5-5
Section 5 Transducer Blocks
Installation and Operation Manual
X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG
December, 2017
Model MT3809G F
OUNDATION
TM
Fieldbus
Index
Sub Index
Parameter Name
Description
Data Type
Valid Values
Initialized
Value
Read only or
Read/W
rite
Table 5-1
Parameters of the Analog Input Transducer Block (continued)
56 TEST
Test interface to test the alarm and pulse outputs.
Testing is only possible when in testing mode
56
1
TEST.CONTACT_OUTPUT
Select the first or second alarm output to test
U8
1 to 2
0
Read/
Write
56
2
TEST.ACTION_STATUS
Set the output high or low
U8
0 to 1
0
Read/
Write
56
3
TEST.TEST_PULSE_OUTPUT
Enable the pulse output test
U8
0 to 1
0
Read/
Write
56 4
TEST.
TEST_PULSE_FREQUENCY
Frequency which is used to test the pulse output
Float
0.00 to 100.0
0
Read/
Write
56 5
TEST.TEST_PULSES_COUN
T
Number of pulses before the test sequence is stopped
U32
1 to 100
0
Read/
Write
56
6
TEST.ENTER_LEAVE
This parameter is used to enter or leave the test mode
U8
(0) Leave
(1) Enter
(0) Leave
Read/
Write
57 DISPLAY_SETTINGS
Change the settings to the attached display
57 1
DISPLAY_SETTINGS.
SCREEN_MODE
Enables the view of the flow and the two totalizers
Bit String
(0) None
(1) Flow rate
(2) Resettable totalizer
(4) Inventory totalizer
(1) Flow Rate
Read/
Write
57 2
DISPLAY_SETTINGS.
FLOW_CYCLE_TIME
Time between the screen modes
U32
5
Read/
Write
57 3
DISPLAY_SETTINGS.
UOM_FULLSCALE
The unit of measurement full scale is use to get the best
representation on the display
Float
100.0
Read/
Write
58
SENSOR_ZERO
Sets the magnet sensor to zero for the calibration
U8
(0) Idle
(1) Zero
(0) Idle
Read/
Write