3
Operating instructions
General requirements
Please note that the small basic stove must be installed taking the specific state
building regulations into account, "any national or local rules, general specifications
and application rules must be observed"
Please consult your competent district master chimney sweep about this prior to
installation.
He will advise you on the suitable chimney as well as all other requirements which
are of relevance for the setup and commissioning of your basic stove. A sufficient
combustion air supply must be ensured in particular, especially with a well sealed
building shell, flat ventilation systems etc. in order to guarantee smooth operation.
Your chimney sweep will be able to help here too. He will also check that the
fireplace has been connected properly.
The small basic stove described here is tested according to
DIN EN 15250:2007,
15a B-VG Austria)
and may be attached to a chimney with multiple connections
provided that the chimney's technical conditions allow this. If the basic stove is
attached to a chimney with multiple connections, the springs in the firebox door must
not be removed. This ensures that the door closes automatically after adding more
fuel and thus the supply pressure of the chimney is not affected.
Installation site / fire protection regulations
When setting up the small basic stove, the valid fire protection regulations of the
German Fire Code Ordinance (FeuVo) must be observed. The specified minimum
distances to combustible objects and walls must be maintained and the flooring must
also be protected.
Note on setting up the fireplace only on surfaces with a sufficient load bearing
capacity. If the load bearing capacity is not sufficient, suitable measures must be
taken (e.g. a panel for load distribution) to remedy this. Safety distances:
300 m
m
R
ear
w
al
l
Combustible components
250 mm
Side
C
om
bus
tibl
e c
om
pone
nt
s
800 m
m
Fr
ont
Combustible
components