoor coil.

TROUBLESHOOTING

Refer to the Troubleshooting Chart (Table 5) for troubleshooting

information.

START--UP CHECKLIST

Use the Start--Up Checklist at the back of this manual.

704A

Содержание 704A

Страница 1: ...iston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 C99062 Fig 1 Unit 704A SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components...

Страница 2: ...e that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a no...

Страница 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Страница 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Страница 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704A024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Страница 6: ...to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be i...

Страница 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Страница 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Страница 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Страница 10: ...nal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Страница 11: ...efrigerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes...

Страница 12: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Страница 13: ...13 A05112 Fig 13 Wiring Diagram 208 230 1 60 704A...

Страница 14: ...14 A06307 Fig 14 Wiring Diagram 208 230 3 60 704A...

Страница 15: ...15 A06485 Fig 15 Wiring Diagram 460 3 60 704A...

Страница 16: ...nit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and complete the circuit through compres...

Страница 17: ...se from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect and tag electrical powerto theunit beforecleaning...

Страница 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Страница 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Страница 20: ...TNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AI...

Отзывы: