Figure 37 Zone Configuration Options
4.4.1 Alarm Verification Facility (AVF)
•
AVF Enabled
An alarm condition will not immediately signal an alarm state on the initial detector activation.
The zone with AVF enabled will reset the detector in that zone for the first 16-20 seconds
(reset cycle). The smoke detector will latch on if there is further detection on that detector
within the next verification cycle. This causes the zone alarm condition to remain on. If no
further alarm input was detected during the reset cycle, no alarm conditions will be generated.
•
AVF disabled
If the AVF is disabled, an alarm condition will be generated as soon as an alarm input is
detected.
To select AVF:
C
heck the “Alarm Verification” check boxes for each zone required for the alarm to be verified.
To select
“All” Zones:
•
R
ight click on the “Alarm Verification” heading and
•
Choose
“Set the Feature To all”.
•
Select “Reset the Feature to All” to uncheck all boxes.