Fig. 23 — 

Typical EconoMi$er X Wiring Diagram for 1 or 2 Speed Units (Not for 48/50LC 07-12 Units)

Instructions for 48/50LC 07-12 Units Only

1. Follow steps 1 through 10 in the previous section.

2. The  48/50LC  07-12  units  require  different  wiring  than  is

factory-attached  to  the  W7220  controller.  Disconnect  the

complete wiring harness factory-attached to the W7220 con

-

troller, as shown below in Fig. 24. This harness can be dis

-

carded.

NOTE: The 4-wire 48TMHSRSE--A20 harness provided with the

economizer will also NOT be used on the 48/50LC07-12 units;

see Fig. 25.

3. The 48/50LC 07-12 units that do not have a factory-installed

economizer will have a new W7220 controller wiring harness

shipped in the control box section of the HVAC unit. This

harness, Carrier part number 48LCHSRADH--A00, is shown

in Fig. 27 and 26.

4. The  connectors  on  the  right  side  of  Fig.  27  on  the

48LCHSRADH--A00 harness attach to the W7220 controller

installed  in  the  unit  control  box.  (See  Fig.  26  and  28.)

48LCHSRADH--A00  harness  connectors  are  labeled  to

easily identify the plug-in location on the controller.

5. Locate the Compressor Staging Control (CSC) board in the

HVAC unit. When a field-installed economizer is used the J5

jumper on the CSC must be removed. Remove the J5 jumper.

(See Fig. 28.)

6. The  connectors  on  the  left  side  of  Fig.  26  on  the

48LCHSRADH--A00 harness attach to the unit’s CSC board.

Connect J3 and J5 plugs to the CSC board.

7. Screw  the  green  wire  with  yellow  stripe  in  the

48LCHSRADH--A00  harness  to  the  control  box  (ground).

(See Fig. 12 and 28.)

8. Mount  the  provided  HH79AH001  mixed  air  temperature

(MAT) sensor (C7250) to the indoor blower. Confirm that the

screws do not interfere with blower rotation. (See Fig. 15.)

Locate the 50HE403859 2-green wire harness shipped with

the EconoMi$er X kit. It will have a plug on one end and

terminals on the other end. Connect the plug from this harness

to  the  MAT  sensor.  (See  Fig.  15.)  Connect  the  (2)  spade

terminals on the 50HE403859 harness to orange and brown

wires in the indoor blower section wire bundle.

9. Follow steps 21 through 25 earlier in these instructions.

Mixed Air Sensor

Field Mount on

Indoor Blower

1

HH79AH001

HONEYWELL C7250

Dry Bulb

Outside Air

Sensor

12-Pin Female

Plug from Economizer

Economizer 

Harness 

In Unit

50HE403859

Harness

GRN
GRN

WHT

BLK

GRN

BLU

BLK

GRA

GRA

GRA

GRA

PNK

PNK

BLU

BLK

PNK

GRA

GRA

GRA

RED

PNK

ORG

BRN

YEL

VIO

VIO

VIO

ORG

ORG

BRN

BRN

GRN

GRN

6

7

2

3

10

11

5

1

12

9

4

8

RED

ORG

1

2

3

4

RED

Economizer

Actuator

1

2

3

4

HH57AC081

1

2

1

Enthalpy Outside

Air Sensor

To Optional

Power Exhaust

PL6

Plug

12-Pin Male

Plug in Unit

48TMHSRSE--A20

Harness with

4-Pin Female Plug

4-Pin Male

Plug

10-Pin Male

Plug

PNK

BLU

BLK

GRA

GRA

RED

“R” ON CTB

ORG

BRN

YEL

“C” ON CTB

BLU

BLK

GRN / YEL

WHT

BLU

GRA

ORG

YEL

BLK

BRN

RED

VIO

1

1

2

2

3

3

4

10

6

4

5

9

1

3

8

2

7

1

2

3

4

5

6

7

8

9

10

4

9

3

8

10

2

6

7

5

1

4

10-Pin Female

Plug Disconnected

from CTB

CO2

(Optional)

Ground

“W1” on CTB

W7220 Controller,

Field Mounted in

Unit Control Box

MAT

MAT

OAT

OAT

ACT 24V

ACT COM

S-BUS

S-BUS

EXH1

IAQ COM

ACT 2-10

AUX1 OUT

IAQ 2-10

E-GRD

AUX2 IN

Y1 IN

Y1 OUT

Y2 OUT

Y2 IN

OCC

C

R

10-Pin Female

Plug Connects to

ECON on

Central Terminal

Board

BRN

YEL

Either the OAT or the Enthalpy
Sensor can be used but not both.
Remove OAT if Enthalpy’s used.

Refer to Figures 33 and 34 for Remote
Fault Detection and Diagnostic Monitoring.

LEGEND

3

Refer to Figure 31 for wiring optional
Differential Return Air Sensor kit.

ECONOMIZER RETURN CHAMBER

INDOOR BLOWER SECTION

UNIT CONTROL BOX COMPARTMENT

DA

RA

OA

12

3

S-Bus

Temp & Humidity

HH57AC081

S-Bus

CTB: Central Terminal Board
MAT: Mixed Air Temperature Sensor
OAT: Outside Air Temperature Sensor

HH79AH001

HONEYWELL C7250

IMPORTANT:  This  section  is  for  economizer  installation

instructions on 48/50LC 07-12 units only.

Содержание 547J

Страница 1: ...in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will ...

Страница 2: ... Table 4 for package contents See Table 5 for sensor usage IMPORTANT These economizers meet all the economizer requirements as specified in ASHRAE 90 1 IECC and California s Title 24 Economizer must be installed square to avoid damper leakage or damper binding Squareness tolerance is 1 32 in IMPORTANT Read these instructions completely before attempting to install the accessory economizer Table 1 ...

Страница 3: ...r 1 50HE403859 2 green wire harness for mixed air temperature sensor 1 48TMHSRSE A20 4 Wire Harness 1 Hood Assembly with Top and 2 Sides 1 Hood Divider 1 Hood Filter Divider 2 Aluminum Filters 1 Hardware Bag Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dry bulb sensor is factory installed...

Страница 4: ...0 pin female plug from the controller harness to ECON on the CTB See Fig 10 and page 9 14 Connect the White wire from the controller harness to the W1 terminal on the CTB See Fig 10 and page 9 15 Connect the red and brown wires from the controller harness to the CTB See Fig 11 and page 9 The red wire connects to R on the CTB and the brown wire connects to C 16 Locate the green wire with yellow str...

Страница 5: ... Some control box configurations may differ Fig 7 Mount Controller Assembly in Unit Control Box Fig 8 Unplug ECON Plug from Central Terminal Board CTB HVAC Unit Filters Insert Screw in EconoMi er X Flanges Wiring Harness EconoMi er X Unit Filter Rack Unit Base Economi er X Hold Down Tab Economi er X Rear Flange Economi er X Rooftop Unit s 12 Pin Male Plug EconoMi er X 12 Pin Female Plug Indoor Fan...

Страница 6: ...10 Connect 10 Pin Plug to Central Terminal Board Fig 11 Connect Red and Brown Wires to Central Terminal Board Fig 12 Connect Ground Wire From Controller Central Terminal Board White Wire 10 Pin Female Plug from Controller Central Terminal Board ...

Страница 7: ...d Connect Mixed Air Sensor Fig 16 Connect Pink and Violet Wires in Indoor Blower Section 4 pin Male Plug From Controller 48TMHSRSE A20 Harness Control Box 48TMHSRSE A20 Harness Indoor Blower Section Brown and Orange wires from 48TMHSRSE A20 Harness Indoor Blower Mixed Air Temperature Sensor 50HE403589 2 Green Wire Harness Pink and Violet Wires from 48TMHSRSE A20 Harness Indoor Blower ...

Страница 8: ...A01 30 37 17 43 19 05 29 50 55 CRECOMZR069A01 40 37 22 28 24 48 36 27 80 CRECOMZR071A01 52 92 27 03 33 41 46 92 98 A B C Hood Top And Side Assembly Hood Divider D Hood Filter Divider Hood Top Filter Clip Outside Air Cleanable Aluminum Filter Barometric Airflow Hood Divider EconoMi er X Hood Filter Door 0 500 1000 1500 2000 2500 0 0 05 0 1 0 15 0 2 0 25 0 3 RELIEF FLOW CFM RETURN DUCT STATIC PRESSU...

Страница 9: ... one end and terminals on the other end Connect the plug from this harness to the MAT sensor See Fig 15 Connect the 2 spade terminals on the 50HE403859 harness to orange and brown wires in the indoor blower section wire bundle 9 Follow steps 21 through 25 earlier in these instructions Mixed Air Sensor Field Mount on Indoor Blower 1 HH79AH001 HONEYWELL C7250 Dry Bulb Outside Air Sensor 12 Pin Femal...

Страница 10: ...g 24 Remove Complete Harness Factory Attached to W7220 Controller Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units Fig 26 Photo of 48LCHSRADH A00 W7220 Controller Harness Shipped with 48 50LC 07 12 Units ...

Страница 11: ...11 Fig 27 48LCHSRADH A00 W7220 Controller Harness Shipped With 48 50LC 07 12 Units ...

Страница 12: ...ld is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not used with 48 50LC 07 12 units ...

Страница 13: ...for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081 Dimensional Connection and Switching Information LEGEND Default Setting OFF OFF OFF IMPORTANT To use the HH57AC081 sensor for outside air sensor the dip switches on the sensor must be set to OFF OFF OFF See Table 8 ECONOMIZING AVAILABLE NOT AVAILABLE ENTHALPY RA HUM RH RA TEMP TEMPERATURE ABSOLUTE HUMIDITY ES5 ES4 ES3 ES2 ES1 HL P1 T RH ...

Страница 14: ...value at 75 F and 50 relative humidity As an example at approximately 6 000 foot elevation the fixed enthalpy limit is approximately 30 7 Btu lb Demand Controlled Ventilation DCV Refer to EconoMi er X wiring diagrams Fig 23 and 28 and DCV instructions if demand control ventilation CO2 sensor is used CO2 sensor will wire into the blue and black connections at the controller as shown in Fig 23 28 an...

Страница 15: ... that is acceptable to some codes is an annunciator light visible by service personnel See Fig 34 for typical wiring to the controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired For Remote FDD Fig 34 Annunciator Light Wired for Remote FDD C R AUX2 1 OCC E GND EXH1 AUX1 0 Y2 I Y2 O Y1 I Y1 O C R W7220 ECONOMIZER U1 U1 R Rc C A L A TH8321R OR TH8321WF SUB BASE MAT Controller...

Страница 16: ...nu parameter 10 Press the Menu Up Exit button to return to the previous menu Menu Structure Refer to Table 10 for summarized standard settings Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The menus in display order are STATUS SETPOINTS SYSTEM SETUP ADVANCED SETUP CHECKOUT ALARMS PROGRAMMING W7220 CONTROLLER The next several pages detail the differ...

Страница 17: ...ble 10 Standard W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F 53 F 38 to 70 F LOW T LOCK 32 F 45 to 80 F 32 F 45 to 80 F DRYBLB SET 63 F 48 to 80 F 63 F 48 to 80 F Only displayed if using single DB OA sensor ENTH CURVE ES3 ES1 to ES5 ES3 ES1 to ES5 Only displayed...

Страница 18: ...nd displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays measured value of outdoor air temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA HUM nn 0 to 100 OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of...

Страница 19: ... 1 heat and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2 is not used Set for HEATING ventilation MIN POS H 4 4 V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT HIGH SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used IF using 2 speed ...

Страница 20: ...ITION Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 to 3000 ppm increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0 h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been acti...

Страница 21: ... A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux setting is NONE not action taken ERV 24 Vac out Turns on or signals an ERV that the conditions are not good for economizing but are for ERV operation SYS 24 Vac out Issues a system alarm Alarms displ...

Страница 22: ...eturn to Minimum Damper position if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan mo tors will be energized by the economizer control as the dampers open above the EXH1 SET setpoint and will be de energized as the dampers close below the EXH1 SET setpoint For single speed unit Damper movement from full closed to full open or vice ...

Страница 23: ...V 24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MIN POS H W CO2 Sensor CLOSED FROM VENTMIN L TO VENTMAX L FROM VENTMIN L TO VENTMAX L FROM VENTMIN H TO VENTMAX H FROM VENTMIN H TO VENTMAX H ...

Страница 24: ...enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset in temperature and humidity for each sensor connected to the economizer Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setp...

Отзывы: