background image

17

IV. COMPRESSOR LOCKOUT DEVICE

The compressor lockout (CLO) device prevents the compres-
sor from starting or running in a high pressure, loss-of-
charge or freezestat open situation. Reset the CLO device by
setting the thermostat to eliminate cooling demand and
return it to the original set point. If the system shuts down
again for the same fault, determine the possible cause before
attempting to reset the CLO device.

V. PRELIMINARY OIL CHARGE (541A)

The compressor is factory charged with oil (see Table 1).
When oil is checked at start-up, it may be necessary to add or
remove oil to bring it to the proper level. Add oil only if
necessary to bring oil into view in sight glass. Use only
Bryant-approved compressor oil. 
One recommended oil
level adjustment method is as follows:

A. Add Oil

Close suction service valve and pump down crankcase to
2 psig. Wait a few minutes and repeat until pressure remains
steady at 2 psig. Remove oil fill plug above the sight glass,
add oil through plug hole, and replace plug. Run compressor
for 20 minutes and check oil level.

NOTE: 

Use only Bryant-approved compressor oil. Approved

sources are:

Petroleum Specialties, Inc.. . . . . . . . . . . . . . . . . . . Cryol 150A
Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capella WF-32
Witco Chemical Co.. . . . . . . . . . . . . . . . . . . . . . . . .Suniso 3GS

Do not use oil that has been drained out, or oil that has been
exposed to atmosphere.

B. Remove Oil

Pump down compressor to 2 psig. Loosen the 

1

/

4

-in. pipe plug

at the compressor base and allow the oil to seep out past the
threads of the plug. Retighten plug when level is correct.

NOTE: 

The crankcase is slightly pressurized. Do not remove

the plug, or the entire oil charge will be lost.

Small amounts of oil can be removed through the oil pump
discharge connection while the compressor is running.

VI. START UNIT

The field disconnect is closed, the fan circuit breaker is
closed, and the space thermostat is set above ambient so that
there is no demand for cooling. Only the crankcase heater
will be energized.

Next, close the compressor circuit breaker and then reset
space thermostat below ambient so that a call for cooling is
ensured.

NOTE: 

Do not use circuit breaker to start and stop the com-

pressor except in an emergency.

After starting, there is a delay of at least 3 seconds before
compressor starts.

VII. ADJUST REFRIGERANT CHARGE

Refer to Charging Charts Fig. 19A-19C and Table 8. Do not
exceed maximum refrigerant charge. Vary refrigerant until
the conditions of the chart are met. Note that charging
charts are different from type normally used. Charts are
based on charging the units to the correct subcooling for the
various operating conditions. Accurate pressure gage and
temperature sensing device are required.

Connect the pressure gage to the service port on the liquid
line service valve. Mount the temperature sensing device
on the liquid line, close to the liquid line service valve and
insulate it so that outdoor ambient temperature does not
affect the reading. Indoor airflow must be within the normal
operating range of the unit. Operate unit a minimum of
15 minutes. Ensure pressure and temperature readings have
stabilized. Plot liquid pressure and temperature on chart
and add or reduce charge to meet curve. Adjust charge to
conform with charging chart, using the liquid pressure and
temperature to read chart.

If the sight glass is cloudy, check refrigerant charge again.
Ensure all fans are operating. Also ensure maximum allow-
able liquid lift has not been exceeded. If charged per chart
and if the sight glass is still cloudy, check for a plugged filter
drier or a partially closed solenoid valve. Replace or repair,
as needed.

VIII. CHECK HEATING CYCLE OPERATION

Place thermostat selector switch at HEAT and reset the
space set point above ambient temperature so that a call for
heating is ensured. Compressor will start within 5 minutes.
Observe system operation.

IX. CHECK COMPRESSOR OIL LEVEL (541A)

After adjusting the refrigerant charge, allow the system to
run fully loaded for 20 minutes. Running oil level should be
within view in the crankcase sight glass. Stop compressor at
the field power supply disconnect and check the crankcase
oil level. Add oil only if necessary to bring the oil into view in
the sight glass. If oil is added, run the system for an addi-
tional 10 minutes, then stop and check oil level. If the level
remains low, check the piping system for proper design for oil
return; also check the system for leaks.

If the initial check shows too much oil (too high in the sight
glass) remove oil to proper level. See Preliminary Oil Charge
section for proper procedure for adding and removing oil.

When the above checks are complete, repeat the procedure
with the unit operating at minimum load conditions. Unload
the compressor by disconnecting the field-control circuit lead

at TB2 

 .

Reconnect the field-control circuit lead when checks are
complete.

X. FINAL CHECKS

Ensure all safety controls are operating, control panel covers
are on, and the service panels are in place.

Table 8 — Maximum Refrigerant Charge

CAUTION: 

 

Never charge liquid into the low-

pressure side of system. Do not overcharge. During
charging or removal of refrigerant, be sure indoor-fan
system is operating.

CAUTION: 

 Charge unit on cooling cycle only. If

unit is charged on heating cycle, overcharging may
occur.

UNIT

R-22

(lb)

575B

072

27.0

575C

090

34.2

120

34.2

541A

180

62.0

Y2

Содержание 541A

Страница 1: ...ow clearance wiring refrig erant piping and servicing unit See Fig 1 3 for unit dimensions Figure 4 shows typical component locations for 541A180 units Locate unit so that outdoor coil airflow is unre...

Страница 2: ...it securely to pad or supports after unit is in position and is level Be sure to mount unit level to ensure proper oil return to compressors Mounting holes on unit can be used to secure unit to vibrat...

Страница 3: ...3 Fig 2 575C090 120 Unit Dimensions...

Страница 4: ...lows local codes or jurisdictions may prevail Side compressor 31 2 ft 1067 mm Side opposite compressor 3 ft 914 mm Ends 2 ft 616 mm Top 5 ft 1524 mm WEIGHT DISTRIBUTION UNIT 541A WEIGHT lb kg Total Op...

Страница 5: ...rol Solenoid 4 Compressor Lockout CLO Device 23 Filter Drier 5 Outdoor Fan Relay 14 Control Relay CR3 24 Muffler 6 Outdoor Fan Contactor 15 Liquid Line Solenoid 25 Oil Solenoid 7 Compressor Contactor...

Страница 6: ...ting Charge Typical lb 20 20 22 37 Shipping Charge lb 1 9 9 3 COMPRESSOR Scroll Semi hermetic reciprocating Qty Model 1 SR_75 1 ZR_94 1 ZR125 1 06DF537 Oil Charge oz 88 90 110 128 No Cylinders N A 6 S...

Страница 7: ...drop Complete the refrigerant piping from indoor unit to outdoor unit before opening the liquid and vapor lines at the outdoor unit For specific filter driers see Table 4 D Liquid Line Piping Procedu...

Страница 8: ...ration only Wind baffles field supplied and field installed are recommended for all units with low ambient head pressure control Refer to Low Ambient Control Installation Instructions shipped with acc...

Страница 9: ...ystem is to be shut down for a prolonged period it is recommended that the suction and discharge valves be closed to prevent an excessive accumulation of refrigerant in the com pressor oil 3 Terminals...

Страница 10: ...MOCP values are calculated in accordance with the NEC Article 440 2 Motor RLA and LRA values are established in accordance with Underwriters Laboratories UL Standard 1995 3 The 575 v units are UL Can...

Страница 11: ...al Electrical Code NFPA No 70 and in conformance with local codes and authorities having jurisdiction 2 For use with copper conductors only BK Black BL Blue O Orange R Red W White Y Yellow CAUTION Not...

Страница 12: ...IP Equipment GND Ground HC Heater Contactor IFC Indoor Fan Contactor IFM Indoor Fan Motor NEC National Electrical Code TB Terminal Block Fig 11 Wiring Diagram 541A180 Unit With Standard Thermostat and...

Страница 13: ...RCUIT BREAKER 5 HP AND LARGER UNIT WIRING IFM BLK BLK BLK 21 22 23 12 13 11 1 2 3 HTR1 IFC RELAY BOARD 33ZCRLYBRD TSTAT CR Y2 R Y1 C X W1 W2 G Y2 R Y1 C X W1 W2 G CR LEGEND NOTE Use copper conductors...

Страница 14: ...W2 G C X CR LEGEND Do not configure TSTAT for heat pump NOTE Use copper conductors only CR Control Relay Field Supplied EQUIP Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor...

Страница 15: ...g do not exceed 150 psi b Using soap bubbles and or an electronic leak detector test refrigerant piping connections and joints and the indoor coil See Fig 16 c Check for leaks Evacuate and dehydrate e...

Страница 16: ...f the unit power leads 4 Reapply power to the compressor verify correct pressures The suction and discharge pressure levels should now move to their normal start up levels II COMPRESSOR OVERLOAD This...

Страница 17: ...us operating conditions Accurate pressure gage and temperature sensing device are required Connect the pressure gage to the service port on the liquid line service valve Mount the temperature sensing...

Страница 18: ...warm air supplying the conditioned space Defrost mode is terminated when the DFT reaches 65 F D Air Circulation When the fan switch is at FAN ON the indoor air fans oper ate continuously to provide ve...

Страница 19: ...ise the circuit is completed from R to Y2 and the Cooling mode is initiated in Heat Pump B in a similar manner When the thermostat is satisfied the contacts open deener gizing first the Heat Pump B an...

Страница 20: ...pressor 5 Remove screws from compressor mounting plate 6 Remove or disconnect crankcase heater from com pressor base 7 Remove compressor from unit 8 On 541A180 unit remove compressor holddown bolts an...

Страница 21: ...frigerant is then directed to flow through check valve C which is open through the filter drier and into the liquid header assembly 3 The liquid refrigerant is expanded as it passes through the capill...

Страница 22: ...G DEVICE FILTER DRIER CK VALVE C CK VALVE A CK VALVE B FILTER DRIER COMPR CK VALVE B CK VALVE A CK VALVE C LLSV LIQUID HOT GAS GAS AND OIL MUFFLER ACCUMULATOR REVERSING VALVE REFRIGERANT MIXTURE FROM...

Страница 23: ...hich secure tube sheets and replace top cover and rear corner posts 7 Restore unit power B Cleaning and Maintaining E Coated Coils Routine cleaning of coil surfaces is essential to maintain proper ope...

Страница 24: ...struc tions included with the cleaner The optimum solution temperature is 100 F 4 Thoroughly apply Environmentally Sound Coil Cleaner solution to all coil surfaces including finned area tube sheets an...

Страница 25: ...25 TROUBLESHOOTING CHART HEATING CYCLE LEGEND CCH Crankcase Heater N C Normally Closed...

Страница 26: ...Copyright 2004 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 5357 506 TROUBLESHOOTING CHART COOLING CYCLE LEGEND CCH Crankcase Heater TXV Thermostatic Expansion Valve...

Страница 27: ...ALL WIRING TERMINALS including main power supply TIGHT Y N ______________ HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS Y N ______________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM...

Страница 28: ...WING OIL LEVEL IN VIEW Y N NOTES ______________________________________________________________________________________________________________ ________________________________________________________...

Отзывы: