background image

14

INSTALL ALL POWER, INTERCONNECTING

WIRING, AND PIPING TO INDOOR UNIT

1. Run interconnecting piping and wiring from the outdoor

unit to the indoor unit.

2. Connect wiring from the outdoor unit per the connection

diagram (see Fig. 26).

3. Replace the field wiring cover and close the indoor unit

front cover.

4. Connect the refrigerant piping and a drain line outside of

the indoor unit. Complete the pipe insulation at the flare

connection then fasten the piping and wiring to the wall as

required. Completely seal the hole in the wall.

5. Piping:

a. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 28).

b. Remove the service connection, if provided with the unit.

Oblique

DŽ

90

Roughness

Burr

A150767

Fig. 28

 - 

Pipe Cutting

c. Remove all the burrs from the cut cross section of the pipe

avoiding any burrs inside the tubes.

d. Remove the flare nuts attached to the indoor and outdoor

units.

e. Install the correct size flare nut onto the tubing and make

the flare connection. See Table 6 for the flare nut spaces.

Table 6—Flare Nut Spacing

OUTER DIAM. (mm)

A (mm)

Max.

Min.

Ø 

1

/

4

(6.35)

0.05 (1.3)

0.03 (0.7)

Ø 

3

/

8

(9.52)

0.06 (1.6)

0.04 (1.0)

Ø 

1

/

2

(12.7)

0.07 (1.8)

0.04 (1.0)

Ø 5/8" (15.88)

0.09 (2.2)

0.08 (2.0)

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"

A

"

A150768

Fig. 29

 - 

Flare Nut Spacing

f. Apply a small amount of refrigerant oil to the flare

connection on the tubing.

g. Align the center of the pipes and/or service valve.

Indoor unit tubing

Flare nut

Piping

A150769

Fig. 30

 - 

Align Pipe Center

h. Connect both the liquid and gas piping to the indoor unit.

i. Tighten the flare nut using a torque wrench as specified in

Table 7.

Table 7—Tightening Torque

PIPE DIAMETER

INCH (mm)

TIGHTENING TORQUE

Ft-lb

N-m

Ø

1

/

4

” 

(6.35)

10 to 13

13.6 to 17.6

Ø

3

/

8

” 

(9.52)

24 to 31

32.5 to 42.0

Ø

1

/

2

” 

(12.7)

37 to 46

50.1 to 62.3

Ø

5

/

8

” 

(15.88)

50 to 60

67.7 to 81.3

Flare nut

Copper tube

A150770

Fig. 31

 - 

Tighten the Flare Nut

6. Connect the drain line. The drain line must not have a trap

anywhere in its length. The drain line must pitch downwards.

The drain line must be insulated up to the outside wall.

NOTE

:  For applications where gravity cannot be used for

drainage, a condensate pump accessory is available. Consult the
condensate pump Installation Instructions for more information.

WIRELESS REMOTE CONTROL INSTALLATION

Mounting Bracket (if installed on the wall)

1. Use the two screws supplied with the control to attach the

mounting bracket to the wall in a location selected by the

customer and within operating range.

2. Install the remote control batteries.
3. Place the remote control into the remote control mounting

bracket.

4. For remote control operation, refer to the unit owner’s

manual.

WIRED REMOTE CONTROLLER

For setup instructions, refer to the wired controller installation

manual. Refer to Fig. 24 for the 4 and 5 Pin connections for the

different wired remote controllers.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

CAUTION

!

Refrigerant tubes and the indoor coil should be evacuated using the

recommended deep vacuum method (500 microns). The alternate

triple evacuation method may be used if the procedure outlined

below is followed. Always break a vacuum with dry nitrogen.

FINAL TUBING CHECK

IMPORTANT

: Ensure certain factory tubing on the indoor unit

has not shifted during shipment. Ensure tubes are not rubbing
against each other or any sheet metal. Pay close attention to the
feeder tubes, making sure the wire ties on the feeder tubes are
secure and tight.

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

RELEASE CHARGE INTO SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

A95425

Fig. 32

 - 

Triple Evacuation Method

Содержание 619REQ009CBMA

Страница 1: ...tual model may differ slightly NOTE Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS IND...

Страница 2: ...hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in...

Страница 3: ...r than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit This ensu...

Страница 4: ...e of BX cable is not recommended Recommended Connection Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3...

Страница 5: ...DY PANEL BODY PANEL BODY PANEL DIMENSIONS Height in mm 10 24 260 1 97 50 10 24 260 1 97 50 10 24 260 1 97 50 Width in mm 22 44 570 25 47 647 22 44 570 25 47 647 22 44 570 25 47 647 Depth in mm 22 44 5...

Страница 6: ...6 CLEARANCES INDOOR Fig 3 Cassette Unit Clearance...

Страница 7: ...it s If not reinforce the site prior to installation Refer to the install cardboard to determine where the location should be reinforced IMPORTANT To guarantee a good performance the unit must be inst...

Страница 8: ...installing optional accessories review the optional accessories list in the installation manual Depending on field conditions it may be easier to install optional accessories before the indoor unit i...

Страница 9: ...tion 1 Indoor drain pipe 2 Drain socket Unit mm 1 2 5 7 0 5 1 1 5m 300 11 8in 6 5 4 3 n i 7 8 0 2 2 n i 5 9 2 0 5 7 n i 3 0 n i 9 0 2 0 3 5 3 5ft Fig 13 Drain Setup Pipe 1 Ceiling slab 2 Hanger bracke...

Страница 10: ...2 Water receiver When the electric wiring work is complete check the drainage flow during COOL running ElectricalWiring 1 Remove the indoor unit control box lid 2 Follow the Wiring Diagram label atta...

Страница 11: ...with the supplied screws see Fig 19 1 Decoration panel 2 Screws M5 supplied with the panel 1 2 Fig 19 Attach the Decoration Panel 3 After installing the decoration panel ensure there is no space betw...

Страница 12: ...x plug to be connected to Wired Controller s cable Grille Display 10 pin Molex plug to be connected to Control Board Grille Louver Motor Power 5 Pin Molex plug to be connected to Control Board Fig 23...

Страница 13: ...1 46 Indoor unit powered by the outdoor unit Permissible limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150634 Fig 26 Connecti...

Страница 14: ...3 5 8 15 88 50 to 60 67 7 to 81 3 Flare nut Copper tube A150770 Fig 31 Tighten the Flare Nut 6 Connect the drain line The drain line must not have a trap anywhere in its length The drain line must pit...

Страница 15: ...the tubing where possible 2 Ensure the drain tube slopes downward along its entire length 3 Ensure all tubing and connections are properly insulated 4 Fasten the tubes to the outside wall when possibl...

Страница 16: ...ent overload protection 2 times O F1 Open circuit or short circuit of outdoor ambient temperature sensor T4 3 times O F2 Open circuit or short circuit of condenser coil temperature sensor T3 4 times O...

Отзывы: