NOTE:

Allow system to operate in the cooling mode for a

minimum of 10 minutes before checking or adjusting refrigerant
charge.

CAUTION:

When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must
always be very minimal. If a substantial adjustment is
indicated, an abnormal condition exists somewhere in the
cooling system, such as insufficient airflow across either
coil or both coils. Failure to adjust charge properly or
correct the abnormal conditions will cause damage to the
unit.

Proceed as follows:

1. Remove caps from low- and high-pressure service fittings.

2. Using hoses with valve core depressors, attach low- and

high-pressure gauge hoses to low- and high-pressure service
fittings, respectively.

3. Start unit in Cooling mode and let unit run until system

pressures stabilize.

4. Measure and record the following:

a. Outdoor ambient-air temperature (°F db).

b. Indoor coil inlet-air temperature (°F wb).

c. Suction-tube temperature (°F) at low-side service fitting.

d. Suction (low-side) pressure (psig).

5. Using “Superheat Charging Charts” compare outdoor-air

temperature (°F db) with the Indoor coil air inlet tempera-
ture (°F wb) to determine desired system operating super-
heat temperature. See Table 13A–H and Fig. 30.

6. Using ’’Required Suction-Tube Temperature (F)’’ table,

compare desired superheat temperature with suction (low-
side) operating pressure (psig) to determine proper suction-
tube temperature. See Fig. 30.

7. Compare actual suction-tube temperature with proper

suction-tube temperature. Using a tolerance of ±3° F, add
refrigerant if actual temperature is more than 3° F higher
than proper suction-tube temperature, or remove refrigerant
if actual temperature is more than 3° F lower than required
suction-tube temperature.

NOTE:

If the problem causing the inaccurate readings is a

refrigerant leak, refer to Check for Refrigerant Leaks section.

F.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE:

For cooling operation, the recommended airflow is 350 to

450 cfm for each 12,000 Btuh of rated cooling capacity.

Table 8 shows cooling airflows at various external static pressures.
Table 9 shows Fan Only and Cooling modes for ECM units
(048-060). Refer to these tables to determine the airflow for the
system being installed.

NOTE:

Be sure that all supply- and return-air grilles are open,

free from obstructions, and adjusted properly.

WARNING:

Disconnect electrical power to the unit and

install lockout tag before changing blower speed. Elec-
trical shock can cause serious injury or death.

Airflow can be changed by changing the lead connections of the
blower motor.
Unit 657A three-speed motors (024–042) are factory wired for low
speed operation.

G.

For 208/230v-PSC Blower Motor

For color coding on the 208/230V motor leads, see Table 4.

To change the speed of the indoor fan motor (IFM), remove the fan
motor speed leg lead from the indoor fan relay (IFR) and replace
with lead for desired blower motor speed. Insulate the removed
lead to avoid contact with chassis parts.

H.

For 208/230v-ECM Blower Motor

To configure the 657A 048-60 unit, move the 5 Easy Select board
wires to the terminals which control the airflow. Refer to the Easy
Select interface board (Fig. 29) located next to the terminal.
Perform the following steps for basic system configuration.

1. AUX HEAT RANGE (VIO) NOTE: If no heater is in-

stalled, this step can be omitted. The airflow for electric
heat is selected with the AUX HEAT RANGE terminals.
Refer to Table 2 and the installation instructions for electric
heaters for minimum airflow required for safe heater
operation. Refer to table below for the available airflows.
Each select pin is configured for a certain airflow. The
airflow will be supplied in the Heating mode on air
conditioners when electric heat is the primary heating
source. The preset factory default selection is the highest
airflow.

2. AC/HP SIZE (BLU) - The preset factory default selection

for AC/HP SIZE (air conditioner/heat pump) is set to 400
cfm/ton. The selection pins are configured for 350 cfm/ton
and 400 cfm/ton.

3. TYPE (ORN) - The TYPE is a preset factory default

selection. The preset factory default setting is AC for the
657A units. Default setting should not be altered.

4. AC/HP CFM ADJUST (BLK) - The preset factory default

selection is MED. Selections HI and LO will adjust the
airflow supplied for all operational modes (see table below).
The selection options allow installer to adjust airflow to
meet such individual needs as noise and static compensa-
tion, etc.

Fig. 28—Transformer Label

C95025

TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR

IT WILL NOT AUTOMATICALLY RESET

DISCONNECT POWER AND INSTALL
LOCKOUT TAG PRIOR TO SERVICING

THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING

TABLE 4—COLOR CODING FOR 208/230–V MOTOR

LEADS

3-SPEED

black = high speed

blue = medium speed

red = low speed

—21—

Содержание 657A

Страница 1: ...Also make sure the User s Manual and Replacement Guide are left with the unit after installation SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be hazardous due to...

Страница 2: ...s 2 5 for unit dimensions All units are shipped in a horizontal discharge configuration for installation on a ground level slab All units can be converted to down flow discharge configurations for roo...

Страница 3: ...h the roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 8 This is necessary for unit drain to function properl...

Страница 4: ...maximum horizontal extension of a partial overhang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor air inlet or the fan discharge may be detri...

Страница 5: ...unit has duct flanges on the supply and return air openings on the side of the unit See Fig 2 5 for connection sizes and locations When designing and installing ductwork consider the following CAUTIO...

Страница 6: ...2 Heater limit switches may trip at air quantities below those recommended NOTE A 90 degree elbow must be provided in the supply ductwork to comply with UL Underwriters Laboratories codes for use with...

Страница 7: ...recommended to be used for rigging Install brackets as follows Fig 7 657A Rigging Instructions UNIT SIZE CHART A CHART B Max Weight A B Max Weight C D LB KG IN MM IN MM LB KG IN MM IN MM 024 296 134...

Страница 8: ...tional information Lifting holes are provided in base rails as shown in Fig 7 See Detail A or B B Refer to rigging instructions on unit A INSTALLATION 1 Position the lifting bracket assembly around th...

Страница 9: ...ast 1 in lower than the unit drain pan condensate connection to prevent the pan from overflowing Prime the trap with water Connect a drain tube using a minimum of 3 4 in PVC 3 4 in CPVC or 3 4 in copp...

Страница 10: ...uct Cover C95015 Fig 14 Indoor Blower Access Panel C950016 INDOOR BLOWER ACCESS PANEL REMOVE SCREWS Fig 15 Converting Blower Assembly to Vertical Airflow C950010 PLUG ASSEMBLIES RACEWAY FILLER BRACKET...

Страница 11: ...oles in duct flanges as templates drill the remaining holes with the no 26 147 in drill 5 Fully secure the duct flanges using the remaining screws provided NOTE The finished kit installation accommoda...

Страница 12: ...perimeter of the vertical discharge opening cover See Fig 13 9 Using a straight edge and sharp knife cut the insulation around the perimeter of the cover Remove the screws TABLE 1 PHYSICAL DATA UNIT...

Страница 13: ...nit base Secure using screw removed in Step 7 Reconnect indoor fan motor leads and insert wire tie back into unit control box 13 Cover the horizontal duct openings Duct covers can be ordered as an acc...

Страница 14: ...ground to minimize the pos sibility of personal injury if an electrical fault should occur This ground may consist of an electrical wire connected to the unit ground lug in the control compart ment o...

Страница 15: ...the red lead to the contactor terminal from which the orange lead was disconnected 5 Using the wire nut removed from the red lead insulate the loose terminal on the orange lead 6 Wrap the wire nut wit...

Страница 16: ...60 70 70 80 100 100 22 5 26 0 33 7 39 1 45 1 50 1 67 9 78 1 25 30 35 40 50 60 70 80 22 8 30 30 036 208 230 1 187 253 16 0 88 0 1 2 2 6 3 75 5 00 5 60 7 50 7 50 10 0 11 30 15 0 18 1 20 8 27 1 31 3 36 1...

Страница 17: ...no additional leaks are not found 5 Charge unit with R 22 refrigerant using a volumetric charging cylinder or accurate scale Refer to unit rating plate for required charge Be sure to add extra refrige...

Страница 18: ...room tem perature Observe that compressor outdoor fan and indoor blower motors start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts do...

Страница 19: ...Fig 26 Wiring Diagram 024 to 042 208 230 60 1 C95037 19...

Страница 20: ...Fig 27 Wiring Diagram 048 to 060 208 230 60 1 with ECM Indoor C95038 20...

Страница 21: ...from obstructions and adjusted properly WARNING Disconnect electrical power to the unit and install lockout tag before changing blower speed Elec trical shock can cause serious injury or death Airflo...

Страница 22: ...simultaneously through the Y and G terminals of the thermostat respectively On units with a compressor time delay relay there is a built in 5 minute 45 seconds delay between compressor starts Energiz...

Страница 23: ...AT RANGE VIO setting or the AC HP SIZE BLU setting whichever is greater This may be a noticeable change in airflow When thermostat is satisfied contacts open deenergizing contactor and relay motors an...

Страница 24: ...C INDOOR BLOWER AND MOTOR NOTE Motors without oilers are prelubricated Do not attempt to lubricate these motors For longer life operating economy and continuing efficiency clean accumulated dirt and g...

Страница 25: ...1200 1400 1600 1800 2000 2200 5 20 0 030 0 033 0 037 0 042 0 047 0 052 0 060 0 067 0 075 TABLE 12 FILTER PRESSURE DROP IN WG UNIT SIZE FILTER SIZE IN 500 600 700 800 900 1000 1100 1200 1300 1400 1500...

Страница 26: ...5 6 24 1 25 0 33 3 34 8 33 8 32 6 31 8 31 0 30 2 80 16 4 17 6 21 4 16 8 23 2 31 8 32 2 31 3 30 4 29 5 28 6 85 9 4 8 6 14 7 21 6 29 4 29 8 28 9 27 8 27 0 90 11 6 18 9 26 4 27 3 26 4 25 5 95 3 7 10 8 18...

Страница 27: ...21 6 23 0 24 4 24 5 24 6 80 8 9 8 9 8 9 12 4 16 0 19 4 21 0 22 4 23 8 24 0 24 0 85 8 2 8 2 8 2 11 8 15 3 18 7 20 2 21 8 23 3 23 4 23 4 90 7 7 7 7 7 7 10 8 13 7 16 7 18 7 20 7 22 7 22 7 22 9 95 7 2 7...

Страница 28: ...NOTE Refer to the heating and or cooling sequence of operation in this publication as an aid in determining proper control operation TABLE 13H SUPERHEAT CHARGING TABLE UNIT 060 TEMP F AIR ENT COND EV...

Страница 29: ...evices that are of the fixed orifice type located in the header to the indoor and outdoor coils J LIQUID LINE STRAINER The liquid line strainer to protect metering device is made of wire mesh and loca...

Страница 30: ...ay valve and is directed to the cooling liquid line check valve It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line 2 T...

Страница 31: ...Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant Air in system Recover refrigerant evacuate system and recharge Heat Indoor a...

Страница 32: ...ghtness III START UP Supply Voltage C S __________ S R __________ R C __________ Compressor Amps C __________ S __________ R __________ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Conden...

Отзывы: