Unit without thru--base connection kit —
Pass the thermostat control wires through the hole
provided in the corner post; then feed the wires through
the raceway built into the corner post to the control box.
Pull the wires over to the terminal strip on the upper--left
corner of the Central Terminal Board (CTB). See Fig. 31.
RACEWAY
HOLE IN END PANEL (HIDDEN)
C08027
Fig. 31 -- Field Control Wiring Raceway
NOTE
:
If thru--the--bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating, when available.
Electric Heaters
549J units may be equipped with field--installed accessory
electric heaters. The heaters are modular in design, with
heater frames holding open coil resistance wires strung
through ceramic insulators, line--break limit switches and
a control contactor. One or two heater modules may be
used in a unit.
Heater modules are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 32, Fig. 33 and Fig. 34.
Not all available heater modules may be used in every
unit. Use only those heater modules that are UL listed for
use in a specific size unit. Refer to the label on the unit
cabinet for the list of approved heaters.
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sales Package part number. See
Table 7 for correlation between heater Model Number and
Sales Package part number.
NOTE
: The value in position 9 of the part number differs
between the sales package part number (value is 1 or 3)
and a bare heater model number (value is 0).
DISCONNECT MOUNTING
LOCATION
UNIT BLOCK-OFF
PANEL
OUTDOOR
ACCESS PANEL
INDOOR
ACCESS
PANEL
C08133
Fig. 32 -- Typical Access Panel Location
DISCONNECT
MOUNTING
LOCATION
EMT OR RIGID CONDUIT
(FIELD-SUPPLIED)
SINGLE
POINT BOX
CENTER
POST
HEATER
COVERS
HEATER
MOUNTING
BRACKET
HEATER
MODULE
(LOCATION 2)
HEATER
MODULE
(LOCATION 1)
SINGLE POINT
BOX
MOUNTING
SCREW
BRACKET AND
CONDUIT
DRIP BOOT
MAIN
CONTROL
BOX
CONTROL WIRE TERMINAL BLOCK
MANUAL RESET
LIMIT SWITCH
C08134
Fig. 33 -- Typical Component Location
TRACK
FLANGE
C08135
Fig. 34 -- Typical Module Installation
Содержание 549J Series
Страница 4: ...4 C160144 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Страница 5: ...5 C160145 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Страница 6: ...6 C10757A Fig 3 Unit Dimensional Drawing 09 Size Units ...
Страница 7: ...7 C10758A Fig 3 Unit Dimensional Drawing 09 Size Unit cont ...
Страница 40: ...40 a549J 001 Fig 44 Typical RTU Open Controller Wiring Diagram ...