Table 8 — 551B060 Air Delivery — Vertical Discharge Units
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
711
0.33
769
0.39
878
0.51
971
0.64
1052
0.78
1600
751
0.39
806
0.45
906
0.58
1004
0.73
1087
0.88
1700
791
0.46
846
0.53
941
0.66
1030
0.80
1112
0.96
1800
852
0.55
905
0.62
1002
0.78
1084
0.93
1163
1.10
1900
894
0.64
945
0.72
1037
0.88
1119
1.04
1194
1.21
2000
936
0.74
984
0.82
1072
0.98
1154
1.16
1226
1.33
2100
978
0.85
1024
0.93
1108
1.10
1190
1.29
1259
1.47
2200
1021
0.97
1064
1.05
1145
1.22
1225
1.43
1294
1.62
2300
1064
1.10
1104
1.18
1183
1.36
1260
1.57
1330
1.78
2400
1107
1.24
1145
1.32
1222
1.52
1296
1.73
1365
1.94
2500
1150
1.39
1186
1.48
1262
1.68
1331
1.89
1400
2.12
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1134
0.95
1213
1.11
1276
1.38
1331
1.49
1600
1159
1.02
1231
1.20
1311
1.39
1395
1.59
1700
1184
1.12
1258
1.30
1322
1.49
1403
1.69
1800
1235
1.29
1303
1.48
1371
1.69
1433
1.90
1900
1266
1.40
1330
1.59
1396
1.81
1460
2.03
2000
1297
1.53
1362
1.73
1422
1.94
1485
2.16
2100
1327
1.66
1393
1.87
1452
2.08
1510
2.31
2200
1359
1.81
1423
2.02
1483
2.24
1538
2.46
2300
1392
1.97
1454
2.18
1515
2.41
1569
2.64
2400
1426
2.15
1485
2.36
1544
2.59
1601
2.84
2500
1461
2.34
1518
2.55
1575
2.78
—
—
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface
indicates
a
field-supplied
drive
is
required.
(See
Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp.
4. Maximum continuous bhp is 1.80. Extensive motor and electrical
testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your
local representative to verify.
7. Motor drive range: 1020 to 1460. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
—23—