WARNING:

Lifting point should be directly over the

center of gravity for the unit. Failure to follow this
warning could result in personal injury or death.

VI.

CONNECT CONDENSATE DRAIN

NOTE:

When installing condensate drain connection be sure to

comply with local codes and restrictions.

Unit disposes of condensate through a 3/4-in. NPT fitting which
exits through the compressor access panel. See Fig. 2–5 (Front
View) for location of condensate connection.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground-
level installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1-in. lower than the drain-pan
condensate connection to prevent the pan from overflowing. Prime
the trap with water. When using a gravel apron, make sure it slopes

away from the unit.
If the installation requires draining the condensate water away
from the unit, install a 2-in. trap using a 3/4-in. NPT connection
(See Fig. 18). Make sure that the outlet of the trap is at least 1-in.
lower than the unit drain-pan condensate connection to prevent the
pan from overflowing. Prime the trap with water. Connect a drain
tube using a minimum of 3/4-in. PVC, 3/4-in. CPVC, or 3/4-in.
copper pipe (all field supplied). Do not undersize the tube. Pitch
the drain tube downward at a slope of at least 1 in. for every 10 ft
of horizontal run. Be sure to check the drain tube for leaks. Prime
trap at the beginning of the cooling season start-up.

VII.

INSTALL DUCT CONNECTIONS

The unit has duct flanges on the supply- and return-air openings on
the side and bottom of the unit. For downshot applications the
ductwork can be connected to the roof curb. See Fig. 2-5 for
connection sizes and locations.

IMPORTANT:

Use flexible connectors between ductwork and

unit to prevent transmission of vibration. Use suitable gaskets to
ensure weathertight and airtight seal. When electric heat is

Fig. 11—Optional Heat Pump Mounting Frame

C95013

NOTES:
1. Material consists of angle iron — 31.8 mm (1-1/4 in.) to 38 mm

(1-1/2 in.) commerical standard.

2. We ldframe together.
3. Pa int with z 

 inc-rich paint (rust-proof).

1

4

2

3

959 mm

(37 3/4  in.)

1

2

3

4

305 mm (12 in.) 

  TO  

    610 mm (24 in.) (4) REQ.

1010 mm
(39 3/4 in.) (2) REQ.

909 mm (35 3/4 in.) (2) REQ.
38 mm (1 1/4 in.)

406 mm (16 in.) (8) REQ.

1060 mm

(41 3/4  in.)

Fig. 12—Indoor Coil Access Panel

C95014

ACCESS PANEL
(REMOVE SCREWS)

—9—

Содержание 657A

Страница 1: ...Also make sure the User s Manual and Replacement Guide are left with the unit after installation SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be hazardous due to...

Страница 2: ...s 2 5 for unit dimensions All units are shipped in a horizontal discharge configuration for installation on a ground level slab All units can be converted to down flow discharge configurations for roo...

Страница 3: ...h the roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 8 This is necessary for unit drain to function properl...

Страница 4: ...maximum horizontal extension of a partial overhang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor air inlet or the fan discharge may be detri...

Страница 5: ...unit has duct flanges on the supply and return air openings on the side of the unit See Fig 2 5 for connection sizes and locations When designing and installing ductwork consider the following CAUTIO...

Страница 6: ...2 Heater limit switches may trip at air quantities below those recommended NOTE A 90 degree elbow must be provided in the supply ductwork to comply with UL Underwriters Laboratories codes for use with...

Страница 7: ...recommended to be used for rigging Install brackets as follows Fig 7 657A Rigging Instructions UNIT SIZE CHART A CHART B Max Weight A B Max Weight C D LB KG IN MM IN MM LB KG IN MM IN MM 024 296 134...

Страница 8: ...tional information Lifting holes are provided in base rails as shown in Fig 7 See Detail A or B B Refer to rigging instructions on unit A INSTALLATION 1 Position the lifting bracket assembly around th...

Страница 9: ...ast 1 in lower than the unit drain pan condensate connection to prevent the pan from overflowing Prime the trap with water Connect a drain tube using a minimum of 3 4 in PVC 3 4 in CPVC or 3 4 in copp...

Страница 10: ...uct Cover C95015 Fig 14 Indoor Blower Access Panel C950016 INDOOR BLOWER ACCESS PANEL REMOVE SCREWS Fig 15 Converting Blower Assembly to Vertical Airflow C950010 PLUG ASSEMBLIES RACEWAY FILLER BRACKET...

Страница 11: ...oles in duct flanges as templates drill the remaining holes with the no 26 147 in drill 5 Fully secure the duct flanges using the remaining screws provided NOTE The finished kit installation accommoda...

Страница 12: ...perimeter of the vertical discharge opening cover See Fig 13 9 Using a straight edge and sharp knife cut the insulation around the perimeter of the cover Remove the screws TABLE 1 PHYSICAL DATA UNIT...

Страница 13: ...nit base Secure using screw removed in Step 7 Reconnect indoor fan motor leads and insert wire tie back into unit control box 13 Cover the horizontal duct openings Duct covers can be ordered as an acc...

Страница 14: ...ground to minimize the pos sibility of personal injury if an electrical fault should occur This ground may consist of an electrical wire connected to the unit ground lug in the control compart ment o...

Страница 15: ...the red lead to the contactor terminal from which the orange lead was disconnected 5 Using the wire nut removed from the red lead insulate the loose terminal on the orange lead 6 Wrap the wire nut wit...

Страница 16: ...60 70 70 80 100 100 22 5 26 0 33 7 39 1 45 1 50 1 67 9 78 1 25 30 35 40 50 60 70 80 22 8 30 30 036 208 230 1 187 253 16 0 88 0 1 2 2 6 3 75 5 00 5 60 7 50 7 50 10 0 11 30 15 0 18 1 20 8 27 1 31 3 36 1...

Страница 17: ...no additional leaks are not found 5 Charge unit with R 22 refrigerant using a volumetric charging cylinder or accurate scale Refer to unit rating plate for required charge Be sure to add extra refrige...

Страница 18: ...room tem perature Observe that compressor outdoor fan and indoor blower motors start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts do...

Страница 19: ...Fig 26 Wiring Diagram 024 to 042 208 230 60 1 C95037 19...

Страница 20: ...Fig 27 Wiring Diagram 048 to 060 208 230 60 1 with ECM Indoor C95038 20...

Страница 21: ...from obstructions and adjusted properly WARNING Disconnect electrical power to the unit and install lockout tag before changing blower speed Elec trical shock can cause serious injury or death Airflo...

Страница 22: ...simultaneously through the Y and G terminals of the thermostat respectively On units with a compressor time delay relay there is a built in 5 minute 45 seconds delay between compressor starts Energiz...

Страница 23: ...AT RANGE VIO setting or the AC HP SIZE BLU setting whichever is greater This may be a noticeable change in airflow When thermostat is satisfied contacts open deenergizing contactor and relay motors an...

Страница 24: ...C INDOOR BLOWER AND MOTOR NOTE Motors without oilers are prelubricated Do not attempt to lubricate these motors For longer life operating economy and continuing efficiency clean accumulated dirt and g...

Страница 25: ...1200 1400 1600 1800 2000 2200 5 20 0 030 0 033 0 037 0 042 0 047 0 052 0 060 0 067 0 075 TABLE 12 FILTER PRESSURE DROP IN WG UNIT SIZE FILTER SIZE IN 500 600 700 800 900 1000 1100 1200 1300 1400 1500...

Страница 26: ...5 6 24 1 25 0 33 3 34 8 33 8 32 6 31 8 31 0 30 2 80 16 4 17 6 21 4 16 8 23 2 31 8 32 2 31 3 30 4 29 5 28 6 85 9 4 8 6 14 7 21 6 29 4 29 8 28 9 27 8 27 0 90 11 6 18 9 26 4 27 3 26 4 25 5 95 3 7 10 8 18...

Страница 27: ...21 6 23 0 24 4 24 5 24 6 80 8 9 8 9 8 9 12 4 16 0 19 4 21 0 22 4 23 8 24 0 24 0 85 8 2 8 2 8 2 11 8 15 3 18 7 20 2 21 8 23 3 23 4 23 4 90 7 7 7 7 7 7 10 8 13 7 16 7 18 7 20 7 22 7 22 7 22 9 95 7 2 7...

Страница 28: ...NOTE Refer to the heating and or cooling sequence of operation in this publication as an aid in determining proper control operation TABLE 13H SUPERHEAT CHARGING TABLE UNIT 060 TEMP F AIR ENT COND EV...

Страница 29: ...evices that are of the fixed orifice type located in the header to the indoor and outdoor coils J LIQUID LINE STRAINER The liquid line strainer to protect metering device is made of wire mesh and loca...

Страница 30: ...ay valve and is directed to the cooling liquid line check valve It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line 2 T...

Страница 31: ...Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant Air in system Recover refrigerant evacuate system and recharge Heat Indoor a...

Страница 32: ...ghtness III START UP Supply Voltage C S __________ S R __________ R C __________ Compressor Amps C __________ S __________ R __________ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Conden...

Отзывы: