CONDENSER ONLY RATINGS* (CONTINUED)
SST
° F (° C)
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
55 (12.78)
65 (18.33)
75 (23.89)
85 (29.44)
95 (35.0)
105 (40.56)
115 (46.11)
125 (51.67)
180BNA036****B LOW
30
(---1.11)
TCG
18.80
18.20
17.60
16.80
15.90
14.80
13.70
12.40
SDT
64.30
73.90
83.50
93.00
102.60
112.10
121.60
131.20
KW
0.88
1.05
1.22
1.41
1.61
1.85
2.12
2.44
35
(1.67)
TCG
21.20
20.60
19.90
19.00
18.00
16.90
15.70
14.30
SDT
65.40
74.90
84.50
94.00
103.50
113.00
122.40
131.90
KW
0.87
1.04
1.21
1.39
1.59
1.82
2.09
2.41
40
(4.44)
TCG
23.90
23.10
22.30
21.40
20.30
19.10
17.80
16.30
SDT
66.60
76.10
85.50
95.00
104.40
113.90
123.30
132.70
KW
0.87
1.03
1.20
1.37
1.57
1.80
2.06
2.37
45
(7.22)
TCG
26.70
25.90
25.00
24.00
22.90
21.60
20.20
18.60
SDT
67.90
77.30
86.70
96.10
105.40
114.80
124.20
133.50
KW
0.87
1.03
1.19
1.36
1.55
1.78
2.03
2.34
50
(10.0)
TCG
29.70
28.90
27.90
26.80
25.60
24.20
22.70
21.00
SDT
69.20
78.60
87.90
97.20
106.50
115.80
125.10
134.40
KW
0.87
1.02
1.18
1.35
1.54
1.75
2.01
2.30
55
(12.78)
TCG
33.00
32.10
31.00
29.80
28.50
27.10
25.40
23.60
SDT
70.70
79.90
89.20
98.40
107.60
116.90
126.10
135.30
KW
0.87
1.02
1.17
1.34
1.52
1.73
1.98
2.27
60
(15.56)
TCG
36.50
35.50
34.30
33.10
31.70
30.10
28.40
26.50
SDT
72.20
81.40
90.50
99.70
108.80
118.00
127.10
136.20
KW
0.88
1.02
1.17
1.33
1.51
1.71
1.95
2.24
180BNA048****A HI
30
(---1.11)
TCG
37.80
36.90
35.80
34.60
33.00
31.30
29.20
26.90
SDT
68.90
78.30
87.90
97.30
106.80
116.10
125.50
134.80
KW
1.86
2.14
2.45
2.77
3.13
3.52
3.97
4.48
35
(1.67)
TCG
42.00
41.00
39.90
38.50
36.90
35.00
32.80
30.30
SDT
70.30
79.70
89.20
98.60
107.90
117.20
126.50
135.70
KW
1.89
2.18
2.48
2.81
3.17
3.57
4.02
4.53
40
(4.44)
TCG
46.50
45.50
44.20
42.70
41.00
39.00
36.60
34.00
SDT
71.80
81.20
90.50
99.90
109.20
118.40
127.50
136.70
KW
1.94
2.22
2.52
2.85
3.22
3.62
4.07
4.59
45
(7.22)
TCG
51.40
50.30
48.90
47.30
45.40
43.30
40.80
38.00
SDT
73.50
82.70
92.00
101.20
110.40
119.60
128.70
137.70
KW
1.98
2.27
2.57
2.90
3.26
3.67
4.13
4.65
50
(10.0)
TCG
56.70
55.40
53.90
52.20
50.20
47.90
45.20
42.20
SDT
75.20
84.30
93.50
102.60
111.80
120.80
129.90
138.80
KW
2.03
2.32
2.62
2.95
3.32
3.73
4.19
4.71
55
(12.78)
TCG
62.30
60.90
59.40
57.50
55.30
52.90
50.10
46.80
SDT
76.90
86.00
95.10
104.10
113.20
122.10
131.10
140.00
KW
2.09
2.37
2.67
3.00
3.37
3.78
4.25
4.78
60
(15.56)
TCG
68.30
66.90
65.10
63.10
60.80
58.20
55.20
51.70
SDT
78.80
87.80
96.80
105.70
114.70
123.60
132.40
141.10
KW
2.15
2.43
2.73
3.06
3.43
3.85
4.32
4.84
180BNA048****A LOW
30
(---1.11)
TCG
26.60
25.70
24.70
23.50
22.20
20.70
19.00
17.10
SDT
65.50
75.20
84.80
94.40
104.00
113.50
123.00
132.50
KW
1.31
1.54
1.78
2.02
2.29
2.60
2.96
3.36
35
(1.67)
TCG
30.00
29.00
27.80
26.50
25.10
23.40
21.60
19.60
SDT
66.80
76.40
86.00
95.50
105.00
114.50
123.90
133.40
KW
1.31
1.54
1.76
2.00
2.27
2.57
2.92
3.32
40
(4.44)
TCG
33.60
32.50
31.20
29.80
28.20
26.50
24.50
22.40
SDT
68.10
77.60
87.20
96.60
106.10
115.50
124.90
134.30
KW
1.31
1.53
1.75
1.99
2.25
2.54
2.88
3.28
45
(7.22)
TCG
37.60
36.30
34.90
33.40
31.70
29.80
27.70
25.40
SDT
69.50
79.00
88.40
97.90
107.20
116.60
125.90
135.20
KW
1.31
1.53
1.74
1.97
2.23
2.52
2.85
3.24
50
(10.0)
TCG
41.90
40.50
39.00
37.30
35.40
33.40
31.10
28.60
SDT
71.10
80.40
89.80
99.20
108.50
117.70
127.00
136.10
KW
1.32
1.53
1.74
1.96
2.21
2.49
2.82
3.20
55
(12.78)
TCG
46.50
45.00
43.30
41.50
39.40
37.20
34.80
32.10
SDT
72.70
82.00
91.30
100.50
109.70
118.90
128.00
137.10
KW
1.33
1.53
1.73
1.95
2.19
2.47
2.79
3.16
60
(15.56)
TCG
51.50
49.80
48.00
46.00
43.80
41.40
38.70
35.90
SDT
74.40
83.60
92.80
102.00
111.10
120.20
129.20
138.20
KW
1.35
1.54
1.73
1.94
2.18
2.45
2.76
3.12
See notes on page 19