![Brooks Firetracker FT420 Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/brooks/firetracker-ft420/firetracker-ft420_technical-manual_2818733072.webp)
Technical Manual
FT420
– Iss 2.4
72
Module
Feature
Multimeter Probe +
Multimeter Probe -
Expected Resistance
Range (Ohm)
Result
Optional Zone Input 4 TB2
– 7, ZONE4 +
TB2
– 8, ZONE4 -
2.5K
– 5K
Optional Zone Input 5 TB3
– 1, ZONE5 +
TB3
– 2, ZONE5 -
2.5K
– 5K
Optional Zone Input 6 TB3
– 3, ZONE6 +
TB3
– 4, ZONE6 -
2.5K
– 5K
Optional Zone Input 7 TB3
– 5, ZONE7 +
TB3
– 6, ZONE7 -
2.5K
– 5K
Optional Zone Input 8 TB3
– 7, ZONE8 +
TB3
– 8, ZONE8 -
2.5K
– 5K
Optional
Zone Input
Expansion
Board 1
Optional Zone Input 1 TB2
– 1, ZONE1 +
TB2
– 2, ZONE1 -
2.5K
– 5K
Optional Zone Input 2 TB2
– 3, ZONE2 +
TB2
– 4, ZONE2 -
2.5K
– 5K
Optional Zone Input 3 TB2
– 5, ZONE3 +
TB2
– 6, ZONE3 -
2.5K
– 5K
Optional Zone Input 4 TB2
– 7, ZONE4 +
TB2
– 8, ZONE4 -
2.5K
– 5K
Optional Zone Input 5 TB3
– 1, ZONE5 +
TB3
– 2, ZONE5 -
2.5K
– 5K
Optional Zone Input 6 TB3
– 3, ZONE6 +
TB3
– 4, ZONE6 -
2.5K
– 5K
Optional Zone Input 7 TB3
– 5, ZONE7 +
TB3
– 6, ZONE7 -
2.5K
– 5K
Optional Zone Input 8 TB3
– 7, ZONE8 +
TB3
– 8, ZONE8 -
2.5K
– 5K
Optional
Supervised
output
Expansion
Board 1
Optional Supervised
output 1
TB2
– 1, O+
TB2
– 2, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 2, O-
TB2
– 1, O+
24V output: 40K
– 54K
Optional Supervised
output 2
TB2
– 3, O+
TB2
– 4, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 4, O-
TB2
– 3, O+
24V output: 40K
– 54K
Optional Supervised
output 3
TB2
– 5, O+
TB2
– 6, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 6, O-
TB2
– 5, O+
24V output: 40K
– 54K
Optional Supervised
output 4
TB2
– 7, O+
TB2
– 8, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 8, O-
TB2
– 7, O+
24V output: 40K
– 54K
Optional
Supervised
output
Expansion
Board 2
Optional Supervised
output 1
TB2
– 1, O+
TB2
– 2, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 2, O-
TB2
– 1, O+
24V output: 40K
– 54K
Optional Supervised
output 2
TB2
– 3, O+
TB2
– 4, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 4, O-
TB2
– 3, O+
24V output: 40K
– 54K
Optional Supervised
output 3
TB2
– 5, O+
TB2
– 6, O+
Speaker: 40K
– 54K
24V output: > 14
TB2
– 6, O+
TB2
– 5, O-
24V output: 40K
– 54K
Optional Supervised
output 4
TB2
– 7, O+
TB2
– 8, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 8, O-
TB2
– 7, O+
24V output: 40K
– 54K
Optional
Supervised
output
Expansion
Board 3
Optional Supervised
output 1
TB2
– 1, O+
TB2
– 2, O-
Speaker: 40K
– 54K
24V output: > 14
TB2
– 2, O-
TB2
– 1, O+
24V output: 40K
– 54K