TROUBLESHOOTING

For a list of common operating issues and concerns see Table 15.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any power

loss or interruption, as all settings are stored in the economizer

controller’s non-volatile flash memory.

NOTE: If power goes below 18 Vac, the W7220 module assumes

a  power  loss  and  the  5-minute  power  up  delay  will  become

functional when power returns above 18 vac.

Alarms

The economizer module provides alarm messages that display on

the 2-line LCD.

NOTE: Upon power up, the module waits several seconds before

checking  for  alarms.  This  allows  time  for  all  the  configured

devices (e.g. sensors, actuator) to become operational.

If one or more alarms are present and there has been no keypad

activity  for  at  least  5  minutes,  the Alarms  menu  displays  and

cycles through the active alarms.

The Alarms menus can be navigated at any time. See Table 11 for

the Alarms menu.

Clearing Alarms

Once  the  alarm  has been  identified and the cause has been re

-

moved (e.g. replaced faulty sensor). They can be cleared from the

display.

To clear an alarm, perform the following: 

1. Navigate to the desired alarm. 

2. Press the 

 button. 

3. ERASE? displays. 
4. Press the 

 button. 

5. ALARM ERASED displays. 
6. Press the 

 (Menu Up/Exit) button to complete the action

and return to the previous menu.

NOTE: If the alarm still exists after being cleared, it will redisplay

within 5 seconds.

 

Table 15 — 

Operating Issues and Concerns

ISSUE OR CONCERN

POSSIBLE CAUSE AND REMEDY

My outdoor temperature reading on the STATUS menu is not 

accurate

Check the sensor wiring:

•  Enthalpy sensors are to be wired to the S-Bus terminals.

•  Temperature sensors are to be wired to the OAT and MAT terminals.

If my enthalpy sensor drifts in accuracy over time, can I 

recalibrate it?

The sensor cannot be re-calibrated in the field; however, a menu item under the 

ADVANCED menu allows input of a limited offset in temperature and humidity for each 

sensor connected to the economizer.

Will I be able to see the LCD screen when it is in the unit?

The LCD screen has a backlight that is always illuminated.

What is a good setpoint for the Mixed Air Temperature (MAT)?

The mixed air temperature is the temperature of air to supply to the space. In a 

commercial building, this is between 50 and 55°F (10 to 13°C). The mixed air is the 

mixing of the return air and the outdoor air.

I am using enthalpy sensors. Why did the control ask me to 

input a dry bulb changeover temperature?

In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in 

the control is to default to the temperature sensor in the enthalpy sensor.

In checkout, the outdoor damper closes when I command it to 

open.

Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper 

should drive open or closed with the return air damper having the opposite effect.

How do I set my minimum position when using a CO

2

 sensor?

The minimum position is set using the VENTMIN and VENTMAX setup in the 

SETPOINTS menu. VENTMIN is the minimum ventilation required when using an 

occupancy sensor and VENTMAX is the minimum ventilation when not using an 

occupancy sensor for Demand Controlled Ventilation. The VENTMAX position is set 

the same as with the potentiometer on the analog economizers and is the output 

voltage to the damper actuator. The range is 2 Vdc closed OA damper and 10 Vdc 

open OA damper.

What if my damper does not go completely closed in the 

checkout operation?

Check the damper linkage or hub to make sure the damper is able to close completely.

Does the economizer save my program values if the unit 

loses power?

Yes, once the changes are stored in the controller they will be stored until they are 

changed by the operator.

If the unit is left in checkout, how long will the unit stay in 

checkout mode without input?

The unit will remain in checkout for 10 minutes, then return to normal operation.

Содержание 547J

Страница 1: ...in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will ...

Страница 2: ... Table 4 for package contents See Table 5 for sensor usage IMPORTANT These economizers meet all the economizer requirements as specified in ASHRAE 90 1 IECC and California s Title 24 Economizer must be installed square to avoid damper leakage or damper binding Squareness tolerance is 1 32 in IMPORTANT Read these instructions completely before attempting to install the accessory economizer Table 1 ...

Страница 3: ...r 1 50HE403859 2 green wire harness for mixed air temperature sensor 1 48TMHSRSE A20 4 Wire Harness 1 Hood Assembly with Top and 2 Sides 1 Hood Divider 1 Hood Filter Divider 2 Aluminum Filters 1 Hardware Bag Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dry bulb sensor is factory installed...

Страница 4: ...0 pin female plug from the controller harness to ECON on the CTB See Fig 10 and page 9 14 Connect the White wire from the controller harness to the W1 terminal on the CTB See Fig 10 and page 9 15 Connect the red and brown wires from the controller harness to the CTB See Fig 11 and page 9 The red wire connects to R on the CTB and the brown wire connects to C 16 Locate the green wire with yellow str...

Страница 5: ... Some control box configurations may differ Fig 7 Mount Controller Assembly in Unit Control Box Fig 8 Unplug ECON Plug from Central Terminal Board CTB HVAC Unit Filters Insert Screw in EconoMi er X Flanges Wiring Harness EconoMi er X Unit Filter Rack Unit Base Economi er X Hold Down Tab Economi er X Rear Flange Economi er X Rooftop Unit s 12 Pin Male Plug EconoMi er X 12 Pin Female Plug Indoor Fan...

Страница 6: ...10 Connect 10 Pin Plug to Central Terminal Board Fig 11 Connect Red and Brown Wires to Central Terminal Board Fig 12 Connect Ground Wire From Controller Central Terminal Board White Wire 10 Pin Female Plug from Controller Central Terminal Board ...

Страница 7: ...d Connect Mixed Air Sensor Fig 16 Connect Pink and Violet Wires in Indoor Blower Section 4 pin Male Plug From Controller 48TMHSRSE A20 Harness Control Box 48TMHSRSE A20 Harness Indoor Blower Section Brown and Orange wires from 48TMHSRSE A20 Harness Indoor Blower Mixed Air Temperature Sensor 50HE403589 2 Green Wire Harness Pink and Violet Wires from 48TMHSRSE A20 Harness Indoor Blower ...

Страница 8: ...A01 30 37 17 43 19 05 29 50 55 CRECOMZR069A01 40 37 22 28 24 48 36 27 80 CRECOMZR071A01 52 92 27 03 33 41 46 92 98 A B C Hood Top And Side Assembly Hood Divider D Hood Filter Divider Hood Top Filter Clip Outside Air Cleanable Aluminum Filter Barometric Airflow Hood Divider EconoMi er X Hood Filter Door 0 500 1000 1500 2000 2500 0 0 05 0 1 0 15 0 2 0 25 0 3 RELIEF FLOW CFM RETURN DUCT STATIC PRESSU...

Страница 9: ... one end and terminals on the other end Connect the plug from this harness to the MAT sensor See Fig 15 Connect the 2 spade terminals on the 50HE403859 harness to orange and brown wires in the indoor blower section wire bundle 9 Follow steps 21 through 25 earlier in these instructions Mixed Air Sensor Field Mount on Indoor Blower 1 HH79AH001 HONEYWELL C7250 Dry Bulb Outside Air Sensor 12 Pin Femal...

Страница 10: ...g 24 Remove Complete Harness Factory Attached to W7220 Controller Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units Fig 26 Photo of 48LCHSRADH A00 W7220 Controller Harness Shipped with 48 50LC 07 12 Units ...

Страница 11: ...11 Fig 27 48LCHSRADH A00 W7220 Controller Harness Shipped With 48 50LC 07 12 Units ...

Страница 12: ...ld is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220 controller from the Carrier factory is removed and not used with 48 50LC 07 12 units ...

Страница 13: ...for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081 Dimensional Connection and Switching Information LEGEND Default Setting OFF OFF OFF IMPORTANT To use the HH57AC081 sensor for outside air sensor the dip switches on the sensor must be set to OFF OFF OFF See Table 8 ECONOMIZING AVAILABLE NOT AVAILABLE ENTHALPY RA HUM RH RA TEMP TEMPERATURE ABSOLUTE HUMIDITY ES5 ES4 ES3 ES2 ES1 HL P1 T RH ...

Страница 14: ...value at 75 F and 50 relative humidity As an example at approximately 6 000 foot elevation the fixed enthalpy limit is approximately 30 7 Btu lb Demand Controlled Ventilation DCV Refer to EconoMi er X wiring diagrams Fig 23 and 28 and DCV instructions if demand control ventilation CO2 sensor is used CO2 sensor will wire into the blue and black connections at the controller as shown in Fig 23 28 an...

Страница 15: ... that is acceptable to some codes is an annunciator light visible by service personnel See Fig 34 for typical wiring to the controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired For Remote FDD Fig 34 Annunciator Light Wired for Remote FDD C R AUX2 1 OCC E GND EXH1 AUX1 0 Y2 I Y2 O Y1 I Y1 O C R W7220 ECONOMIZER U1 U1 R Rc C A L A TH8321R OR TH8321WF SUB BASE MAT Controller...

Страница 16: ...nu parameter 10 Press the Menu Up Exit button to return to the previous menu Menu Structure Refer to Table 10 for summarized standard settings Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The menus in display order are STATUS SETPOINTS SYSTEM SETUP ADVANCED SETUP CHECKOUT ALARMS PROGRAMMING W7220 CONTROLLER The next several pages detail the differ...

Страница 17: ...ble 10 Standard W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F 53 F 38 to 70 F LOW T LOCK 32 F 45 to 80 F 32 F 45 to 80 F DRYBLB SET 63 F 48 to 80 F 63 F 48 to 80 F Only displayed if using single DB OA sensor ENTH CURVE ES3 ES1 to ES5 ES3 ES1 to ES5 Only displayed...

Страница 18: ...nd displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays measured value of outdoor air temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA HUM nn 0 to 100 OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of...

Страница 19: ... 1 heat and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2 is not used Set for HEATING ventilation MIN POS H 4 4 V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT HIGH SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used IF using 2 speed ...

Страница 20: ...ITION Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 to 3000 ppm increment by 50 CO2 ppm span to match CO2 sensor STG3 DLY 2 0 h 0 min 5 min 15 min then 15 min intervals Up to 4 h or OFF COOLING STAGE 3 DELAY Delay after stage 2 for cool has been acti...

Страница 21: ... A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux setting is NONE not action taken ERV 24 Vac out Turns on or signals an ERV that the conditions are not good for economizing but are for ERV operation SYS 24 Vac out Issues a system alarm Alarms displ...

Страница 22: ...eturn to Minimum Damper position if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan mo tors will be energized by the economizer control as the dampers open above the EXH1 SET setpoint and will be de energized as the dampers close below the EXH1 SET setpoint For single speed unit Damper movement from full closed to full open or vice ...

Страница 23: ...V 24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MIN POS H W CO2 Sensor CLOSED FROM VENTMIN L TO VENTMAX L FROM VENTMIN L TO VENTMAX L FROM VENTMIN H TO VENTMAX H FROM VENTMIN H TO VENTMAX H ...

Страница 24: ...enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset in temperature and humidity for each sensor connected to the economizer Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always illuminated What is a good setp...

Отзывы: