CONDENSER ONLY RATINGS*
SST
° F (° C)
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
55 (12.78)
65 (18.33)
75 (23.89)
85 (29.44)
95 (35.0)
105 (40.56)
115 (46.11)
125 (51.67)
180BNA024****A HI
30
(---1.11)
TCG
22.50
21.30
20.20
18.90
17.60
16.30
14.90
13.40
SDT
67.50
77.40
87.20
97.00
106.80
116.70
126.60
136.70
KW
1.00
1.16
1.33
1.50
1.69
1.91
2.15
2.44
35
(1.67)
TCG
24.90
23.60
22.30
20.90
19.50
18.10
16.50
15.00
SDT
68.70
78.50
88.20
98.00
107.80
117.60
127.50
137.60
KW
1.02
1.18
1.35
1.52
1.72
1.93
2.18
2.47
40
(4.44)
TCG
27.40
26.00
24.60
23.10
21.50
20.00
18.30
16.60
SDT
70.00
79.70
89.40
99.10
108.80
118.50
128.40
138.50
KW
1.05
1.20
1.37
1.55
1.74
1.96
2.21
2.50
45
(7.22)
TCG
30.10
28.60
27.00
25.40
23.70
22.00
20.30
18.50
SDT
71.30
80.90
90.50
100.20
109.80
119.60
129.40
139.40
KW
1.07
1.23
1.39
1.57
1.76
1.99
2.24
2.53
50
(10.0)
TCG
33.10
31.40
29.70
27.90
26.10
24.20
22.40
20.40
SDT
72.60
82.10
91.70
101.30
111.00
120.60
130.40
140.40
KW
1.09
1.25
1.41
1.59
1.79
2.01
2.27
2.57
55
(12.78)
TCG
36.20
34.40
32.50
30.60
28.60
26.60
24.60
22.50
SDT
74.00
83.50
93.00
102.50
112.10
121.80
131.50
141.40
KW
1.12
1.28
1.44
1.62
1.82
2.04
2.30
2.61
60
(15.56)
TCG
39.60
37.60
35.50
33.50
31.30
29.20
27.00
24.70
SDT
75.50
84.90
94.30
103.80
113.40
122.90
132.60
142.40
KW
1.15
1.31
1.47
1.65
1.85
2.08
2.34
2.64
180BNA024****A LOW
30
(---1.11)
TCG
13.40
13.10
12.80
12.30
11.70
11.00
10.20
9.20
SDT
61.90
71.70
81.50
91.20
101.00
110.70
120.40
130.10
KW
0.58
0.71
0.84
0.99
1.14
1.31
1.52
1.75
35
(1.67)
TCG
15.20
14.90
14.50
13.90
13.30
12.60
11.70
10.70
SDT
62.80
72.60
82.30
92.00
101.70
111.40
121.00
130.70
KW
0.59
0.72
0.86
1.00
1.15
1.33
1.53
1.77
40
(4.44)
TCG
17.10
16.70
16.30
15.80
15.10
14.30
13.30
12.20
SDT
63.70
73.50
83.20
92.90
102.50
112.20
121.80
131.40
KW
0.61
0.74
0.87
1.01
1.16
1.34
1.54
1.78
45
(7.22)
TCG
19.10
18.80
18.30
17.70
17.00
16.10
15.10
13.90
SDT
64.70
74.40
84.10
93.80
103.40
113.00
122.60
132.10
KW
0.62
0.75
0.88
1.02
1.18
1.35
1.56
1.79
50
(10.0)
TCG
21.40
21.00
20.50
19.90
19.10
18.10
17.10
15.80
SDT
65.80
75.50
85.10
94.70
104.30
113.80
123.40
132.90
KW
0.65
0.77
0.90
1.04
1.19
1.37
1.57
1.80
55
(12.78)
TCG
23.80
23.40
22.80
22.20
21.30
20.30
19.20
17.80
SDT
66.90
76.60
86.10
95.70
105.20
114.80
124.20
133.70
KW
0.67
0.79
0.92
1.05
1.20
1.38
1.58
1.82
60
(15.56)
TCG
26.30
25.90
25.40
24.60
23.70
22.70
21.40
20.00
SDT
68.10
77.70
87.30
96.80
106.30
115.70
125.20
134.60
KW
0.70
0.81
0.94
1.07
1.22
1.39
1.60
1.83
180BNA036****B HI
30
(---1.11)
TCG
29.00
28.10
27.00
25.80
24.50
23.10
21.50
19.70
SDT
67.10
76.70
86.20
95.70
105.20
114.60
124.10
133.50
KW
1.38
1.58
1.80
2.02
2.26
2.52
2.81
3.14
35
(1.67)
TCG
32.20
31.20
30.10
28.80
27.40
25.80
24.10
22.30
SDT
68.40
77.90
87.30
96.80
106.20
115.60
125.00
134.40
KW
1.41
1.61
1.82
2.05
2.29
2.55
2.85
3.18
40
(4.44)
TCG
35.70
34.60
33.40
32.00
30.50
28.90
27.00
25.10
SDT
69.80
79.20
88.60
98.00
107.30
116.70
126.00
135.30
KW
1.44
1.64
1.86
2.08
2.32
2.59
2.89
3.22
45
(7.22)
TCG
39.40
38.30
37.00
35.50
33.90
32.10
30.20
28.10
SDT
71.20
80.50
89.90
99.20
108.50
117.80
127.00
136.30
KW
1.48
1.68
1.89
2.11
2.36
2.63
2.93
3.27
50
(10.0)
TCG
43.50
42.20
40.80
39.20
37.50
35.60
33.60
31.30
SDT
72.70
82.00
91.30
100.50
109.80
119.00
128.10
137.30
KW
1.52
1.72
1.93
2.15
2.40
2.67
2.97
3.31
55
(12.78)
TCG
47.80
46.40
44.90
43.30
41.40
39.40
37.20
34.80
SDT
74.30
83.50
92.70
101.90
111.10
120.20
129.30
138.40
KW
1.56
1.76
1.97
2.19
2.44
2.71
3.02
3.36
60
(15.56)
TCG
52.30
50.90
49.30
47.50
45.60
43.40
41.10
38.50
SDT
76.00
85.10
94.20
103.30
112.40
121.40
130.40
139.40
KW
1.61
1.81
2.02
2.24
2.49
2.76
3.07
3.41
See notes on page 19