5-3
Section 5 Transducer Blocks
Installation and Operation Manual
X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG
December, 2017
Model MT3809G F
OUNDATION
TM
Fieldbus
Index
Sub Index
Parameter Name
Description
Data Type
Valid Values
Initialized
Value
Read only or
Read/W
rite
Table 5-1
Parameters of the Analog Input Transducer Block (continued)
29
MODEL_NUMBER
Model number of the assembled device
ASCII
Max 20 chars
Calibrated
Value
Read/
Write
30
RES_TOTALIZER
A resettable totalizer independent of the function block
30
1
RES_TOTALIZER.UOM
The units of measurement which the totalizer will use
U16
Supported UOMs
Gallon
Read/
Write
30
2
RES_TOTALIZER.VALUE
The value of the resettable totalizer
Float
0.0 Read
31
RESET_RES_TOTALIZER
Used to reset the resettable totalizer
U8
(0) Idle
(1) Reset
Idle
Read/
Write
32 RES_TOT_DIG_DEC
Setting of max number of integer digits before automatic
reset
U8 0
to
7
2
Read/
Write
33 INV_TOTALIZER
A inventory totalizer which is independent of the function
block
33
1
INV_TOTALIZER.UOM
The units of measurement used for the totalizer
U16
Supported UOMs
Gallon
Read/
Write
33
2
INV_TOTALIZER.VALUE
The value of the inventory totalizer
Float
0.0 Read
34 INV_TOT_DIG_DEC
Setting of max number of integer digits before automatic
reset
U8 0
to
7
2
Read/
Write
35 LO_FLOW
The settings for the low flow alarm with a dedicated
alarm output on the transmitter
35
1
LO_FLOW.ALARM_EN
Enables or disables the low flow alarm
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
35 2 LO_FLOW.ALARM_TYPE
A non latching alarm type will clear the alarm if the flow
is above the low flow setting
U8
(0) Non-latched
(1) Latched
(0) Non-latched
Read/
Write
35 3 LO_FLOW.ALARM_LIMIT
The value which will cause the alarm if the flow value
falls below this value
Float
9.99
Read/
Write
35 4
LO_FLOW.
ALARM_LIMIT_DELAY
The time a flow needs to be below the setting before the
alarm is triggered
U8
0 to 255 Seconds
0
Read/
Write
36 HIGH_FLOW
The settings for the high flow alarm with a dedicated
alarm output on the transmitter
36
1
HIGH_FLOW.ALARM_EN
Enables or disables the high flow alarm
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
36 2
HIGH_FLOW.
ALARM_TYPE
A non latching alarm type will clear the alarm if the flow
is below the high flow setting
U8
(0) Non-latched
(1) Latched
(0) Non-latched
Read/
Write
36 3
HIGH_FLOW.
ALARM_LIMIT
The value which will cause the alarm if the flow value
rises above this value
Float
90.0
Read/
Write
36 4
HIGH_FLOW.
ALARM_LIMIT_DELAY
The time a flow needs to be above the setting before the
alarm is triggered
U8 0
to
255
0
Read/
Write
37 PULS_OUT_CFG
This alarm is used if the configuration for the pulse
output is wrong. This alarm has no physical output on
the transmitter
37 1
PULS_OUT_CFG.
ENABLE
Enables or disables the pulse output configuration alarm
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
37 2 PULS_OUT_CFG.TYPE
A non latching alarm type will clear the alarm if
configuration is corrected.
U8
(0) Non-latched
(1) Latched
(1)Latched
Read/
Write
38 PULS_OUT_OVERRUN
This alarm is used if the pulse output cannot keep up
with the pulse algorithm
38 1
PULS_OUT_ OVERRUN.
ENABLE
Enables or disables the pulse output overrun alarm
U8
(0) Disabled
(1) Enabled
(0) Disabled
Read/
Write
38 2
PULS_OUT_ OVERRUN.
TYPE
A non latching alarm type will clear the alarm if overrun
is solved
U8
(0) Non-latched
(1) Latched
(0) Non-latched
Read/
Write
39 DIAG
This alarm is used to inform if a software error has
occurred
39
1
DIAG.ENABLE
Enables or disables the diagnostic alarm
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
39 2 DIAG.TYPE
A non latching alarm type will clear the alarm if the
problem is solved.
U8
(0) Non-latched
(1) Latched
(1)Latched
Read/
Write
40
DB_INIT
This alarm is reserved for future use
40
1
DB_INIT.ENABLE
This alarm is reserved for future use
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
40
2
DB_INIT.TYPE
This alarm is reserved for future use
U8
(0) Non-latched
(1) Latched
(1)Latched
Read/
Write
41
POWER
This alarm is reserved for future use
41
1
POWER.ENABLE
This alarm is reserved for future use
U8
(0) Disabled
(1) Enabled
(1) Enabled
Read/
Write
41
2
POWER.TYPE
This alarm is reserved for future use
U8
(0) Non-latched
(1) Latched
(1)Latched
Read/
Write
42
BROOKS_SERIAL_NUMBER
The serial number assigned to the device
Visible
String
ASCII
Max 32 chars
Calibrated
value
Read/
Write
43
CURRENT_ALARM_STATUS
Bitwise representation of the alarms.
U32
(0) No Alarm
(1) Diag_Alarm
(2) Reserved
(4) Reserved
(8) Flow_High_Alarm
(16) Flow_Low_Alarm
(32) Pulse_Config_Alarm
(64)Pulse_Overrun_Alarm
0 Read
44 ACTIVE_DIAG_STATUS
Bitwise representation of the cause of the diagnostic
alarm
U32
(0) Good
(1) Ram fail
(2) Flash fail
(4) Database fail
(8) Float position fail
(16) Calibration fail
0 Read
45 RESET_ALARM
Function to reset the alarms which are shown active in
current alarm status
U8
(0) Idle
(1) Reset
(0) Idle
Read/
Write
46 PULSE_OUTPUT
Settings to set the pulse output on the transmitter
Table continued on next page.