4. Commissioning
4.1 Presetting
The control units in gas condensing boilers of the Paramount three/four 60-115
series are preset not to actuate a modulating pump.
4.2 Use as heating circuit pump
Settings if used as a heating circuit pump
If the pump HEP is used as a heating circuit pump, under prog. no. 6085, make the
setting shown in the following table.
Function
Prog. no.
Setting level
Setting
Configuration
PWM output P1
6085
E
Heating circuit pump HC1 Q2
or
Heating circuit pump HC2 Q6
or
Heating circuit pump HC3
Q20
1) Alternative setting if heating circuit 2 is to be supplied
2) Alternative setting if heating circuit 3 is to be supplied
Set the minimum and maximum pump speeds in accordance with the system con-
figuration under menu item
Heating circuit 1-heating circuit 3
Function
Prog. no.
Setting level
Setting
Heating circuit 1
Pump speed min
882
E
Pump speed max
883
E
Heating circuit 2
Pump speed min
1182
E
Pump speed max
1183
E
Heating circuit 3
Pump speed min
1482
E
Pump speed max
1483
E
Commissioning
7660118-03
07.16
Variable speed pump HEP 25-180-10
27
GB
Содержание HEP 25-180-10
Страница 117: ...2 重 2 1 HEP 25 180 10 WGB 50 110 E BGB 50 110 H 2 2 重 重 重 7660118 03 07 16 HEP 25 180 10 117 CN ...
Страница 118: ...3 3 1 重 1 HEP 25 180 10 1 2 1 2 PWM 118 HEP 25 180 10 7660118 03 07 16 CN ...
Страница 120: ...3 4 WGB 50 110 重 HEP 25 180 10 3 5 HEP 3 3 1 WGB 1 2 1 3 Brötje ADH 1 120 HEP 25 180 10 7660118 03 07 16 CN ...
Страница 134: ...Raum für Notizen Space for notes Notices Appunti Plads til notater Nota s Notatki Místo pro poznámky 掯 134 07 16 ...
Страница 135: ...07 16 135 Raum für Notizen Space for notes Notices Appunti Plads til notater Nota s Notatki Místo pro poznámky 掯 ...