Table 23 – RTU Open Controller Inputs and Outputs
POINT NAME
BACnet OBJECT
NAME
TYPE OF I/O
CONNECTION
PIN NUMBER(S)
CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp
zone_temp
AI (10K Thermistor)
J20--- 1 and 2
Analog Input 10
Supply Air Temperature
sa_temp
AI (10K Thermistor)
J2--- 1 and 2
Analog Input 6
Outside Air Temperature
oa_temp
AI (10K Thermistor)
J2--- 3 and 4
Analog Input 7
Space Temperature Offset Pot
stpt_adj_offset
AI (100K Potentiometer)
J20--- 3 and 4
Analog Input 11
Safety Chain Feedback
safety_status
BI (24 VAC)
J1--- 9
Binary Input 4
Compressor Safety Status
(1)
comp_status
BI (24 VAC)
J1--- 2
Binary Input 3
Fire Shutdown Status
firedown_status
BI (24 VAC)
J1--- 10
Binary Input 5
Enthalpy Status
enthalpy_status
BI (24 VAC)
J2--- 6 and 7
Binary Input 8
Humidistat Input Status
humstat_status
BI (24 VAC)
J5--- 7 and 8
Binary Input 9
Zone Temperature
n/a
n/a
J13--- 1--- 4
Rnet
CONFIGURABLE INPUTS
(4)
Indoor Air CO2
iaq
AI (4--- 20 mA)
J4---2 and 3 or J4---5 and 6
Analog Input 2
Outdoor Air CO2
oaq
AI (4--- 20 mA)
Analog Input 1
Space Relative Humidity
space_rh
AI (4--- 20 mA)
Analog Input 10
Supply Fan Status
(2)
sfan_status
BI (24 VAC)
J5---1 and 2 or J5---3 and 4,
J5---5 and 6 or J5---7 and 8
(3)
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Filter Status
(2)
filter_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Door Contact
(2)
door_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Remote Occupancy input
(2)
occ_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
IGC input
(2)
igcovr_status
BI (24 VAC)
Binary Input 9. Mandatory input on gas heat units.
OUTPUTS
Economizer Output
econ_output
AO (4--- 20mA)
J2--- 5
Analog Output 1
Supply Fan VFD
vfd_output
AO (2--- 10Vdc)
J22--- 1 and 2
Analog Output 2
Supply Fan Relay
sfan
BO Relay (24VAC, 1A)
J1--- 4
Binary Output 1 (G)
Cool 1 Relay State
comp_1
BO Relay (24VAC, 1A)
J1--- 8
Binary Output 5 (Y1)
Cool 2 Relay State
comp_2
BO Relay (24VAC, 1A)
J1--- 7
Binary Output 4 (Y2)
Cool 3 Relay State
comp_3
BO Relay (24VAC, 1A)
J11--- 5 and 6
Binary Output 7 (Y3)
Heat 1 Relay State
heat_1
BO Relay (24VAC, 1A)
J1--- 6
Binary Output 3 (W1)
Heat 2 Relay State
heat_2
BO Relay (24VAC, 1A)
J1--- 5
Binary Output 2 (W2)
Power Exhaust Relay State
pexh
BO Relay (24VAC, 1A)
J11--- 2 and 3 (N.O.)
Binary Output 8 (PE)
Dehumidification Relay
dehum
BO Relay (24VAC, 1A)
J11--- 7 and 8 (N.O.)
Binary Output 6
LEGEND
AI
---
Analog Input
AO
---
Analog Output
BI
---
Binary Input
BO
---
Binary Output
(1)
Safety Chain Feedback: 24Vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instructions.
(2)
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.
(3)
Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field installation.
(4)
Refer to the input configuration and accessory sections of the
RTU Open Multi---Protocol Controller Controls, Start ---Up, Operation and Troubleshooting
manual for more detail.
The RTU Open controller requires the use of a Bryant space
sensor. A standard thermostat cannot be used with the RTU
Open controller system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 549J unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--in. (152 mm)
in length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
codes). Drill or punch a
1
/
2
--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 45.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
SUPPLY AIR
RETURN AIR
SUPPLY AIR
TEMPERATURE
SENSOR
ROOF
CURB
C08200
Fig. 45 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
Содержание 549J Series
Страница 4: ...4 C160144 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Страница 5: ...5 C160145 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Страница 6: ...6 C10757A Fig 3 Unit Dimensional Drawing 09 Size Units ...
Страница 7: ...7 C10758A Fig 3 Unit Dimensional Drawing 09 Size Unit cont ...
Страница 40: ...40 a549J 001 Fig 44 Typical RTU Open Controller Wiring Diagram ...