31
Table 11 -- Menu Structure
*
(cont)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED PARAMETER NAME
Notes
STATUS
(cont)
COOL Y1---IN
OFF
ON/OFF
FIRST STAGE COOLING DEMAND (Y1---IN)
Y1---I signal from space thermostat or unitary controller for Cooling Stage 1.
ON = 24 Vac on terminal Y1---I
OFF = 0 Vac on terminal Y1---I
COOL Y1---OUT
OFF
ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
Cool Stage 1 Relay Output to mechanical cooling (Y1---OUT terminal).
COOL Y2---IN
OFF
ON/OFF
SECOND STAVE COOLING DEMAND (Y2---IN)
Y2---I signal from space thermostat or unitary controller for Cooling Stage 2.
ON = 24 Vac on terminal Y2---I
OFF = 0 Vac on terminal Y2---I
COOL Y2---OUT
OFF
ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling (Y2---OUT terminal).
MA TEMP
_ _._
_
F
(or _ _._
_
C)
---40 to 150
_
F
(---18 to 60
_
C)
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed/cooled air from SAT sensor in fan
section.
Displays --- ---.--- if not connected, short or out---of---range. See Menu Note 2
DA TEMP
_ _._
_
F
(or _ _._
_
C)
---40 to 150
_
F
(---18 to 60
_
C)
DISCHARGE AIR TEMPERATURE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
discharge temperature.
Displays --- ---.---
_
F if sensor sends invalid value, if not connected, short or
out---of---range.
OA TEMP
_ _._
_
F
(or _ _._
_
C)
---40 to 140
_
F
(---40 to 60
_
C)
OUTSIDE AIR TEMPERATURE
Displays measured value of outdoor air temperature.
Displays --- ---
_
F if sensor sends invalid value, if not connected, short or
out---of---range.
OA HUM
_ _%
0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA enthalpy sensor.
RA TEMP
_ _._
_
F
(or _ _._
_
C)
0 to 140
_
F
(---18 to 60
_
C)
RETURN AIR TEMPERATURE
(Accessory sensor required)
Displays measured value of return air temperature from RAT sensor.
Displays --- ---
_
F if sensor sends invalid value, if not connected, short or
out---of---range.
RA HUM
_ _%
0 to 100%
RETURN AIR RELATIVE HUMIDITY
(Accessory enthalpy sensor required)
Displays measured value of return air humidity from RA sensor.
Displays --- ---% if sensor sends invalid value, if not connected, short or
out---of---range.
IN CO2
_ _ _ ppm
0 to 2000 ppm
SPACE/RETURN AIR CO2
(CO
2
sensor required, accessory or factory option)
Displays value of measured CO
2
from CO
2
sensor.
Invalid if not connected, short or out---of---range. May be adjusted in
Advanced menu by Zero offset and Span.
DCV STATUS
n/a
ON/OFF
DEMAND CONTROLLED VENTILATION STATUS
(CO
2
sensor required, accessory or factory option)
Displays ON if IN CO2 value above setpoint DCV SET and OFF if below
setpoint DCV SET.
DAMPER OUT
2.0V
2.0 to 10.0V
Displays output voltage or position to the damper actuator. ***
ACT POS
n/a
0 to 100%
Displays actual position of outdoor air damper actuator
ACT COUNT
n/a
1 to 65535
Displays number of times actuator has cycled.
1 Cycle equals accrued 180
_
of actuator movement in any direction
ACTUATOR
n/a
OK/Alarm
(on Alarm menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT
OFF
ON/OFF
EXHAUST STAGE 1 RELAY OUTPUT
Output of EXH1 terminal. Displays On when damper position reaches
programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
EXH2 OUT
OFF
ON/OFF
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX1 O terminal Displays ON when damper position reaches
programmed percentage setpoint
ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O =
EXH2
ERV
OFF
ON/OFF
ENERGY RECOVERY UNIT RELAY OUTPUT
Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No Output;
displays only if AUX1 O = ERV
MECH COOL ON
or
HEAT STAGES ON
0
0, 1, or 2
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active
FAN SPEED
n/a
LOW or HIGH
SUPPLY FAN SPEED
Displays speed setting of fan on a 2---speed fan unit.
W (HEAT ON)
n/a
ON/OFF
HEAT DEMAND STATUS
Displays status of heat demand on a 2---speed fan unit.
Содержание 548J*14D Series
Страница 5: ...5 a548J 011 Fig 2 Unit Dimensional Drawing Size 14 Unit...
Страница 6: ...6 a548J 012 Fig 2 Unit Dimensional Drawing Size 14 Unit cont...
Страница 10: ...10 a548J 013 Fig 6 Roof Curb Details...
Страница 17: ...17 a50 9707 Fig 26 Typical 548J Size 14 Control Wiring Diagram...
Страница 43: ...43 a50 9711 Fig 49 RTU Open Controller System Wiring Diagram...