Brunata Optuna H 

 

UK-QB101575/29.05.2012

 

Installation Guide 

 

     Pages 6/16 

 

      

Brunata a/s · Vesterlundvej 14 · 2730 Herlev · tlf. +45 77 77 70 00 · fax +45 77 77 70 01 · [email protected] · www.brunata.dk 

2.0 Installation of temperature sensors 

Handle the temperature sensors carefully! The sensor cables are fitted with coloured type labels: 
 

Red: sensor in hot line, blue: sensor in cold line. 
 
The programmed installation location is shown in the information loop. 
 
The free temperature sensor can be installed in a ball valve or in a pocket conforming to the requirements for this 
type of sensor. If the sensor is installed in a pocket, it must be inserted as far as the bottom of the pocket and secured. 
 
For installation in a ball valve, a 5-piece coupling set is enclosed in a separate bag. Make sure the sensor is mounted 
symmetrically. The connecting cables must not be shortened or extended. The maximum cable length is ten meters. 
The sensors should preferably be installed directly immersed. Insert one O-ring in the sensor hole using the mounting 
pin supplied. Only tighten the brass or plastic screw by hand (2-3 Nm); tighten the plug screw with a torque of approx. 
12 Nm. 

 

 
1                      2                                 3                                   4                                   5.1         5.2                  6 
   

Meter type

 

Sensor marking 

Terminal

 

Installation position

 

Energy meter in return line  

Red

 

5 Hot 6 

Forward

 

Blue

 

7 Cold 8 

On meter  

Energy meter in forward line 

 

Red

 

5 Hot 6 

On meter 

Blue

 

7 Cold 8 

Return

 

Cooling meter in return line 

Blue

 

7 Cold 8 

Forward

 

Red

 

5 Hot 6 

On meter

 

Cooling meter in forward line

 

Blue

 

7 Cold 8 

On meter

 

Red

 

5 Hot 6 

Return 

Air conditioning meter in return line 

Red

 

5 Hot 6 

Forward

  

Blue

 

7 Cold 8 

On meter 

Air conditioning meter in forward line

 

Red

 

5 Hot 6 

On meter

 

Blue

 

7 Cold 8 

Return

 

Содержание Optuna H 775

Страница 1: ...s is a Danish owned company We have more than 90 years of experience within developing and producing meters heat cost allocators consumption accounts meter services and substations Today meters are of...

Страница 2: ...MAINS UNIT 7 4 0 EXTENSION MODULES 7 4 1 INSTALLATION OF MODULES 8 4 2 COMMUNICATION MODULES 8 4 2 1 M Bus 8 4 2 2 Communication over radio 9 4 2 3 RS 232 Communication module 9 4 2 4 RS 485 Communica...

Страница 3: ...30 C 150 C The temperature range depends on variant and nominal size The encapsulated variant is to be used if condensation is expected The specified operating ambient conditions are 5 55 C IP54 93 re...

Страница 4: ...0 C or more or if Twater Tambient application as cooling meter or heat cooling meter the integrator must be removed from the meter and installed a sufficient distance away from heat sources A wall hol...

Страница 5: ...2012 Installation Guide Pages 5 16 Brunata a s Vesterlundvej 14 2730 Herlev tlf 45 77 77 70 00 fax 45 77 77 70 01 brunata brunata dk www brunata dk T 5 90 C Twater Tambient T 90 130 C 150 C Twater Ta...

Страница 6: ...s enclosed in a separate bag Make sure the sensor is mounted symmetrically The connecting cables must not be shortened or extended The maximum cable length is ten meters The sensors should preferably...

Страница 7: ...r supply for up to one year The LCD readings on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still func...

Страница 8: ...ion module can be used in radio operation The protocol is different for each of the two channels and is preset ex works but can be set to customer specific requirements using the IZAR Set software Eac...

Страница 9: ...h GPRS LAN The protocol corresponds to the Open Metering or HYD standard and is encrypted Reading modes Brunata DriveBy Brunata LiveNetwork 4 2 3 RS 232 Communication module The RS232 communication mo...

Страница 10: ...input 2 as I2 and Pulse inputs are programmable IZAR SET for a value of 1 2 5 10 25 100 250 1000 2500 litres per pulse Possible units are all the energy units available in the meter the volume unit m...

Страница 11: ...outputs are marked on the terminal strip as O1 and or O2 and and in the display as Out1 and Out2 External power supply Vcc 3 30 V DC Output current 20 mA with a residual voltage of 0 5 V Open collect...

Страница 12: ...logue outputs which can be programmed as desired using the IZAR SET software The outputs are marked on the terminal strip as 1 and 2 with the respective polarity and Passive external power supply 10 3...

Страница 13: ...nergy amounts running days water amounts current temperatures maximum values The energy meter has six different display loops Main loop day loop information loop pulse input output loop tariff loop an...

Страница 14: ...press three seconds switches to the next display loop The Energy window sequence 1 1 in the main loop is the basic display The meter automatically switches off the display to save power if the button...

Страница 15: ...he error log Error display Error description C 1 Basic parameter error in flash or RAM E 1 Temperature range exceeds 19 9 C 199 9 C Sensor short circuit sensor break E 3 Forward and return sensor reve...

Страница 16: ...ta dk www brunata dk 8 0 Declaration of conformity for devices after MID These products conform to the essential requirements of the following directives EMC Directive 2004 108 EC R TTE Directive 1999...

Отзывы: