CAUTION:
Be sure burner enclosure front is in place
after adjustments have been made.
j. Look through sight glass in burner enclosure and check
burner flame. The burner flame should be clear blue,
almost transparent. (See Fig. 47.)
B.
Set Temperature Rise
CAUTION:
Temperature rise must be within limits specified on unit
rating plate. Recommended operation is at midpoint of
rise or above. Failure to follow this caution may result in
condensing or overheating the heat exchangers.
Furnace must operate within range of temperature rise specified on
the unit rating plate. Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
NOTE:
Temperature rise can be determined for low-fire opera-
tion by placing setup switch SW-2 on control center in the ON
position. For high-heat operation, place setup switch SW-2 in the
OFF position and jumper R-W2 on control center. DO NOT forget
to return setup switch to OFF position and remove R-W2 jumper
upon completion of testing. (See Fig. 25 for switch and terminal
location.)
3. This furnace is capable of automatically providing the
proper airflow to maintain the temperature rise within the
range specified on the unit rating plate. If the temperature
rise is outside this range, proceed as follows:
a. Check gas input for low- and high-heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive restric-
tions causing static pressure greater than 0.5-in. wc.
d. Ensure bypass humidifier switch (BPH) setup switch
SW-3 on control center is in ON position when a bypass
humidifier is used. (See Fig. 25 for switch location.)
e. Check Troubleshooting Guide for Gas-Fired Condensing
Furnaces.
C.
Set Thermostat Heat Anticipator
The thermostat heat anticipator must be set to match the amp draw
of the components in the R-W/W1 circuit. Accurate amp draw
measurements can be obtained at the thermostat subbase terminals
R and W.
Fig. 48 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after the
blower motor has started and furnace is operating in low heat.
TABLE 11—MODEL 355MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT RATE
(Tabulated Data Based on Altitude Up to 2000 ft and 20,000 Btuh High Heat/13,000 Btuh Low Heat Per Burner)
GAS HEAT
VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
0.68
0.70
0.72
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
Orf
No.
Heat
High/Low
860
43
3.7/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
42
3.4/1.5
41
42
3.2/1.4
3.6/1.5
41
42
3.3/1.4
3.7/1.5
41
42
3.4/1.4
3.8/1.6
875
43
3.6/1.5
43
3.7/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
42
3.4/1.4
41
42
3.2/1.3
3.5/1.5
41
42
3.3/1.4
3.6/1.5
890
43
3.5/1.5
43
3.6/1.5
43
3.7/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
42
3.4/1.4
41
42
3.2/1.3
3.5/1.5
905
43
44
3.3/1.3
3.7/1.5
43
3.5/1.4
43
3.6/1.5
43
3.7/1.5
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
42
3.4/1.4
920
43
44
3.2/1.3
3.7/1.5
43
44
3.3/1.4
3.8/1.6
43
3.5/1.4
43
3.6/1.5
43
3.7/1.5
43
3.8/1.5
42
3.2/1.3
42
3.3/1.3
935
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
43
3.5/1.5
43
3.6/1.5
43
3.7/1.5
43
3.8/1.6
42
3.2/1.3
950
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
43
3.4/1.5
43
3.6/1.5
43
3.7/1.5
43
3.8/1.6
965
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
43
3.4/1.5
43
3.5/1.5
43
3.6/1.5
980
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
43
3.4/1.5
43
3.5/1.5
995
44
45
3.2/1.3
3.8/1.6
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
43
3.4/1.4
1010
45
3.7/1.6
44
45
3.2/1.3
3.8/1.6
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
43
44
3.3/1.4
3.8/1.6
1025
45
46
3.6/1.5
3.8/1.6
45
3.7/1.6
44
3.2/1.3
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
43
44
3.2/1.4
3.7/1.6
1040
45
46
3.5/1.5
3.7/1.6
45
46
3.6/1.5
3.8/1.6
45
3.7/1.6
44
3.2/1.3
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
1055
45
46
3.4/1.4
3.6/1.5
45
46
3.5/1.5
3.7/1.6
45
46
3.6/1.5
3.8/1.6
45
3.8/1.6
44
3.2/1.3
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
1070
45
46
3.3/1.4
3.5/1.5
45
46
3.4/1.4
3.6/1.5
45
46
3.5/1.5
3.7/1.6
45
46
3.7/1.5
3.8/1.6
45
3.8/1.6
44
3.2/1.4
44
3.3/1.4
44
3.4/1.4
1085
45
46
47
3.2/1.4
3.4/1.4
3.8/1.6
45
46
3.3/1.4
3.5/1.5
45
46
3.4/1.5
3.6/1.5
45
46
3.6/1.5
3.7/1.6
45
3.7/1.5
45
3.8/1.6
44
3.2/1.4
44
3.3/1.4
1100
46
47
3.3/1.4
3.7/1.6
45
46
3.2/1.4
3.4/1.4
45
46
3.4/1.4
3.5/1.5
45
46
3.5/1.5
3.6/1.5
45
46
3.6/1.5
3.8/1.6
45
3.7/1.6
45
3.8/1.6
44
3.2/1.4
—36—