40
NOTE: For more information, see General Fan Performance Notes.
PULLEY ADJUSTMENT - BELT DRIVE
582J UNIT
MOTOR/
DRIVE
COMBO
MOTOR PULLEY TURNS OPEN
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
04
1 phase
Medium
Static
1175
1135
1094
1054
1013
973
932
892
851
811
770
High
Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
05
Medium
Static
1175
1135
1094
1054
1013
973
932
892
851
811
770
High
Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
06
Medium
Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
High
Static
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
04
3 phase
Medium
Static
1175
1135
1094
1054
1013
973
932
892
851
811
770
High
Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
05
Medium
Static
1303
1265
1226
1188
1150
1112
1073
1035
997
958
920
High
Static
1550
1516
1482
1447
1413
1379
1345
1311
1276
1242
1208
06
Medium
Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
High
Static
1550
1525
1501
1476
1451
1427
1402
1377
1352
1328
1303
–
Factory setting
N/A
–
Not Available
PERFORMANCE DATA (cont)