28
Outputs —
Actuator signal:
2--10 Vdc; minimum actuator impedance
is 2k ohm; bus two--wire output for bus communicating
actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental —
Operating Temperature:
--40 to 150
_
F (--40 to 65
_
C).
Exception of display operation down to --4
_
F with full
recovery at --4
_
F from exposure to --40
_
F
Storage Temperature:
--40 to 150
_
F (--40 to 65
_
C)
Shipping Temperature:
--40 to 150
_
F (--40 to 65
_
C)
Relative Humidity:
5% to 95% RH non--condensing
Economizer Module Wiring Details —
Use Fig. 43 and Tables 7 and 8 to locate the wiring
terminals for the economizer module.
NOTE
: The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then slide it
back into place.
W7220 Controller
Left Terminal
Block Label
Right Terminal
Block Label
NOTE: The bottom 4 Pin actuator header is not used
C14156
Fig. 43 -- W7220 Economizer Module Terminal
Connection Labels
S--Bus Sensor Wiring —
The labels on the sensors and controller are color coded
for ease of installation. Orange labeled sensors can only
be wired to orange terminals on the controller. Brown
labeled sensors can only be wired to S--Bus (brown)
terminals. Use Fig. 44 and Table 9 to locate the wiring
terminals for each S--Bus sensor.
Use Fig. 44 and Table 10 to set the DIP switches for the
desired use of the sensor.
Table 7 – Economizer Module --
Left Hand Terminal Blocks
Label
Type
Description
Top Left Terminal Block
MAT
MAT
20k NTC
and
COM
Supply Air Temperature Sensor
(polarity insensitive connection)
OAT
OAT
20k NTC
and
COM
Outdoor Air Temperature Sensor
(polarity insensitive connection)
S---BUS
S---BUS
S---Bus
(Sylk* Bus)
Enthalpy Control Sensor
(polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2---10
2---10 Vdc
Air Quality Sensor Input
(e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 Vac
Air Quality Sensor 24 Vac Source
ACT 2---10
2---10 Vdc
Damper Actuator Output (2---10 Vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24V
24 Vac
Damper Actuator 24 Vac Source
n/a
The bottom pin is not used.
Table 8 – Economizer Module --
Right Hand Terminal Blocks
Label
Type
Description
Top Right Terminal Block
n/a
The first pin is not used
AUX2 I
24 Vac IN
Shut Down (SD) or Heat (W)
Conventional only
or
Heat Pump Changeover (O/B) in
Heat Pump mode.
OCC
24 Vac IN
Occupied / Unoccupied Input
E---GND
E---GND
Earth Ground --- System Required
EXH1
24 Vac OUT Exhaust Fan 1 Output
AUX1 O
24 Vac OUT Programmable:
Exhaust fan 2 output
or
Erv
or
System Alarm output
Bottom Right Terminal Block
Y2---I
24 Vac IN
Y2 in --- Cooling Stage 2 Input from
space thermostat
Y2---O
24 Vac OUT Y2 out --- Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1---I
24 Vac IN
Y1 in --- Cooling Stage 1 Input from
space thermostat
Y1---O
24 Vac OUT Y1 out --- Cooling Stage 1 Output to
stage 1 mechanical cooling
C
COM
24 Vac Common
R
24 Vac
24 Vac Power (Hot)
* Sylk is a trademark of Honeywell International Inc.
Содержание 548J*14D Series
Страница 5: ...5 a548J 011 Fig 2 Unit Dimensional Drawing Size 14 Unit...
Страница 6: ...6 a548J 012 Fig 2 Unit Dimensional Drawing Size 14 Unit cont...
Страница 10: ...10 a548J 013 Fig 6 Roof Curb Details...
Страница 17: ...17 a50 9707 Fig 26 Typical 548J Size 14 Control Wiring Diagram...
Страница 43: ...43 a50 9711 Fig 49 RTU Open Controller System Wiring Diagram...