1.3.4 Optional Relay Boards and Speaker Zoning
In addition to the normal alarm zoning, the CIE supports additional programmable relay outputs (non-
supervised) using 8 relay expansion board SUB885 which can be utilised to control ancillary equipment by
independent zones or zone mimic.
If an OWS is used in the FT420, the speaker output can be split into 4 speaker zones using a four
supervised output expansion board SUB886.
1.3.5 Simple Configurations
A user friendly system configuration utility simplifies the installation and on-site service process. Authorised
installers can easily configure all the system parameters via PC configuration software and serial adapter
unit, refer to Chapter 4.
1.3.6 Brooks Alertcom
By adding expansion boards, the FT420 CIE is capable of providing a complete Alertcom manual and
automatic triggering system which includes the following features:
•
Multiple tone and voice messages
A total of up to ten tones and/or voice messages can be activated, based on the system conditions.
•
Visual alarm indications
The Alertcom is capable of providing both audible and visual warnings in alarm and manual
conditions. Its monitored dual strobe output controls the visual indications for both alert and
evacuation conditions separately.
•
Automatic Alertcom system with manual tone selections
Up to eight tones can be broadcasted based on the associated monitored trigger inputs or the manual
selections on the front display. It can be used not only for the emergency warnings, but also for
general message broadcasts, such as the school and lunch bells.
•
PA
Public addressing can be broadcasted
•
Auxiliary audio input
Remote desktop microphone announcements or background music can be broadcasted when the
auxiliary audio input is enabled and the CIE is in quiescent conditions.
1.3.7 Gaseous Extinguishing System
3
The new firmware V2.3, is now able to integrate Brooks Gaseous extinguishing system in the standard
FT420 configuration. The Brooks series of warning signs, local control stations and voice / messages
horns or speakers can be connected to the gas interface module to offer a complete gaseous
extinguishing system as well as detection system. Refer to Chapter 3.10 page 50 and Figure 40 page
77.
3
Software version => V2.3.x must be used