CONVENIENCE OUTLETS
Two types of convenience outlets are offered on 580J mod-
els: Non-powered and unit-powered. Both types provide a 125-
volt GFCI (ground-fault circuit-interrupter) duplex receptacle
rated at 15-A behind a hinged waterproof access cover, located
on the end panel of the unit. See Fig. 26 for amp limitations.
See Fig. 27 for convenience outlet location.
Fig. 26 — Convenience Outlet Utilization Notice Label
NOTE: Unit powered convenience outlets are not available
as factory installed options for single phase (-J voltage
code) models.
Fig. 27 — Convenience Outlet Location
Installing Weatherproof Cover — A weatherproof while-in-
us cover for the factory-installed conenience outlets is now re-
quired by UL standards. This cover cannot be factory-mounted
due its depth; it must be installed at unit installation. For ship-
ment, the convenience outlet is covered with a blank cover
plate.
On units with electro-mechanical controls the weatherproof
cover kit is shipped in the unit’s control box. The kit includes
the hinged cover, a backing plate and gasket.
On units with the factory installed RTU Open option the
weatherproof cover kit is secured to the basepan underneath
the control box. See Fig. 28.
Fig. 28 — Weatherproof Cover — Shipping Location on
Units with Factory Installed RTU Open
Remove the blank cover plate at the convenience outlet.
Loosen the two screws at the GFCI duplex outlet, until ap-
proximately
1
/
2
-in. (13 mm) under screw heads are exposed.
Press the gasket over the screw heads. Slip the backing plate
over the screw heads at the keyhole slots and align with the
gasket; tighten the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 29. Remove two slot fillers in the bottom of the
cover to permit service tool cords to exit the cover. Check for
full closing and latching.
Fig. 29 — Weatherproof Cover Installation
WARNING
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status
before opening unit for service. Locate its disconnect
switch, if appropriate, and open it. Lock-out and tag-out
this switch, if necessary.
Convenience
O
u
tlet
GFCI
Pwd-CO
F
us
e
S
witch
Pwd-CO
Tr
a
n
s
former
Control Box
Acce
ss
P
a
nel
IMPORTANT: DISCONNECT ALL POWER TO
UNIT AND CONVENIENCE OUTLET. LOCK-OUT
AND TAG-OUT ALL POWER PRIOR TO INSTAL-
LATION.
Weatherproof
Cover
RECEPTACLE
NOT SHOWN
COVER – WHILE-IN-USE
WEATHERPROOF
BASE PLATE FOR
GFCI RECEPTACLE
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......